27
26
4 Configuring DI5
From this submenu, use the UP/DOWN arrow buttons to locate DI5 and
select it by pressing the RIGHT arrow button. Press OK again to access
the
NO/NC
field to set the digital input contact to either normally open
(NO) OR normally closed (NC) based on what will be used to trigger the
input.
DI5 :
↑
NO/NC: NO Signal:
Fire alarm
Status:
Off
↓
The external switch digital input can be used to stop the unit remotely. If the external switch input is triggered the unit will initiate the stop sequence
and stop the ventilation. A controller alarm will also appear on the unit external display to indicate that the external switch is active.
External switch
A means of triggering the input will be required (field supplied and specified) and wired to TB3 76 & 4, DI6 & +24VDC respectively (see
wiring diagram). Remember to cut the power to the unit at the all pole circuit breaker before performing any electrical work.
The external switch input is configured on DI6 from the factory and is set as a normally open contact (NO) by default. If you require a normally closed
contact (NC) follow the steps below.
1 Configuration
Go to
Configuration
by using the UP/DOWN arrow buttons. Select by
pressing the RIGHT arrow button
Manual/Auto
Settings
→Configuration
Access rights
2 Inputs/Outputs
Locate
Inputs/Outputs
submenu by using the UP/DOWN arrow
buttons and select it by pressing the RIGHT arrow button
→Inputs/Outputs
Sensor settings
Control function
Fan control
3 DI
Go to
DI
by using the UP/DOWN arrow buttons. Select by pressing the
RIGHT arrow button
AI
→DI
UI
AO
4 Configuring DI6
From this submenu, use the UP/DOWN arrow buttons to locate DI6 and
select it by pressing the RIGHT arrow button. Press OK again to access
the
NO/NC
field to set the digital input contact to either normally open
(NO) OR normally closed (NC) based on what will be used to trigger the
input.
DI6
:
↑
NO/NC: NO Signal:
External switch
Status:
Off
↓
Fire alarm
(cont'd)
Unit operation
(Cont'd)
External switch
(Cont'd)
Unit operation
(Cont'd)
3 DI
Go to
DI
by using the UP/DOWN arrow buttons. Select by pressing the
RIGHT arrow button
AI
→DI
UI
AO
Alarm handling
The unit controller comes with preprogrammed alarms to ensure it functions properly and to help troubleshoot problems when they occur. Active
alarms are indicated by the flashing red LED on the unit external display.
These alarms have different characteristics. Alarms related to safe operation of the unit (alarms class A and B) will, when triggered, stop the
ventilation until the alarm has been acknowledged and the alarm conditions are no longer met. Alarms of lower priority (Classe C) will not stop the
ventilation and will auto reset once the alarm conditions are no longer met. Each alarm has a delay which is the time period the alarm conditions have
to be met before the alarm is triggered. The table below lists all the preconfigured alarms of the unit with their descriptions and other characteristics.
See table below.
Alarm
#
≥
Description
Stop
Auto reset
Delay
Malfunction supply air fan
1
Alarm text: Run error supply air fan
Cause: No feedback from supply air fan
Yes
No
300s (5 min)
Malfunction extract air fan 2
Alarm text: Run error extract air fan
Cause: No feedback from extract air fan
Yes
No
300s (5 min)
Filter guard 1
6
Alarm text: Check supply air filter
Cause: Supply air filter is dirty
No
No
300s (5 min)
Fire alarm
10
Alarm text: Fire alarm
Cause: Fire alarm DI is active
Yes
No
0s
External switch
11
Alarm text: External switch
Cause: External switch DI is active
Yes
Yes
0s
High supply air temp
15
Alarm text: High supply air temp
Cause: Supply air temp ≥ 86°F [30°C]
No
No
300s (5 min)
Low supply air temp
16
Alarm text: Low supply air temp
Cause: Supply air temp ≤ 50°F [10°C]
Yes
No
300s (5 min)
High Extract air temp
21
Alarm text: High extract air temp
Cause: Extract air temp ≥ 86°F [30°C]
No
No
300s (5 min)
Low extract air temp
22
Alarm text: Low extract air temp
Cause: Extract air temp ≤ 50°F [10°C]
No
No
30 min
Sensor error outdoor
temp
27
Alarm text: Sensor error outdoor temp
Cause: No signal from outdoor air sensor
No
No
5s
2 Inputs/Outputs
Locate
Inputs/Outputs
submenu by using the UP/DOWN arrow
buttons and select it by pressing the RIGHT arrow button
→Inputs/Outputs
Sensor settings
Control function
Fan control