Page 10
Step 1-FS
Step 2-FS
Step 3-FS
Step 4-FS
Step 5-FS
Step 6-FS
EXIT FILTER SETUP
Step 7-FS
4. Hardness display will not be allowed to be set in Installer Display Settings (Step 2-NA, page 11).
Filter Setup
STEP 1-FS
– Press NEXT and
buttons simultaneously for 3 seconds. If
screen in Step 2-FS does not appear in 5 seconds, the lock on the valve is
activated. To unlock, press
, NEXT,
, and SET CLOCK in sequence, then
press NEXT and
simultaneously for 3 seconds.
STEP 2-FS
–
Mode:
Choose “FILTERING” using
or
buttons. Press NEXT
to go to Step 3-FS. Press REGEN to exit Filter Setup.
STEP 3-FS
–
Regenerant Fill Volume:
Set fill volume using
or
buttons:
— “oFF” if regenerant is not used (i.e. backwash only); or
— regenerant fill volume (0.1 to 100 gallons—default is 0.8).
Prior to selecting “oFF” or regenerant fill volume, verify the correct valve body,
main piston, regenerant piston, and stack are being used, and that the injector
or injector plug(s) are in the correct locations. See Compliance Table (page 17)
and WS1 & WS1.25 Identification (page 46) in
Tech Control Valves Service
Manual
. Press NEXT to go to Step 4-FS. Press REGEN to return to the
previous step.
STEP 4-FS
–
Backwash:
Set backwash using
or
buttons:
— “NORMAL” for one normal backwash (14 minutes);
— “NORMAL 2” for two normal backwashes (8 minutes each);
— “LONGER” for one longer backwash (16 minutes); or
— “LONGER 2” for two longer backwashes (12 minutes each).
See Tables 5 and 6 (page 5) for additional details. Press NEXT to go to Step
5-FS. Press REGEN to return to the previous step.
STEP 5-FS
–
Gallons Capacity:
Set gallons capacity using
or
buttons:
— “oFF” bases regeneration on Day Override in Step 3N (page 11); or
— number of gallons (20 to 50,100 gallons).
See Table 8 (page 9) for more detail.
4
Press NEXT to go to Step 6-FS. Press
REGEN to return to the previous step.
STEP 6-FS
–
Refill:
Set refill option using
or
buttons:
— “PoST” to refill the brine tank after the final rinse; or
— “PrE” to refill the brine tank two hours before the regeneration time set.
If “oFF” is selected in Step 3-FS (above), the display can be left on “PoST” or
“PrE” because no refill occurs. Press NEXT to go to Step 7-FS. Press REGEN to
return to the previous step.
STEP 7-FS
–
Regen Time:
Set regeneration time option using
or
buttons:
— “NORMAL” means regeneration will occur at the preset time;
— “on 0” means regeneration will occur immediately when the gallons capacity
reaches 0 (zero); or
— “ on 0” means regeneration will occur at one of the following:
— the preset time when the specified number of days between
regenerations is reached; or
— after 10 minutes of no water usage when the gallon capacity reaches
0 (zero).
See Table 8 (page 9) for more detail. Press NEXT to exit Filter System Setup.
Press REGEN to return to the previous step. To lock settings press
, NEXT,
, and SET CLOCK in sequence.