I NSTA LLATIO N
– OPERATING - MAINTENANCE
33
SILVER M
MONTAŻ
–
EKSPLOATACJA - KONSERWACJA
Check list for a hygienic operating method and maintenance of ventilation and air conditioning equipment
activity
measure (if necessary)
month
1
3
6
12
24
11.2
Remove any dry dust and fibre material at the
exchanger intake
remove with vacuum cleaner
As required
11.3
Check condensation drain and siphon
cleaning und evtl. refill
x
11.4
at kitchen discharge air
remove oil and grease residue from
kitchen discharge air with hot water and
grease-dissolving cleaning agents
As required
12
Recuperative energy reclamation - KVS system (see Chapter 5.13)
12.1
Check pumps for damage, attachment,
function and noise
x
12.2
Check fixtures for damage, leak-tightness and
function
x
12.3
Check dirt collector screen for damage
cleaning
x
12.4
Check pipeline system for damage, leak-
tightness and attachment
x
12.5
Check fluid level
refill
x
13
Burner chamber (see Chapter 5.14)
13.1
Dismantle burner chamber. Using a suitable
light source, check burner chamber for
contamination, damage and leakage
damaged burners must be put into
service
x
13.2
After cleaning downstream heating surfaces,
vacuum clean the burner chamber
cleaning
x
13.3
Check flame pan for damage
in the event of damage or deformation,
restore or replace. For this, the burner
plate and cylinder cover must be
dismantled.
x
13.4
Remove inspection cover plate and cleaning
cover from burner chamber. Remove all
turbulators and check general condition
in case of heavy corrosion, replace
individually or completely.
x
13.5
Clean all downstream heating surface pipes
with a stainless steel brush and vacuum clean
the collector tank
cleaning
x
13.6
Check de-watering equipment
cleaning
x
13.7
Subsequent to burner chamber cleaning, carry
out burner service and maintenance in
accordance with burner manufacturer's
directives.
x
13.8
Determine exhaust gas value.
x
13.9
Check gas line, connections and gas control
path for leak-tightness
re-seal
x
13.10
Check regulating and safety devices
x
13.11
Check bypass and burner chamber dampers
x
14
Gas surface burner (see Chapter 5.15)
14.1
Check gas line, connections and gas control
path for leak-tightness
re-seal
x
14.2
Remove any dirt particles from the burner with
a brush; ensure that all air holes are free
cleaning and repair
x
14.3
Check gas discharge openings
clean with nozzle needle. Do not come
in contact with ignition or control
devices
x