Section II
General Product Information
006-0006715 10/31/18
Rev J
10 of 44
MPS-MPPS-4000 Guide
www.synqor.com
Part Numbering Scheme and Options: MPPS
This table shows the part numbering scheme for the full line of SynQor MPS products:
Family
Output
Power
Height
AC Input
Phase #
AC Input
Frequency
DC Output
Voltage
Range
Output Current
Range
Network
MPPS
4000: 4000W
1U: 1.73”
3: 3 Phase
W: 47-800Hz
28: 0-35V
48: 0-55V
72: 0-80V
150: 0-150A
120: 0-120A
078: 0-78A
E00: Ethernet/SNMP
For valid part numbers, refer to the website or contact your local sales representative.
Part Numbering Example: MPPS-4000-1U-3W28-150-E00
The MPPS‑4000 Series of products provide up to 4000 W of fully regulated DC output power.
Various options can be specified according to the part numbering scheme shown in the table:
• The allowable frequency of the AC INPUT can be in the 47‑800 Hz range.
• The default output voltage of the MPPS‑4000 Series can be 28 V, 48 V, or 72 V. These models
are capable of 150A, 120A, and 78A maximum current respectively.
• The DC OUTPUT is fully regulated.
• When placed in parallel, Units use a communication cable to ensure they are sharing evenly.
Each Unit will share to /- 3A of the average current at full load. All Units must have
the same output voltage programmed in order to share current evenly.
• RS232 serial port and logic‑level I/O communication are included in the standard model.
An Ethernet port providing web and SNMP interfaces is standard. The output voltage and
current can be set via the RS‑232 or web interfaces.