13
SILVER M
INSTALLATION
– OPERATING - MAINTENANCE
4.17.
Gas surface burner
The regulations and manufacturer's guidelines applicable to burners
and gas connections must be observed.
When installing the equipment, possible requirements from the
certifying authorities, all local regulations, as well as all demands
from the national equivalent to the DVWG and the technical
regulations for gas installation (TRGI) must be adhered to precisely.
4.18.
Direct lighted heat exchanger
The burner must be secured to the prescribed burner attachment
plate.
The flame tube length for oil or gas burners must be adapted to the
warm air generator burner chamber in such a manner that the flame
exits the flame tube only after it is inside the burner chamber.
The heat exchanger must be built in with a natural incline towards
the condensation drain.
The regulations and manufacturer's guidelines applicable to the
burner, condensation drain, fresh air supply and chimney must be
observed.
Condensate must never remain in the heat register and must drain
freely at all times. Therefore, the condensate drain line must also be
connected.
The safety temperature limiter must be installed 50 cm to 100 cm
downstream from the fan heater in the flow direction.