background image

DRAIN INSTALLATION

The blower draws air through the 
dehumidifier, putting the cabinet under 
negative pressure� As a result, the included 
P-trap is required for proper draining� The 
installed drain fitting on the dehumidifier is 
3/4" FNPT� Use the included fittings to trap 
and install the drain� See 

FIGURE 6

� The 

drain tubing can be hard pipe or flexible 
tubing� 

NOTE:

 PTFE thread seal tape is 

recommended for the threaded connections 
and 

hand tighten only

� Use PVC primer and 

cement for all slip fit connections to prevent 
leaks� After installing the drain connections, 
trap, and tubing, pour enough water (about 
2 pints) into the dehumidifier drain pan to 
prime the trap�

If the drain tubing will be installed to a 
condensate pump, or if a common drain 
tube will serve multiple dehumidifiers 
or air conditioners, a vacuum break is 
recommended to prevent the p-trap from 
being unintentionally siphoned� Install a 
T-fitting with a short section of drain tubing 
pointed vertically and extending above the 
start of the filter (see 

FIGURE 6

)� Install the 

vacuum break after the P-trap�

CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH

A condensate pan is recommended when suspending 
the dehumidifier over finished areas or product� Adhere 
to local codes regarding draining of the condensate 
pan� If a condensate pump is needed, install it in the 
condensate pan as well� 

Install a condensate overflow safety switch (i�e� float 
switch) in the condensate pan, remove the factory 
installed jumper wire between the Float Switch 
terminals on the control and wire the float switch to the 
dehumidifier as shown in 

FIGURE 7

� Overflow safety 

switches on condensate pumps can be wired to the 
Float Switch terminals in a similar fashion�

3/4" MNPT X 3/4"
FEMALE PIPE 
(INCLUDED)

P-TRAP
(INCLUDED)

3/4" PIPE X 3/4" PIPE COUPLING
(NOT INCLUDED)

PVC HARD PIPE
(NOT INCLUDED)

3/4" PIPE TEE

(INCLUDED)

3/4" MNPT X 3/4"
FEMALE PIPE
(INCLUDED)

P-TRAP (INCLUDED)

3/4" FEMALE PIPE X 3/4" FNPT (INCLUDED)

3/4" MNPT X 3/4" BARB (INCLUDED)

3/4" FLEXIBLE TUBE
(NOT INCLUDED)

HIGHER

THAN

FILTER

FRAME

OPTIONAL

VACUUM

BREAK

FL

OAT

Swit

ch

DH

DH

NORMALLY CLOSED

FLOAT SWITCH

FIGURE 6 

– DRAIN ASSEMBLY

FIGURE 7 

– FLOAT SWITCH WIRING

3/4" MNPT X 3/4"
FEMALE PIPE 
(INCLUDED)

P-TRAP
(INCLUDED)

3/4" PIPE X 3/4" PIPE COUPLING
(NOT INCLUDED)

PVC HARD PIPE
(NOT INCLUDED)

3/4" PIPE TEE

(INCLUDED)

3/4" MNPT X 3/4"
FEMALE PIPE
(INCLUDED)

P-TRAP (INCLUDED)

3/4" FEMALE PIPE X 3/4" FNPT (INCLUDED)

3/4" MNPT X 3/4" BARB (INCLUDED)

3/4" FLEXIBLE TUBE
(NOT INCLUDED)

HIGHER

THAN

FILTER

FRAME

OPTIONAL

VACUUM

BREAK

English

 7

Summary of Contents for S710V1

Page 1: ...ties or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised t...

Page 2: ...ch 7 HARD WIRING LINE VOLTAGE 8 MODEL S77 REMOTE CONTROL AND WIRING 9 Alternate External Controls 9 DAISY CHAIN WIRING 10 Model S77 as Driving Control 10 Alternate External Dry Contact Control as Driv...

Page 3: ...RH 277 VAC Rated Current 24A install on dedicated 30A circuit 24A install on dedicated 30A circuit Efficiency 3 0 L kWh 6 35 pints kWh 80 F 60 RH 240 VAC 3 0 L kWh 6 35 pints kWh 80 F 60 RH 240 VAC E...

Page 4: ...neral public The dehumidifiers should be spaced evenly throughout the area to be dehumidified with the following recommendations 1 Avoid placement where the discharge of one dehumidifier is pointing t...

Page 5: ...ard the drain Use solid supports as needed to elevate the unit enough to allow for continuous drain slope Use the adjustable feet to level the unit right to left and front to back so that unit drains...

Page 6: ...t to left and front to back so that unit drains properly IMPORTANT Install lock nuts to secure the dehumidifier to the threaded rod as shown in FIGURE 5 DUCTING Use duct kit part number 5859 for insta...

Page 7: ...nding above the start of the filter see FIGURE 6 Install the vacuum break after the P trap CONDENSATE PAN CONDENSATE PUMP AND FLOAT SWITCH A condensate pan is recommended when suspending the dehumidif...

Page 8: ...ect electrical service at the main fuse or circuit breaker 2 Run electrical service to where the dehumidifier is to be installed following all required local and national codes and standards 3 Remove...

Page 9: ...start up instructions The Model S77 will measure the relative humidity and turn the dehumidifier on and off to control the humidity level to the desired setting The humidity setting can be adjusted f...

Page 10: ...above the humidity setting all units will dehumidify until the humidity measured by the S77 falls below the setting IMPORTANT If the S77 or first dehumidifier experiences a fault or loses power all d...

Page 11: ...setting IMPORTANT If the external control experiences a fault all downstream dehumidifiers will also stop function If any dehumidifier experiences a fault that unit will stop operation as determined b...

Page 12: ...and the control will return to the OFF screen 90 1854 90 1854 REMOTE CONTROL 90 1854 If not installing a Model S77 leave DISABLED and press MODE to go to the next screen 90 1854 If installing a Model...

Page 13: ...l S77 press the ON button the Model S77 will display the measured RH 3 Use the UP or DOWN button on the Model S77 to adjust the humidity setting as desired 4 If the RH measured by the Model S77 rises...

Page 14: ...he UP DOWN arrow buttons 7 Record values and call Technical Support Cycle Power E5 High Temperature Thermistor Failure 1 Check the high temperature sensor connection at the power board Terminal should...

Page 15: ...ent for any component which is found to be defective within such five 5 year period and which is returned not later than thirty 30 days after said five 5 year period by you to either your original sup...

Page 16: ...5853 10 Low Temperature Sensor 5814 11 High Temperature Sensor 5815 7 16 6 13 14 15 12 2 1 3 5 4 11 10 9 8 surna com 1780 55th Street Boulder CO 80301 1 303 993 5271 No Part Description Part No 12 MOV...

Page 17: ...ent troitement surveill s ou qu ils aient re u des consignes concernant l usage s curitaire de l appareil par la personne charg e de leur s curit Faites en sorte de surveiller les enfants pour vous as...

Page 18: ...BLAGE DIRECT TENSION DE LA LIGNE 8 MOD LE S77 COMMANDE DISTANCE ET C BLAGE 9 Commandes externes alternatives 9 C BLAGE EN GUIRLANDE 10 Mod le S77 comme commande d entra nement 10 Commande contact sec...

Page 19: ...a Courant nominal 24 A installation sur un circuit d di de 30 A 24 A installation sur un circuit d di de 30 A Efficacit 3 0 L kWh 6 35 pintes kWh 27 C 80 F 60 d HR 240 V c a 3 0 L kWh 6 35 pintes kWh...

Page 20: ...lles r guliers dans toute la zone d shumidifier en tenant compte des consid rations suivantes 1 vitez de les placer de telle sorte que l vacuation d un d shumidificateur soit dirig e vers l admission...

Page 21: ...in d obtenir une pente ininterrompue vers la conduite d vacuation Utilisez les pieds r glables pour mettre l appareil niveau vers la droite et vers la gauche et vers l arri re et vers l avant de sorte...

Page 22: ...ri re et vers l avant de sorte que l vacuation se fasse correctement IMPORTANT Installez des crous de blocage pour fixer le d shumidificateur la tige filet e comme indiqu dans la FIGURE 5 CONDUITES Ut...

Page 23: ...eportez vous la FIGURE 6 Installez le frein vide apr s le siphon en P BAC CONDENSATS POMPE DE CONDENSATS ET INTERRUPTEUR DU FLOTTEUR Un bac condensats est recommand lorsqu on suspend le d shumidificat...

Page 24: ...u du disjoncteur 2 Amenez l alimentation lectrique l o le d shumidificateur doit tre install en respectant tous les codes et normes locaux et nationaux en vigueur 3 Retirez le panneau d acc s aux circ...

Page 25: ...de mise en marche La commande mod le S77 va mesurer l humidit relative et activer ou d sactiver le d shumidificateur pour maintenir la teneur en humidit au niveau d sir Le r glage de l humidit peut tr...

Page 26: ...e par le mod le S77 Lorsque le niveau d humidit d passe le param tre d humidit toutes les unit s d shumidifient jusqu ce que l humidit mesur e par le mod le S77 tombe en dessous du param tre IMPORTANT...

Page 27: ...commande externe tombe en dessous du param tre IMPORTANT Si la commande externe subit une d fectuosit tous les d shumidificateurs en aval cesseront aussi de fonctionner Si un des d shumidificateurs su...

Page 28: ...afficher l cran Arr t 90 1854 90 1854 COMMANDE DISTANCE 90 1854 Si vous n installez pas un mod le S77 laissez DISABLED d sactiv et appuyez sur MODE pour passer l cran suivant 90 1854 Si vous installe...

Page 29: ...Marche le mod le S77 va afficher l HR mesur e 3 Utilisez le bouton avec les fl ches vers le haut ou vers le bas sur le mod le S77 pour r gler l humidit au niveau d sir 4 Si l HR mesur e par le mod le...

Page 30: ...e bas 7 Notez les et contactez le support technique Rallumer l appareil E5 D faillance de la thermistance hautes temp ratures 1 Inspectez la connexion du capteur de hautes temp ratures au panneau d al...

Page 31: ...obligation exclusive de Research Products Corporation en vertu de cette garantie sera de fournir gratuitement toute pi ce de rechange pour tout composant qui serait d fectueux durant une telle p riode...

Page 32: ...es temp ratures 5814 11 Capteur de hautes temp ratures 5815 N Description de la pi ce N de pi ce 12 Carte movistor 240 V 5854 Carte movistor 277 V 5855 13 Carte de filtre d interf rence lectromagn tiq...

Reviews: