background image

SS-400-006 

4 I56-3535-002R

for 15 seconds . With both HIGH and LOW pressure ports open to ambient air, 
measure and record the voltage drop across the 1000

Ω

 resistor (measurement 

1), 4 .00 volts is typical . Using flexible tubing and rubber stoppers, connect the 
HIGH side of the transmitter to the sampling tube of the duct smoke detec-
tor housing, and the LOW side of the transmitter to the exhaust tube of the 
duct smoke detector housing . Measure and record the voltage drop across the 
1000

Ω

 resistor (measurement 2) . Subtract the voltage recorded in measure-

ment 1 from the voltage recorded in measurement 2 . If the difference is greater 
than 0 .15 volts, there is enough air flow through the duct smoke detector for 
proper operation .

[7]fIELD wIRInG; InSTaLLaTIOn GuIDELInES

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction . Proper wire gauges should be used . 
The conductors used to connect smoke detectors to control panels and acces-
sory devices should be color-coded to prevent wiring mistakes . Improper con-
nections can prevent a system from responding properly in the event of a fire .

For signal wiring (the wiring between detectors or from detector to auxiliary 
devices), it is usually recommended that single conductor wire be no smaller 
than 18 gauge . The duct smoke detector terminals accommodate wire sizes up 
to 12 gauge . Flexible conduit is recommended for the last foot of conduit; solid 
conduit connections may be used if desired .

Duct smoke detectors and alarm system control panels have specifications for 
Signaling Line Circuit (SLC) wiring . Consult the control panel manufacturer’s 
specifications for wiring requirements before wiring the detector loop . 

[7.1]wIRInG InSTRuCTIOnS

Disconnect power from the communication line before installing the DNRHS 
duct smoke detector . 

The DNRHS detectors are designed for easy wiring . The housing provides a 
terminal strip with clamping plates . Wiring connections are made by sliding 
the bare end under the plate, and tightening the clamping plate screw . See 

Figure 7

 below for system wiring .

[7.2] SET THE aDDRESS

Set the desired address on the sensor head code wheel switches . on the back 
of the sensor head .

 .

fIGuRE 8. ROTaRy aDDRESS SwITCHES

[8] VERIfICaTIOn Of OPERaTIOn
[8.1]InSTaLL THE COVER

Install the covers making sure that the cover fits into the base groove . Tighten 
the  screws that are captured in the covers . Note that the cover must be prop-
erly installed for proper operation of the sensor .

[8.2] POwER THE unIT

Activate the communication line on terminals COM + and COM – .

[8.3] DETECTOR CHECk

Standby – If programmed by the system control panel, look for the presence of 
the flashing LEDs through the transparent housing cover .  The LED will flash 
with each communication .

Trouble – If programmed by the system control panel and the detector LEDs 
do not flash, then the detector lacks power (check wiring, missing or improp-
erly placed cover, panel programming, or power supply), the sensor head is 
missing (replace), or the unit is defective (return for repair) .

[8.4]DuCT SmOkE DETECTOR TEST & maInTEnanCE PROCEDuRES

Test and maintain duct smoke detectors as recommended in NFPA 72 . The 
tests contained in this manual were devised to assist maintenance personnel 
in verification of proper detector operation . 

Before conducting these tests, notify the proper authorities that the smoke 
detection system will be temporarily out of service . Disable the zone or system 
under test to prevent unwanted alarms .

[8.4.1]TEST THE unIT

1 .   M02-04-00 Magnet Test (not included) – This sensor can be function-

ally tested with a test magnet .  The test magnet electronically simulates 
smoke in the sensing chamber, testing the sensor electronics and connec-
tions to the control panel .

2 .   Remote Test Accessory – The use of a remote accessory for visible indica-

tion of power and alarm is recommended . 

 

 Verify system control panel alarm status and control panel execution of 
all intended auxiliary functions (i .e . fan shutdown, damper control, etc .) .

 

 Two LEDs on the sensor are controlled by the panel to indicate sensor 
status .  Coded signals, transmitted from the panel, can cause the LEDs 
to blink, latch on, or latch off .  Refer to the control panel technical docu-
mentation for sensor LED operation and expected delay to alarm .

[8.4.2] THE DETECTOR muST BE RESET By THE SySTEm COnTROL PanEL
[8.4.3]SmOkE EnTRy TEST uSInG aEROSOL SmOkE

This test is intended for low-flow systems (<500 FPM) . If the air speed is 
greater than 500 FPM, use a conventional manometer to measure differential 
pressure between the sampling tubes, as described under Measurement Tests 
on Page 3 .

The detectors must also be cleaned immediately after a fire (see cleaning sec-
tion) . Failure to properly maintain air duct smoke detectors may cause unnec-
essary false alarms .

It is recommended that a permanent Detector Test Log be set up and main-
tained, with a record for each individual smoke detector in each building . 
Each detector should be clearly described, with information on the type of 
detector, the model number, the serial number (if any), the location, and the 
type of environment . Data entries should include test dates, type of test mode, 
test results, maintenance, and comments . A detector test log is included in 
this manual .

Drill a ¼-inch hole 3 feet upstream from the duct smoke detector . With the air 
handler on, measure the air velocity with an anemometer . Air speed must be 
at least 300 FPM . Spray aerosol smoke* into the duct through the ¼-inch hole 
for five seconds . Wait two minutes for the duct smoke detector to alarm . If the 
duct smoke detector alarms, air is flowing through the detector . Remove the 
duct smoke detector cover and blow out the residual aerosol smoke from the 
chamber and reset the duct smoke detector at the panel . Use duct tape to seal 
the aerosol smoke entry hole . Remember to replace the cover after the test or 
the detector will not function properly .

*Aerosol smoke can be purchased from Home Safeguard Industries at home-
safeguard .com, model 25S Smoke Detector Tester, and Chekkit Smoke De-
tector Tester model CHEK02 and CHEK06 available from SDi . When used 
properly, the canned smoke agent will cause the smoke detector to go into 
alarm . Refer to the manufacturer’s published instructions for proper use of the 
canned smoke agent .

CO146-00

fIGuRE 7. SySTEm wIRInG DIaGRam fOR DnRHS:

HO572-00

COMM. 

LINE (+)

UL/FM LISTED 

CONTROL 

PANEL

1ST 

DETECTOR

IN LOOP

2ND 

DETECTOR

IN LOOP

COMM. 

LINE (–)

COMM. 

LINE

TENS

ONES

9

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

Summary of Contents for DNRHS

Page 1: ... a building s regular fire detection system System Sensor supports this position and strongly recommends that the user read NFPA Standards 90A 72 and 101 The DNRHS Air Duct Smoke Detectors are listed per UL 268A This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be discussed with your local fire protection specialis...

Page 2: ...on the duct 4 3 1 For rectangular side by side mounting configuration Center punch at 4 target centers 2 A for sampling tubes and 2 B for the rectangular configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target B centers 4 ...

Page 3: ...isture drainage away from the detector The sampling tube should be angled at least 1 4 downward for every 12 of duct width There should be 10 to 12 holes spaced as evenly as possible across the width of the duct If there are more than 2 holes in the section of the tube extending out of the duct select a shorter tube using Table 1 Otherwise trim the tube to leave approximately 1 to 2 inches extendi...

Page 4: ...ctors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone or system under test to prevent unwanted alarms 8 4 1 Test THE UNIT 1 M02 04 00 Magnet Test not inc...

Page 5: ...Ds to align the cover and then gently pushing it until it locks into place 8 Reinstall the detector 9 2 Reinstallation 1 Reinstall the detector in its housing 2 Restore system power 3 Perform Detector Check 4 Notify the proper authorities testing has been completed and the smoke detector system is back in operation 10 Sensor Replacement 1 Remove the sensor head by rotating counterclockwise 2 Pull ...

Page 6: ...for a Return Authorization number send defective units postage prepaid to System Sensor Returns Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring afte...

Page 7: ...SS 400 006 7 I56 3535 002R ...

Page 8: ...ETECTOR TEST LOG Detector Identification Information Manufacturer Detector Model Serial Number Date Installed Description of Detector Location The Results and Maintenance Data Date Tested Test Description Test Results Maintenance Performed Comments ...

Reviews: