Installation
A
B*
C
D
E
F
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
73 7/16
1865
43 1/2
1105
51 1/16
1311
68 1/8
1730
4
102
2 7/8
73
(c - c)
A
C
B
B
D
D
E
E
F
G
G
G
G
G
H
H
H
I
K
(c - c)
(c - c)
(c - c)
(c - c)
Dimensions
* Dimensions B and D are centered to the mounting holes (
Ø 3/4"
)
G
H
I
K (Drain 2x)
Duct Dimensions
in
mm
in
mm
in
mm
in
mm
in
mm
2 11/16
68
50 3/8
1278
54 1/2
1384
3/4 NPT 19 NPT
14 x 34
352 x 859
Space required
A
D
C
B
A
B
C
D
in.
mm
in.
mm
in.
mm
in.
mm
69.5
1763
19.5
497
93
2360
43
1094
Weight
Models
kg
lbs
HRV
386
850
ERV
340
750
Inspection
The HRV/ERV must be located in a conditioned space where it will be possible to conveniently service the unit. Typically the HRV/ERV would be
located in the mechanical room, above a drop ceiling or an area close to the outside wall where the weatherhoods will be mounted.
Conditioned Space must meet the following conditions:
•
Space temperature must be above freezing conditions at all times and preferably maintained above 12°C (54 °F).
•
The condensate drain (if included) must be installed so that the condensate drains and is protected from freezing.
•
The space is easily accessible for equipment maintenance and inspection.
Connecting appliances to the HRV/ERV s not recommended, including:
•
clothes dryer
•
kitchen exhaust hoods
•
combustion venting
•
central vacuum system
These appliances may cause lint, dust or grease to collect in the HRV/ERV , damaging the unit.
Location
The HRV/ERV must be protected from the elements (rain, snow, etc) at all times.
The unit must be mounted level and may be hung with threaded rod with a minimum of 1/2" and a maximum of 3/4" in diameter (field supplied and
specified) through the protruding frame at the base of the unit (see figure below for dimensions). Do not block access to unit doors as indicated.
Rubber or seismic vibration isolation may be required in some region (field supplied and specified).
Connecting any of these type of appliances to the HRV/ERV will void your warranty.
Installation
(Cont'd)
The ECHO units are delivered on a pallet. Handles and necessary components are placed inside the unit.
The inspection hatches are opened by the use of a 5/8” (16 mm) cap key, see figure below. To facilitate opening and closing of the inspection hatches,
install the 2 handles that are placed inside the unit on delivery.
As an extra precaution, inspect the unit and verify that all ordered equipment is delivered before starting the installation. Any discrepancies from the
ordered equipment must be reported to the supplier of Fantech products.
The door handles must be locked before the unit is put into operation to ensure the required level of safety for the unit. (Hex size: 5/16 in
(8 mm)