background image

SS-400-006 

3 I56-3535-002R

[4.4]SECuRE THE DuCT DETECTOR TO THE DuCT

Use two (rectangular configuration) or three (square configuration) of the pro-
vided sheet metal screws to screw the duct detector to the duct .

CAUTION: Do not overtighten the screws .

CAUTION

 

Do not overtighten the screws .

[5]SamPLInG TuBE InSTaLLaTIOn 
[5.1]SamPLInG TuBE SELECTIOn

The sampling tube must be purchased separately . Order the correct length, as 
specified in Table 1, for width of the duct where it will be installed . The sam-
pling tube length must extend at least 

2

/

3

 across the duct width for optimal 

performance .

The sampling tube is always installed with the air inlet holes facing into the 
air flow . To assist proper installation, the tube’s connector is marked with an 
arrow . Make sure the sampling tube is mounted so that the arrow points into 
the airflow as shown in Figure 5 . Mounting the detector housing in a vertical 
orientation is acceptable provided that the air flows directly into the sam-
pling tube holes as indicated in Figure 5 . The sampling tube and exhaust tube 
can be mounted in either housing connection as long as the exhaust tube is 
mounted downstream from the sampling tube .

TaBLE 1. SamPLInG TuBES RECOmmEnDED fOR 
DIffEREnT DuCT wIDTHS:

Outside Duct Width

Sampling Tube Recommended*

Up to 1 ft .

DST1

1 to 2 ft .

DST1 .5

2 to 4 ft .

DST3

4 to 8 ft .

DST5

8 to 12 ft .

DST10 (2-piece)

*Must extend a minimum of 

2

3

 the duct width

fIGuRE 5. aIR DuCT DETECTOR SamPLInG TuBE:

SAMPLING TUBE ENDCAP

ARROW MUST FACE 

INTO AIR FLOW

AIR FLOW 

DIRECTION

CAUTION:

 The sampling tube end cap, included with the detector, is critical 

to proper operation of the duct smoke detector . The end cap is needed to 
create the proper air flow to the sensor of the duct smoke detector . Once any 
sampling tube length adjustments are made, plug the end of the sampling 
tube with the provided end cap .

A plastic exhaust tube is included with the unit to be installed if needed . In-
stall into the housing connection that is downstream from the sampling tube 
connection . The exhaust tube can be installed from the front of the detector 
or the back . A longer 1 foot exhaust tube, model ETX, is available as an acces-
sory in cases where the molded exhaust tube does not extend at least 2 inches 
into the duct .

[5.2]SamPLInG TuBE InSTaLLaTIOn

1 .   For tubes shorter than the width of the duct, slide the sampling tube, 

with installed end cap, into the housing connection that meets the air-
flow first . Position the tube so that the arrow points into the airflow as 
shown in Figure 5 . Per NFPA sampling tubes over 3 feet long should be 
supported at the end opposite of the duct detector . In ducts wider than 8 
feet, work must be performed inside the duct to couple the other section 
of the sampling tube to the section already installed using the ½ inch 
conduit fitting supplied . Make sure that the holes on both sections of the 
air inlet sampling tube are lined up and facing into the airflow .

2 .   For tubes longer than the width of the air duct, the tube should extend 

out of the opposite side of the duct . Drill a ¾ inch hole in the duct op-
posite the hole already cut for the sampling tube . Ensure that the sam-
pling tube is angled downward from the duct smoke detector to allow for 
moisture drainage away from the detector .  The sampling tube should be 
angled at least 

1

4

” downward for every 12” of duct width . There should 

be 10 to 12 holes spaced as evenly as possible across the width of the 
duct . If there are more than 2 holes in the section of the tube extending 
out of the duct, select a shorter tube using Table 1 . Otherwise, trim the 
tube to leave approximately 1 to 2 inches extending outside the duct . 
Plug the end with the end cap and tape closed any holes in the protrud-
ing section of the tube . Be sure to seal the duct where the tube protrudes .

WARNING

In no case should more than 2 air inlet holes be cut off the tube . There must 
be a minimum of 10 holes in the tube exposed to the air stream .

[5.3]mODIfICaTIOnS Of SamPLInG TuBES

There may be applications where duct widths are not what is specified for the 
installation . In such cases, it is permissible to modify a sampling tube that is 
longer than necessary to span the duct width .

Use a 0 .193-inch diameter (#10) drill and add the appropriate number of holes 
so that the total number of holes exposed to the air flow in the duct is 10 to 12 . 
Space the additional holes as evenly as possible over the length of the tube .

CAUTION:

 This procedure should only be used as a temporary fix . It is not 

intended as a permanent substitute for ordering the correct length tubes .

[5.4]REmOTE SamPLInG TuBE InSTaLLaTIOn

The detector arrangement can also incorporate the remote mounting of the 
sampling tube and/or exhaust tube . In this case both the detector, sampling 
tube and exhaust tube (if included) should be rigidly mounted to withstand 
the pressure and vibrations caused by the air velocity . The location of the 
detector’s sampling tube should be such that there is uniform airflow in the 
cross section area . 

Pressure differential across the sampling and exhaust ports in the detector hous-
ing shall be verified to be between 0 .01 and 1 .11 inches of water . Do so by mea-
suring the pressure difference between the inlet and outlet ports on the detector 
housing using a manometer as described in the Measurement Tests sectiont of 
this manual .

[6]mEaSuREmEnT TESTS
[6.1]aIR fLOw

The DNRHS is designed to operate over an extended air speed range of 300 
to 4000 FPM . To verify sufficient sampling of ducted air, turn the air handler 
on and use a manometer to measure the differential pressure between the two 
sampling tubes . The differential pressure should measure at least 0 .01 inches 
of water and no more than 1 .11 inches of water . Because most commercially 
available manometers cannot accurately measure very low pressure differen-
tials, applications with less than 500 FPM of duct air speed may require one 
of the following: 1) the use of a current-sourcing pressure transmitter (Dwyer 
Series 607) or 2) the use of aerosol smoke, see below for test descriptions .

[6.2]LOw fLOw aIR fLOw TEST uSInG DwyER SERIES 607 
DIffEREnTIaL PRESSuRE TRanSmITTER

Verify the air speed of the duct using an anemometer . Air speed must be at 
least 300 FPM . Wire the Dwyer transmitter as shown in 

Figure 5

 . Connect the 

leads of the meter to either side of the 1000

Ω

 resistor . Allow unit to warm up 

HIGH

LOW

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

TO SAMPLING TUBE

TO EXHAUST TUBE

DIFFERENTIAL 

PRESSURE 

TRANSMITTER 

MODEL #607-01

15 TO 36 

VDC SUPPLY

1000 OHM 5%

1 WATT RESISTOR

VOLT METER FLUKE 

MODEL 87 OR 

EQUIVALENT

+

HO-163-01

HO-551-00

fIGuRE 6: PROCEDuRE fOR VERIfyInG aIR fLOw

Summary of Contents for DNRHS

Page 1: ... a building s regular fire detection system System Sensor supports this position and strongly recommends that the user read NFPA Standards 90A 72 and 101 The DNRHS Air Duct Smoke Detectors are listed per UL 268A This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be discussed with your local fire protection specialis...

Page 2: ...on the duct 4 3 1 For rectangular side by side mounting configuration Center punch at 4 target centers 2 A for sampling tubes and 2 B for the rectangular configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target B centers 4 ...

Page 3: ...isture drainage away from the detector The sampling tube should be angled at least 1 4 downward for every 12 of duct width There should be 10 to 12 holes spaced as evenly as possible across the width of the duct If there are more than 2 holes in the section of the tube extending out of the duct select a shorter tube using Table 1 Otherwise trim the tube to leave approximately 1 to 2 inches extendi...

Page 4: ...ctors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone or system under test to prevent unwanted alarms 8 4 1 Test THE UNIT 1 M02 04 00 Magnet Test not inc...

Page 5: ...Ds to align the cover and then gently pushing it until it locks into place 8 Reinstall the detector 9 2 Reinstallation 1 Reinstall the detector in its housing 2 Restore system power 3 Perform Detector Check 4 Notify the proper authorities testing has been completed and the smoke detector system is back in operation 10 Sensor Replacement 1 Remove the sensor head by rotating counterclockwise 2 Pull ...

Page 6: ...for a Return Authorization number send defective units postage prepaid to System Sensor Returns Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring afte...

Page 7: ...SS 400 006 7 I56 3535 002R ...

Page 8: ...ETECTOR TEST LOG Detector Identification Information Manufacturer Detector Model Serial Number Date Installed Description of Detector Location The Results and Maintenance Data Date Tested Test Description Test Results Maintenance Performed Comments ...

Reviews: