A-96.250.451 / 190121
AMI Deltacon Power
Program List and Explanations
67
5.2.1.43
Control Parameters:
if Parameters = Temp.1
5.2.1.43.13
Setpoint
Range: -25 to +270 °C
5.2.1.43.23
P-Band:
Range: -25 to +270 °C
5.2.1.43
Control Parameters:
if Parameters = Temp. 2
5.2.1.43.14
Setpoint
Range: -25 to +270 °C
5.2.1.43.24
P-Band:
Range: -25 to +270 °C
5.2.1.43
Control Parameters:
if Parameters = Difference
5.2.1.43.16
Setpoint
Range: 0.000 –3000
S
5.2.1.43.26
P-Band:
Range: 0.000 –3000
S
5.2.1.43
Control Parameters:
if Parameters = Sample flow
5.2.1.43.17
Setpoint
Range: 0.0 –20 l/h
5.2.1.43.27
P-Band:
Range: 0.0 –20 l/h
5.2.1.43
Control Parameters:
if Parameters = pH
5.2.1.43.18
Setpoint
Range: 0.00 –14 pH
5.2.1.43.28
P-Band:
Range: 0.00 –14 pH
5.2.1.43
Control Parameters:
if Parameters = Ammonia
5.2.1.43.19
Setpoint
Range: 0.00 –500 ppm
5.2.1.43.29
P-Band:
Range: 0.00 –500 ppm
5.2.1.43.3
Reset time:
The reset time is the time till the step response of a sin
-
gle I-controller will reach the same value as it will be suddenly
reached by a P-controller.
Range: 0–9’000 sec
5.2.1.43.4
Derivative time:
The derivative time is the time till the ramp response
of a single P-controller will reach the same value as it will be sudden
-
ly reached by a D-controller.
Range: 0–9’000 sec