SystemAir fantech ECHO 2800Xi Series Installation, Operation And Maintenance Manual Download Page 13

25

24

1 Configuration

Go to 

Configuration

 by using the UP/DOWN arrow buttons. Select by 

pressing the RIGHT arrow button

Manual/Auto

Settings

→Configuration

Access rights

2 Inputs/Outputs

Locate 

Inputs/Outputs

 submenu by using the UP/DOWN arrow 

buttons and select it by pressing the RIGHT arrow button

→Inputs/Outputs

Sensor settings

Control function

Fan control

3 DI

Go to

 DI 

by using the UP/DOWN arrow buttons. Select by pressing the 

RIGHT arrow button

AI

→DI

UI

AO

4 Configuring DI4

From this submenu, use the UP/DOWN arrow buttons to locate DI4 and 

select it by pressing the RIGHT arrow button. Press OK again to access 

the 

NO/NC

 field to set the digital input contact to either normally open 

(NO) OR  normally closed (NC) based on what  will be used to trigger the 

input.

DI4 :

NO/NC: NO Signal:

Ext run 1/1

Status: Off  

 

 

 

      

A timer is also available for the extended running mode. By default, the timer value for the function is set to 0 minutes. This means that the unit will go 
in extended running once the input is triggered and remain in extended running until the input goes from on to off. 

Depending on the source used to trigger the input and/or the nature of the application, an extended running timer can be configured. The timer will 
start after the extended running input goes from on to off. For example, if the extended running input is triggered, the unit will go into normal speed 
(1/1) and remain in that mode as long as the input is active. Once the input goes from on to off, the unit will remain in extended running for the 
duration set for the timer. To configure the extended running timer follow the steps below.

1 Time settings

Go back to the top level menu by using the arrow buttons then locate the 

Time settings

 menu. Select it by pressing the RIGHT arrow button

Temperature

Air Control

→Time settings

Access rights

2 Extended running

From the

 Time settings

 submenu locate 

Extended running

 

and select it by pressing the RIGHT arrow button. 

Timer normal speed

Timer reduced speed

→Extended running

Holidays

3 Configure extended running

From this submenu, press the OK button to access the fields and set 

values. 

Extended running

0 min

Set the time value for extended running to

 

remain active once the extended running input 

goes from on to off.

Time in ext running

0 min

This field only displays the actual timer value, 

in minutes. Starting at 0 minute and counting 

up every minute until the timer as reach the 

extended running time value configured above. 

Always leave value at 0 min.  

The fire alarm digital input can be used to connect the unit to fire alarms or the building management system (BMS) in order to stop the unit in case of 
a fire. If the fire alarm input is triggered the unit will initiate the stop sequence and stop the ventilation. A controller alarm will also appear on the unit 
external display to indicate that the fire alarm input is active.  

Fire alarm

The fire alarm(s) or BMS output has to be wired to terminals TB3 75 & 4, DI5 & +24VDC respectively (see wiring diagram). Remember to 
cut the power to the unit at the all pole circuit breaker before performing any electrical work.

Check if the unit’s operation, as explained above in case of a fire, conforms to the local building code or the authorities having jurisdiction in 
your area.

Unit operation 

(Cont'd)

Extended running  

(Cont'd)

Unit operation 

(Cont'd)

Extended running  

(Cont'd)

The fire alarm input is configured on DI5 from the factory and is set as a normally open contact (NO) by default. If you require a normally closed 
contact (NC) follow the steps below.

1 Configuration

Go to 

Configuration

 by using the UP/DOWN arrow buttons. Select by 

pressing the RIGHT arrow button

Manual/Auto

Settings

→Configuration

Access rights

A means of triggering the input will be required (field supplied and specified) and wired to terminals TB3 74 & 4, DI4 & +24VDC respectively 
(see wiring diagram). Remember to cut the power to the unit at the all pole circuit breaker before performing any electrical work. The 
Extended running digital input has precedence over the recirculation digital input and the normal, reduced and recirculation schedules. If any 
stop condition is met, the unit will stop even if the extended running input is active.

The extended running input is configured on DI4 from the factory and is set as a normally open contact (NO) by default. If you require a normally closed 
contact (NC) follow the steps below.

Summary of Contents for fantech ECHO 2800Xi Series

Page 1: ...on of the National Building Code and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components a...

Page 2: ...d with BPM module only 21 o Extended running 23 o Fire alarm 26 o External switch 26 Alarm handling 27 Configuring BACnet MS TP port 1 29 Maintenance 31 Limited warranty 32 Parts list 33 The key to pr...

Page 3: ...clothes dryer kitchen exhaust hoods combustion venting central vacuum system These appliances may cause lint dust or grease to collect in the HRV ERV damaging the unit Location The HRV ERV must be pr...

Page 4: ...used to recirculate indoor air when ventilation is not required See the Recirculation section for more details If a BPM module accessory has been supplied with the unit it should be installed as per...

Page 5: ...ned and sealed to the ducts with proper duct sealant to minimize air leakage Dampers fitted to the ductwork connecting the unit to the outside weather hoods should be adequately insulated in order to...

Page 6: ...esponsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended The amount of air CFM that an HRV ERV will deliver is directly re...

Page 7: ...he return air side and can be accessed by opening the larger hinged access panel Pressure transducer modules Each module has two 2 pressure transducer The first pressure transducer on the PTE module m...

Page 8: ...nting holes 8 Connection block 9 Connection to yellow cable 10 Connection to orange cable 11 Connection to red cable 12 Connection to brown cable 13 Connection to black cable Supplied Cable 10 12 11 1...

Page 9: ...hanges from stopped to starting up 2 The digital outputs for the fresh air damper and the exhaust air damper are activated 3 The exhaust air fan and the supply air fan will start after a preset time N...

Page 10: ...e and time follow the steps below Time settings schedule 1 Time settings Go to Time settings by using the UP DOWN arrow buttons Select by pressing the RIGHT arrow button Temperature Air Control Time s...

Page 11: ...be done when ventilation is not required during a certain period but air circulation is desired Recirculation units equipped with the BPM module only To have the recirculation mode controlled by a dig...

Page 12: ...ow button Manual Auto Settings Configuration Access rights Once the input has been set the recirculation mode can be configured 3 Recirculation Using the UP DOWN arrow buttons locate the use extra tim...

Page 13: ...cess the fields and set values Extended running 0 min Set the time value for extended running to remain active once the extended running input goes from on to off Time in ext running 0 min This field...

Page 14: ...ing the UP DOWN arrow buttons Select by pressing the RIGHT arrow button AI DI UI AO Alarm handling The unit controller comes with preprogrammed alarms to ensure it functions properly and to help troub...

Page 15: ...isplay Follow the steps below to handle active alarms 1 Access the alarm log Press the alarm button to access the alarm log when the red LED is flashing to indicate that an alarm has been triggered On...

Page 16: ...n a large sink bathtub or shower 5 Pour clean tap water through the face of the core facing upward until it runs clear Ensure the entire surface is rinsed 6 Rotate the core so that its other air inlet...

Page 17: ...ges incurred in the use of the ventilation system Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area Fantech reserves the right to supply r...

Page 18: ...35 34 Notes Notes...

Page 19: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Reviews: