25
24
1 Configuration
Go to
Configuration
by using the UP/DOWN arrow buttons. Select by
pressing the RIGHT arrow button
Manual/Auto
Settings
→Configuration
Access rights
2 Inputs/Outputs
Locate
Inputs/Outputs
submenu by using the UP/DOWN arrow
buttons and select it by pressing the RIGHT arrow button
→Inputs/Outputs
Sensor settings
Control function
Fan control
3 DI
Go to
DI
by using the UP/DOWN arrow buttons. Select by pressing the
RIGHT arrow button
AI
→DI
UI
AO
4 Configuring DI4
From this submenu, use the UP/DOWN arrow buttons to locate DI4 and
select it by pressing the RIGHT arrow button. Press OK again to access
the
NO/NC
field to set the digital input contact to either normally open
(NO) OR normally closed (NC) based on what will be used to trigger the
input.
DI4 :
NO/NC: NO Signal:
Ext run 1/1
Status: Off
↓
A timer is also available for the extended running mode. By default, the timer value for the function is set to 0 minutes. This means that the unit will go
in extended running once the input is triggered and remain in extended running until the input goes from on to off.
Depending on the source used to trigger the input and/or the nature of the application, an extended running timer can be configured. The timer will
start after the extended running input goes from on to off. For example, if the extended running input is triggered, the unit will go into normal speed
(1/1) and remain in that mode as long as the input is active. Once the input goes from on to off, the unit will remain in extended running for the
duration set for the timer. To configure the extended running timer follow the steps below.
1 Time settings
Go back to the top level menu by using the arrow buttons then locate the
Time settings
menu. Select it by pressing the RIGHT arrow button
Temperature
Air Control
→Time settings
Access rights
2 Extended running
From the
Time settings
submenu locate
Extended running
and select it by pressing the RIGHT arrow button.
Timer normal speed
Timer reduced speed
→Extended running
Holidays
3 Configure extended running
From this submenu, press the OK button to access the fields and set
values.
Extended running
0 min
Set the time value for extended running to
remain active once the extended running input
goes from on to off.
Time in ext running
0 min
This field only displays the actual timer value,
in minutes. Starting at 0 minute and counting
up every minute until the timer as reach the
extended running time value configured above.
Always leave value at 0 min.
The fire alarm digital input can be used to connect the unit to fire alarms or the building management system (BMS) in order to stop the unit in case of
a fire. If the fire alarm input is triggered the unit will initiate the stop sequence and stop the ventilation. A controller alarm will also appear on the unit
external display to indicate that the fire alarm input is active.
Fire alarm
The fire alarm(s) or BMS output has to be wired to terminals TB3 75 & 4, DI5 & +24VDC respectively (see wiring diagram). Remember to
cut the power to the unit at the all pole circuit breaker before performing any electrical work.
Check if the unit’s operation, as explained above in case of a fire, conforms to the local building code or the authorities having jurisdiction in
your area.
Unit operation
(Cont'd)
Extended running
(Cont'd)
Unit operation
(Cont'd)
Extended running
(Cont'd)
The fire alarm input is configured on DI5 from the factory and is set as a normally open contact (NO) by default. If you require a normally closed
contact (NC) follow the steps below.
1 Configuration
Go to
Configuration
by using the UP/DOWN arrow buttons. Select by
pressing the RIGHT arrow button
Manual/Auto
Settings
→Configuration
Access rights
A means of triggering the input will be required (field supplied and specified) and wired to terminals TB3 74 & 4, DI4 & +24VDC respectively
(see wiring diagram). Remember to cut the power to the unit at the all pole circuit breaker before performing any electrical work. The
Extended running digital input has precedence over the recirculation digital input and the normal, reduced and recirculation schedules. If any
stop condition is met, the unit will stop even if the extended running input is active.
The extended running input is configured on DI4 from the factory and is set as a normally open contact (NO) by default. If you require a normally closed
contact (NC) follow the steps below.