background image

SS-400-006 

5 I56-3535-002R

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 
manufacturer .  Misuse or overuse to these products may have long term ad-
verse effects on the smoke detector .  Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements .

[9]DETECTOR CLEanInG PROCEDuRES

Notify the proper authorities that the smoke detector system is undergoing 
maintenance, and that the system will temporarily be out of service . Disable 
the zone or system undergoing maintenance to prevent unwanted alarms and 
possible dispatch of the fire department .

[9.1]DETECTOR SEnSOR

1 .  Remove the sensor to be cleaned from the system .
2 .   Remove the sensor cover by pressing firmly on each of the four removal 

tabs that hold the cover in place .

3 .   Vacuum the screen carefully without removing it . If further cleaning is 

required continue with Step 4, otherwise skip to Step 7 .

4 .   Remove the chamber cover/screen assembly by pulling it straight out .
5 .   Use a vacuum cleaner or compressed air to remove dust and debris from 

the sensing chamber .

6 .   Reinstall the chamber cover/screen assembly by sliding the edge over the 

sensing chamber . Turn until it is firmly in place .

7 .   Replace the cover using the LEDs to align the cover and then gently 

pushing it until it locks into place .

8 .  Reinstall the detector .

[9.2]REInSTaLLaTIOn

1 .  Reinstall the detector in its housing .
2 .  Restore system power . 
3 .  Perform Detector Check .
4 .   Notify the proper authorities testing has been completed and the smoke 

detector system is back in operation .

[10]SEnSOR REPLaCEmEnT

1 .  Remove the sensor head by rotating counterclockwise .
2 .  Pull gently to remove it . 
3 .   To replace the sensor head, align the mounting features and rotate clock-

wise into place .

[11] OPTIOnaL aCCESSORIES

Optional accessories include RA400Z/RA100Z, RTS451/RTS151 and 

 

RTS451KEY/RTS151KEY .

NOTE: Ensure blue wire always remains connected to RA+ on the field 
connector side of the terminal block.

(+)

(-)

RA400Z/RA100Z

– RA

+ RA

REMOTE ALARM LED 

OPTION 1 PER UNIT 

fIGuRE 9. wIRInG DIaGRam fOR DnRHS TO Ra400Z/Ra100Z:

H0570-03

Note: If using a RA400Z, the tab should be broken for use with the intelli-
gent duct smoke detector. If using RA100Z, ensure that jumper is removed

The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates 
test of the alarm capability of the duct smoke detector . These accessories pro-
vide the stimulus to initiate an alarm condition at the detector . The DNRHS 
duct smoke detector must be reset by the system control panel .

TEST COIL TERMINALS

DCOIL

TEST COIL SCREW

H0561-01

fIGuRE 10. DnRHS wITH TEST COIL

SENSOR COVER

COVER REMOVAL TABS

SCREEN ASSEMBLY

SENSING 

CHAMBER

C0170-00

fIGuRE 11. LaSER HEaD EXPLODED VIEw:

Summary of Contents for DNRHS

Page 1: ... a building s regular fire detection system System Sensor supports this position and strongly recommends that the user read NFPA Standards 90A 72 and 101 The DNRHS Air Duct Smoke Detectors are listed per UL 268A This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be discussed with your local fire protection specialis...

Page 2: ...on the duct 4 3 1 For rectangular side by side mounting configuration Center punch at 4 target centers 2 A for sampling tubes and 2 B for the rectangular configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target B centers 4 ...

Page 3: ...isture drainage away from the detector The sampling tube should be angled at least 1 4 downward for every 12 of duct width There should be 10 to 12 holes spaced as evenly as possible across the width of the duct If there are more than 2 holes in the section of the tube extending out of the duct select a shorter tube using Table 1 Otherwise trim the tube to leave approximately 1 to 2 inches extendi...

Page 4: ...ctors as recommended in NFPA 72 The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone or system under test to prevent unwanted alarms 8 4 1 Test THE UNIT 1 M02 04 00 Magnet Test not inc...

Page 5: ...Ds to align the cover and then gently pushing it until it locks into place 8 Reinstall the detector 9 2 Reinstallation 1 Reinstall the detector in its housing 2 Restore system power 3 Perform Detector Check 4 Notify the proper authorities testing has been completed and the smoke detector system is back in operation 10 Sensor Replacement 1 Remove the sensor head by rotating counterclockwise 2 Pull ...

Page 6: ...for a Return Authorization number send defective units postage prepaid to System Sensor Returns Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring afte...

Page 7: ...SS 400 006 7 I56 3535 002R ...

Page 8: ...ETECTOR TEST LOG Detector Identification Information Manufacturer Detector Model Serial Number Date Installed Description of Detector Location The Results and Maintenance Data Date Tested Test Description Test Results Maintenance Performed Comments ...

Reviews: