Check list for a hygienic operating method and maintenance of ventilation and air conditioning equipment
activity
measure (if necessary)
month
1
3
6
12
24
4.1
Check pocket type filters and frames for
contaminants and damage
cleaning and repair
x
4.2
Check filter seat for leak-tightness and visually
inspect for damage
repair
x
4.3
Check filter insert for obvious contamination,
odours or leakage
replace
x
4.4
Check differential pressure
replace filter insert when final resistance
is reached
x
4.5
Filter change at the latest 1st level
x
x
4.6
Filter change at the latest 2nd level
x
Activated carbon filter
4.7
Perform odour check
activated carbon filter cartridge to be
replaced
x
5
Heat exchanger (see Chapter 5.6)
5.1
Allow the heat exchanger to cool down to the
ambient temperature
5.2
Check lamella-fins for contamination
cleaning and repair
x
5.3
Check lamella-fins and piping for damage
comb out bent or warped lamella-fins
x
5.4
Check heat exchanger leak-tightness
repair
x
5.5
Check feed/return lines for function
x
5.6
Check the frost protection for function
thermostat by means of coolant spray
at the start of the cooling period
5.7
Check condensation drain at the cooling
radiator
Cleaning
x
5.8
Check siphon for function
clean and refill (at the start of the cold
period)
x
6
Droplet separator (see Chapter 5.7
6.1
Check droplet separator and condensate tank
for contaminants and damage
when cleaning the droplet separator,
remove the cartridges and lamella-fins
(remove bio-film)
x
7
Cooling system (see Chapter 5.8)
7.1
Clean lamella-fin surfaces
Evaporator and condenser
x
7.2
Check compressor oil level
the oil should cover at least half of the
viewing glass with the compressor
switched off
x
7.3
Check condensate drainage
clean (be aware of unusual odours or
operating conditions)
x
7.4
Leak test
By certified refrigeration specialists
x
8
Spray humidifier (see Chapter 5.9)
8.1
Decalcification of entire spray humidifier
add in the lime solvent to the circulation
water and operate the circulation pump
until the lime is dissolved. The entire
spray humidifier must be subsequently,
thoroughly rinsed
x
8.2
Decalcification of the humidifier nozzles and
nozzle fittings, under no circumstances may
the nozzle bore holes be cleaned with hard
cleaning and repair
x