SystemAir fantech ECHO 2800Xi Series Installation, Operation And Maintenance Manual Download Page 7

13

12

Unit components and electrical connections 

(Cont'd)

Power IN
7/8" - 1" 
knockout

Control IN
7/8" - 1" 
knockout

The main power connection of this unit must be preceded by an all pole circuit breaker. The connection from this circuit breaker to the unit main 
power knockout must be run in flexible conduit (field supply & specify) for the reason that the unit electrical connection box is mounted on a hinged 
access panel used to service the fan motors. 

Main power & circuit breaker connection

This unit is equipped with two (2) electronically-commutated (EC) fan motors referred to as SF & SAF (supply air/fan) or EF & EAF (exhaust air/fan)
(see unit wiring diagram). Both fan motors can be accessed by opening the smaller hinged access panel. 

EC fan motor assemblies

The speed of these EC fan motors are controlled by analog outputs from the unit controller. With feedback from the unit’s built in pressure 
transducer modules, the controller will modulate the fan speed in order to maintain the airflow set point. This method of controlling the unit airflow is 
called Constant Air Volume (CAV). More details in the “Pressure transducer modules” section. 

As mentioned in the previous section, this unit is equipped with two (2) pressure transducer modules referred to as Pressure transducer exhaust 
(PTE) and Pressure transducer supply (PTS) (see unit wiring diagram). They are located inside of the unit on the return air side and can be accessed 
by opening the larger hinged access panel.

Pressure transducer modules

Each module has two (2) pressure transducer. 

The first pressure transducer on the PTE module measures the pressure drop over the inlet ring of the exhaust air fan in order to control the fan 
speed. The second one measures the pressure drop over the supply air filter for the dirty filter alarm. 

The first pressure transducer on the PTS module measures the pressure drop over the inlet ring of the supply air fan in order to control the fan 
speed. The second one measures the pressure drop over the exhaust air filter for the dirty filter alarm

More details on the pressure transducers in the “Airflow control” & “Alarm handling” section.

If EFD dampers and/or a BPM module has been supplied with the unit and mounted as per their provided installation instruction, the electrical con-
nection can now be made. 

The outdoor air damper is connected to terminal TB3 10-12 (see unit wiring diagram) using the harness provided with the accessory. 

The exhaust air damper is connected to terminal TB3 10-14 (see unit wiring diagram) using the harness provided with the accessory. 

The BPM module is connected to terminal TB3 10-12 (see unit wiring diagram) using the harness provided with the accessory. 

Wiring the dampers & the BPM module actuators

The dampers and/or BPM module must be installed and wired back to the electrical connection box as indicated above for the unit to 
function properly. Ensure this is done before proceeding.

Unit components and electrical connections 

(Cont'd)

Summary of Contents for fantech ECHO 2800Xi Series

Page 1: ...on of the National Building Code and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components a...

Page 2: ...d with BPM module only 21 o Extended running 23 o Fire alarm 26 o External switch 26 Alarm handling 27 Configuring BACnet MS TP port 1 29 Maintenance 31 Limited warranty 32 Parts list 33 The key to pr...

Page 3: ...clothes dryer kitchen exhaust hoods combustion venting central vacuum system These appliances may cause lint dust or grease to collect in the HRV ERV damaging the unit Location The HRV ERV must be pr...

Page 4: ...used to recirculate indoor air when ventilation is not required See the Recirculation section for more details If a BPM module accessory has been supplied with the unit it should be installed as per...

Page 5: ...ned and sealed to the ducts with proper duct sealant to minimize air leakage Dampers fitted to the ductwork connecting the unit to the outside weather hoods should be adequately insulated in order to...

Page 6: ...esponsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended The amount of air CFM that an HRV ERV will deliver is directly re...

Page 7: ...he return air side and can be accessed by opening the larger hinged access panel Pressure transducer modules Each module has two 2 pressure transducer The first pressure transducer on the PTE module m...

Page 8: ...nting holes 8 Connection block 9 Connection to yellow cable 10 Connection to orange cable 11 Connection to red cable 12 Connection to brown cable 13 Connection to black cable Supplied Cable 10 12 11 1...

Page 9: ...hanges from stopped to starting up 2 The digital outputs for the fresh air damper and the exhaust air damper are activated 3 The exhaust air fan and the supply air fan will start after a preset time N...

Page 10: ...e and time follow the steps below Time settings schedule 1 Time settings Go to Time settings by using the UP DOWN arrow buttons Select by pressing the RIGHT arrow button Temperature Air Control Time s...

Page 11: ...be done when ventilation is not required during a certain period but air circulation is desired Recirculation units equipped with the BPM module only To have the recirculation mode controlled by a dig...

Page 12: ...ow button Manual Auto Settings Configuration Access rights Once the input has been set the recirculation mode can be configured 3 Recirculation Using the UP DOWN arrow buttons locate the use extra tim...

Page 13: ...cess the fields and set values Extended running 0 min Set the time value for extended running to remain active once the extended running input goes from on to off Time in ext running 0 min This field...

Page 14: ...ing the UP DOWN arrow buttons Select by pressing the RIGHT arrow button AI DI UI AO Alarm handling The unit controller comes with preprogrammed alarms to ensure it functions properly and to help troub...

Page 15: ...isplay Follow the steps below to handle active alarms 1 Access the alarm log Press the alarm button to access the alarm log when the red LED is flashing to indicate that an alarm has been triggered On...

Page 16: ...n a large sink bathtub or shower 5 Pour clean tap water through the face of the core facing upward until it runs clear Ensure the entire surface is rinsed 6 Rotate the core so that its other air inlet...

Page 17: ...ges incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to supply r...

Page 18: ...35 34 Notes Notes...

Page 19: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Reviews: