65/70 |
FDS...EX
Electrical connections
Type of activation H0-EX
IMPORTANT: Fire damper must be grounded. Wires connecting damper parts, must not be removed
This type of activation mechanism does not have any electrical equipment.
Type of activation H2-EX
IMPORTANT: Risk of electric shock!
Each explosion-proof electrical equipment installed in or on the fire damper must conform to its explosion-proof given
explosive atmospheres according to EN 60079-10.
Fire damper must be grounded. Wires connecting damper parts must not be removed
Switch off the power supply before working on any electrical equipment.
Only qualified electricians are allowed to work on the electrical system.
Microswitch:
Power Supply: AC 125/250 V or DC 12/24 VElectrical Parameters: 3A
NOTES:
• Supply via safety isolation transformer.
• Power consumption must be observed!
Legend
1
Grey cable colour
2
Orange cable colour
3
Pink cable colour
4
White cable colour
5
Red cable colour
6
Brown cable colour (Do not use for type of activation H2-EX)
X:7
Blue cable colour (Do not use for type of activation H2-EX)
Summary of Contents for FDS-3G EX Series
Page 1: ...FDS EX Atex Fire Damper ...
Page 8: ...8 70 FDS EX Product parts ...
Page 27: ...27 70 FDS EX ...
Page 30: ...30 70 FDS EX ...
Page 31: ...31 70 FDS EX ...
Page 35: ...35 70 FDS EX ...
Page 36: ...36 70 FDS EX ...
Page 39: ...39 70 FDS EX ...
Page 40: ...40 70 FDS EX ...
Page 43: ...43 70 FDS EX 5 1 On Out FDS EI90S EX W 1600 H 1000 EI 90 ve i o S a b ...
Page 44: ...44 70 FDS EX ...
Page 48: ...48 70 FDS EX ...
Page 49: ...49 70 FDS EX ...
Page 52: ...52 70 FDS EX ...
Page 53: ...53 70 FDS EX ...
Page 57: ...57 70 FDS EX 5 4 On Out FDS 3G EX 100 100 1200 800 EI 60 ve i o S a b ...
Page 58: ...58 70 FDS EX ...
Page 59: ...59 70 FDS EX ...
Page 63: ...63 70 FDS EX 7 Multi FDS EI90S EX W 1600 H 1000 EI 90 ve i o S b ...
Page 70: ...Systemair DESIGN 2021 04 27 Handbook_FDS_EX_en GB ...