3.1.3 LPG Data Plate:
Remove the LPG Data Plate from the documents supplied with this appliance and
cover over the NAT GAS Data Plate which can be found on this unit.
This unit is now ready to be used for G30, G31 &G30/G31 gas types.
3.2 How to Check the Appliances Internal Gas Valve is Fully Open/Out of
Action:
The table provided in the Technical Information section (1.2) gives information on
the supply pressures of different gas types. Please ensure the valve is sufficiently
open by using a manometer on the Outlet Pressure Post pressure (with the burner
lit) to check the reading is as close to the supply pressure as possible. If the outlet
pressure point has a significant drop in pressure from the inlet, please go through
step 3.1.2 again.
3.3 Converting to Natural Gas:
Natural Gas Jets (2.2mm) should have been kept in a safe place when you originally
converted from Natural Gas to LPG. If you have lost these parts, please contact
Active Food Systems.
If your appliance was originally requested as LPG and you wish to convert to Natural
Gas, the relevant conversion kit will be in your documentation.
3.3.1 Changing Injectors for Natural Gas:
A)
Carefully unscrew the 4 retaining hexagonal screws holding each burner
using a 7mm socket.
B)
Remove the LPG 1.5mm jet using a 9mm socket and keep in a safe place
in case you need to convert back to LPG, and replace with 2.2mm Jet.
Screw down the burner again. A new Gasket may be required.