9 System Component Service & Maintenance Table
The prescribed service and maintenance intervals must be maintained in order to warrant a fault-free operation.
Service and maintenance are the basis for a warranty.
The application timeframe for the following points cannot be prescribed. Periodic service, maintenance and cleaning of the equipment depends
upon the level of dirt and contamination. These interval guidelines apply to standard RAC systems under normal operating conditions. With
heavy contamination or 24h operations, the intervals should be set at least 1 level shorter.
Check list for a hygienic operating method and maintenance of ventilation and air conditioning equipment
activity
measure (if necessary)
month
1
3
6
12
24
1 Chamber centre / Equipment housing (see Chapter 5.1)
1.1
All equipment chambers are to be checked for
contamination, damage and corrosion
cleaning and repair
x
1.2
Check the processes in free run-out
repair
x
1.3
Check doors for leak-tightness and latches for
freedom of movement
repair
x
1.4
Check duct connection attachments for leak-
tightness
repair
x
1.5
Check for water build-up
cleaning, determine cause
x
1.6
Check seals on doors for function
Replace
x
2 Ventilator (see Chapter 5.2)
2.1
Check ventilator for contamination and damage
cleaning and repair
x
2.2
Check bearing
re-lubricate (observe deadlines)
x
2.3
Check the vibration damper for function
repair
x
2.4
Check attachment bolts
re-tighten
x
2.5
If problems are detected (noises), check
ventilator and motor bearings
determine cause
For conspicuous problems
2.6
If problems are detected (vibrations), check
ventilator running wheel without the v-belt for
out-of-balance condition
determine cause
(the running wheel must come to a rest
in any position)
For conspicuous problems
2.7
Check thermistor for function
replace
x
V-belts (see Chapter 5.3)
2.8
Check the belt drive for contaminants, damage
and wear
cleaning and repair
x
2.9
Check for secure attachment of the complete
drive
repair
x
2.10
Replace the complete belt set
As required
2.11
Check protection equipment for function
repair
x
2.12
Adjust alignment of the motor and ventilator
plates
x
2.13
Check belt tension
re-tension
x
3 Sound attenuator (see Chapter 5.4)
3.1
Check baffle for contaminants and damage
carefully cleaning or repair
x
4 Filter unit (see Chapter 5.5)