SystemAir fantech ECHO 2800Xi Series Installation, Operation And Maintenance Manual Download Page 11

21

20

 The schedules are set to inactive (00:00 – 00:00 Monday to Sunday & holidays) from the factory. If it is intended to have the unit 
operated by schedules then they have to be programmed in the field.  Once the airflow set points, the time/date and the schedules have 
been programed, the unit will start up and operate at the given airflow set point when a schedule is active. If it is intended to have the unit 
operate at normal speed constantly for a given day then set the period 1 of the normal speed schedule for that day to 00:00 – 24:00. If all 
week days are set to 00:00 – 24:00 the unit will run continuously, year round. The same can be done with the reduced speed schedule but 
keep in mind that the normal speed schedule has precedence over the reduced one.

Holiday periods can be programmed and set to be active or inactive in the normal or reduced speed schedules. Set the day of which month a holiday 
period starts followed by the day of which month it ends (i.e. 12-25 – 12-26 for December 25 to December 26 or 01-01 – 01-01 for January 1). 
Once holiday periods have been set, access the schedules to set the holiday run time. To program the holiday periods follow the steps below.

1 Holiday

Access the holiday submenu from the time settings menu. Press the OK 

button to access the fields, use the arrow buttons to set a value and 

press OK again to save the value. Up to 24 holiday periods can be set for 

a year. 

Holidays  

(mm:dd)

1: mm-dd - mm-dd

2: mm-dd - mm-dd

3: mm-dd - mm-dd

If the outdoor air temperature falls below the frost threshold of the unit the exchanger defrost function will be triggered and the unit will cycle between 
ventilation and the selected defrost mode in order to prevent any frost build up within the unit.

Exchanger defrost

1 Configuration

Go to 

Configuration

 by using the UP/DOWN arrow buttons. Select by 

pressing the RIGHT arrow button

Manual/Auto

Settings

→Configuration

Access rights

3 Exchanger frost prevention 

From this submenu, press the OK button to access the fields. Ensure the 

Mode

 is set to 

On

 and the 

Type

 is set to

 Recirculation

 by using 

the arrow buttons to set a value and press OK again to save the value. 

Mode

On

Type

Recirculation

If a BPM module has been installed on the unit, the recirculation operation mode can be made available. It can be configured to run via a digital input 
and/or a schedule. When recirculation is activated, the exhaust air fan will stop, the BPM module will close the path to the outdoor air and open the 
path to the indoor recirculation air and the supply air fan will recirculate air throughout the space. This can be done when ventilation is not required 
during a certain period but air circulation is desired. 

Recirculation (units equipped with the BPM module only)

To have the recirculation mode controlled by a digital input, the input will have to be configured first. A means of triggering the input will also 
be required (field supplied and specified) and wired to terminals TB3 71 & 4, DI1 & +24VDC respectively (see wiring diagram). 
Remember to cut the power to the unit at the all pole circuit breaker before performing any electrical work. The recirculation digital input has 
precedence over the normal & reduced speed schedules. If any stop condition is met, the unit will stop even if the recirculation input is active.

To configure the recirculation digital input, after the means of triggering the input has been wired, follow the steps below.

1 Configuration

Go to 

Configuration

 by using the UP/DOWN arrow buttons. Select by 

pressing the RIGHT arrow button

Manual/Auto

Settings

→Configuration

Access rights

2 Inputs/Outputs

Locate 

Inputs/Outputs

 submenu by using the UP/DOWN arrow 

buttons and select it by pressing the RIGHT arrow button

→Inputs/Outputs

Sensor settings

Control function

Fan control

Time settings & schedule 

(Cont'd)

Unit operation 

(Cont'd)

Exchanger defrost 

(Cont'd)

Unit operation 

(Cont'd)

3 DI

Go to

 DI 

by using the UP/DOWN arrow buttons. Select by pressing the 

RIGHT arrow button

AI

→DI

UI

AO

During exhaust only defrost, the supply fan will shut down and the outdoor air damper (if equipped) will close (interruption of the cold outdoor airflow). 
The unit will keep extracting warm air for a defined period of time preventing any frost build up before going back to normal ventilation mode. This 
mode of defrost is configured from the factory and available on every unit by default. 

If a BPM module has been installed on the unit, the option of recirculation defrost is available. During recirculation defrost, the motorized damper on 
the module will temporarily block the incoming outdoor air stream and open a path to circulate warm air from the building through the HRV/ERV. The 
exhaust fan shuts down and the supply fan will circulate warm air for a defined period of time to prevent any frost build up before going back to normal 
ventilation mode.

To configure the recirculation defrost for a unit equipped with the BPM module follow the steps below.

Exchanger defrost sequece (exhaust only defrost and reciculation defrost)

Defrost Stage

Outdoor air temperature

Defrost run time/ Normal run time (min)

1

≤ 23 oF (-5 oC)

5/40

2

≤ 14 oF (-10 oC)

5/35 

3

≤ 5 oF (-15 oC)

5/30

4

≤ -4 oF (-20oC)

5/25

2 Exchanger frost prevention

Go to 

Exchanger

 frost prevention by using the UP/DOWN arrow 

buttons. Select by pressing the RIGHT arrow button

Exchanger deicing

→Exchanger frost pre

Cooling recovery

Enthalpy control

Summary of Contents for fantech ECHO 2800Xi Series

Page 1: ...on of the National Building Code and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components a...

Page 2: ...d with BPM module only 21 o Extended running 23 o Fire alarm 26 o External switch 26 Alarm handling 27 Configuring BACnet MS TP port 1 29 Maintenance 31 Limited warranty 32 Parts list 33 The key to pr...

Page 3: ...clothes dryer kitchen exhaust hoods combustion venting central vacuum system These appliances may cause lint dust or grease to collect in the HRV ERV damaging the unit Location The HRV ERV must be pr...

Page 4: ...used to recirculate indoor air when ventilation is not required See the Recirculation section for more details If a BPM module accessory has been supplied with the unit it should be installed as per...

Page 5: ...ned and sealed to the ducts with proper duct sealant to minimize air leakage Dampers fitted to the ductwork connecting the unit to the outside weather hoods should be adequately insulated in order to...

Page 6: ...esponsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended The amount of air CFM that an HRV ERV will deliver is directly re...

Page 7: ...he return air side and can be accessed by opening the larger hinged access panel Pressure transducer modules Each module has two 2 pressure transducer The first pressure transducer on the PTE module m...

Page 8: ...nting holes 8 Connection block 9 Connection to yellow cable 10 Connection to orange cable 11 Connection to red cable 12 Connection to brown cable 13 Connection to black cable Supplied Cable 10 12 11 1...

Page 9: ...hanges from stopped to starting up 2 The digital outputs for the fresh air damper and the exhaust air damper are activated 3 The exhaust air fan and the supply air fan will start after a preset time N...

Page 10: ...e and time follow the steps below Time settings schedule 1 Time settings Go to Time settings by using the UP DOWN arrow buttons Select by pressing the RIGHT arrow button Temperature Air Control Time s...

Page 11: ...be done when ventilation is not required during a certain period but air circulation is desired Recirculation units equipped with the BPM module only To have the recirculation mode controlled by a dig...

Page 12: ...ow button Manual Auto Settings Configuration Access rights Once the input has been set the recirculation mode can be configured 3 Recirculation Using the UP DOWN arrow buttons locate the use extra tim...

Page 13: ...cess the fields and set values Extended running 0 min Set the time value for extended running to remain active once the extended running input goes from on to off Time in ext running 0 min This field...

Page 14: ...ing the UP DOWN arrow buttons Select by pressing the RIGHT arrow button AI DI UI AO Alarm handling The unit controller comes with preprogrammed alarms to ensure it functions properly and to help troub...

Page 15: ...isplay Follow the steps below to handle active alarms 1 Access the alarm log Press the alarm button to access the alarm log when the red LED is flashing to indicate that an alarm has been triggered On...

Page 16: ...n a large sink bathtub or shower 5 Pour clean tap water through the face of the core facing upward until it runs clear Ensure the entire surface is rinsed 6 Rotate the core so that its other air inlet...

Page 17: ...ges incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to supply r...

Page 18: ...35 34 Notes Notes...

Page 19: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Reviews: