TABLE 1 

– DIAGNOSTIC CODES

Diagnostic 

Code

Failure Mode

Action

Reset

E1

Internal Humidity or 

Temperature Sensor 

Open or Shorted

1. 

If connection okay, replace User Interface, Part No� 5738�

Cycle Power

E3

Model S77 

Remote Control 

Communication Loss

1. 

Check connections between Model S77 and dehumidifier control board� Terminals should be fully 

inserted and secured in the control board and Model S77 control terminals�

2. 

If connections are correct and secure, turn off the dehumidifier and remove the Model S77� Use a 

short section of 4-wire cable to reconnect the Model S77 to the control board� Turn the dehumidifier 

back on and increase the dryness level setting on the Model S77� If the dehumidifier turns on, the 

problem is with the wiring between the dehumidifier and control�

3. 

If the dehumidifier does not turn on, call Technical Support�

Self-Correcting

E4

Insufficient Capacity

1. 

Check the frost sensor connection at the power board� Terminal should be fully seated on the power 

board pins�

2. 

Remove the side access panel and verify that the sensor is secured to the suction line�

3. 

If the sensor is connected and secured to the refrigeration line proceed to the next step� 

4. 

Reset the fault by cycling power to the dehumidifier�

5. 

Turn the humidity setting down (below room/home humidity level) to make a dehumidification call� 

6. 

Allow the fan and compressor to run for approximately 10-15 minutes and then enter diagnostic 

test mode by simultaneously pressing the UP ARROW and MODE buttons for 3 seconds� The LCD 

will display the temperature measured by the internal sensor while also displaying AIR SAMPLING 

and ON, the humidity measured by the internal sensor while also displaying %RH and ON, and the 

frost sensor temperature while also displaying ON� Scroll through these values and by using the UP/

DOWN arrow buttons� 

7. 

Record values and call Technical Support�

Cycle Power

E5

High Temperature 

Thermistor Failure

1. 

Check the high temperature sensor connection at the power board� Terminal should be fully seated 

on the power board pins�

2. 

Remove the side access panel and verify the sensor is not damaged and connected to the 

refrigeration line coming from the compressor�

3. 

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part 

No� 5815 – contact Technical Support to confirm�

Cycle Power

E6

Low Temperature 

Thermistor Failure

1. 

Check the low temperature sensor connection at the power board�

2. 

Remove the side access panel and verify the sensor is not damaged and connected to the suction line�

3. 

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part 

No� 5814 – contact Technical Support to confirm�

Self-Correcting

E7

Float Switch Open

1. 

Empty the condensate pan�

2. 

Check the float switch connection at the control board�

3. 

If not using a float switch, verify jumper is between float switch terminals on dehumidifier control board�

4. 

If the problem persists, replace the float switch�

Self-Correcting

E8

Inlet Air Temperature 

Out of 50°F – 104°F 

Range or Dew Point 

Below 36°F

1. 

Verify all ductwork is properly sealed�

2. 

If no signs of leak points, contact Technical Support�

Self-Correcting

E9

Fan or Compressor 

Fault

1. 

Cycle power� If problem persists, contact Technical Support�

Cycle Power

TROUBLESHOOTING

Technical Support is available Monday through Friday, 7:00 a�m� to 5:00 p�m� CST, at (800) 972-3710� Use the guides on the following pages to identify 
and correct system faults� Contact Technical Support before replacing the unit or any components and for additional troubleshooting�

DIAGNOSTIC CODES

When an error occurs, the Diagnostic Code along with SERVICE REQUIRED will be displayed on the control 
screen� If a 5818 Alert Light is used, the light will turn on when an error occurs�

90-1854

14 

English

Summary of Contents for S710V1

Page 1: ...ties or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised t...

Page 2: ...ch 7 HARD WIRING LINE VOLTAGE 8 MODEL S77 REMOTE CONTROL AND WIRING 9 Alternate External Controls 9 DAISY CHAIN WIRING 10 Model S77 as Driving Control 10 Alternate External Dry Contact Control as Driv...

Page 3: ...RH 277 VAC Rated Current 24A install on dedicated 30A circuit 24A install on dedicated 30A circuit Efficiency 3 0 L kWh 6 35 pints kWh 80 F 60 RH 240 VAC 3 0 L kWh 6 35 pints kWh 80 F 60 RH 240 VAC E...

Page 4: ...neral public The dehumidifiers should be spaced evenly throughout the area to be dehumidified with the following recommendations 1 Avoid placement where the discharge of one dehumidifier is pointing t...

Page 5: ...ard the drain Use solid supports as needed to elevate the unit enough to allow for continuous drain slope Use the adjustable feet to level the unit right to left and front to back so that unit drains...

Page 6: ...t to left and front to back so that unit drains properly IMPORTANT Install lock nuts to secure the dehumidifier to the threaded rod as shown in FIGURE 5 DUCTING Use duct kit part number 5859 for insta...

Page 7: ...nding above the start of the filter see FIGURE 6 Install the vacuum break after the P trap CONDENSATE PAN CONDENSATE PUMP AND FLOAT SWITCH A condensate pan is recommended when suspending the dehumidif...

Page 8: ...ect electrical service at the main fuse or circuit breaker 2 Run electrical service to where the dehumidifier is to be installed following all required local and national codes and standards 3 Remove...

Page 9: ...start up instructions The Model S77 will measure the relative humidity and turn the dehumidifier on and off to control the humidity level to the desired setting The humidity setting can be adjusted f...

Page 10: ...above the humidity setting all units will dehumidify until the humidity measured by the S77 falls below the setting IMPORTANT If the S77 or first dehumidifier experiences a fault or loses power all d...

Page 11: ...setting IMPORTANT If the external control experiences a fault all downstream dehumidifiers will also stop function If any dehumidifier experiences a fault that unit will stop operation as determined b...

Page 12: ...and the control will return to the OFF screen 90 1854 90 1854 REMOTE CONTROL 90 1854 If not installing a Model S77 leave DISABLED and press MODE to go to the next screen 90 1854 If installing a Model...

Page 13: ...l S77 press the ON button the Model S77 will display the measured RH 3 Use the UP or DOWN button on the Model S77 to adjust the humidity setting as desired 4 If the RH measured by the Model S77 rises...

Page 14: ...he UP DOWN arrow buttons 7 Record values and call Technical Support Cycle Power E5 High Temperature Thermistor Failure 1 Check the high temperature sensor connection at the power board Terminal should...

Page 15: ...ent for any component which is found to be defective within such five 5 year period and which is returned not later than thirty 30 days after said five 5 year period by you to either your original sup...

Page 16: ...5853 10 Low Temperature Sensor 5814 11 High Temperature Sensor 5815 7 16 6 13 14 15 12 2 1 3 5 4 11 10 9 8 surna com 1780 55th Street Boulder CO 80301 1 303 993 5271 No Part Description Part No 12 MOV...

Page 17: ...ent troitement surveill s ou qu ils aient re u des consignes concernant l usage s curitaire de l appareil par la personne charg e de leur s curit Faites en sorte de surveiller les enfants pour vous as...

Page 18: ...BLAGE DIRECT TENSION DE LA LIGNE 8 MOD LE S77 COMMANDE DISTANCE ET C BLAGE 9 Commandes externes alternatives 9 C BLAGE EN GUIRLANDE 10 Mod le S77 comme commande d entra nement 10 Commande contact sec...

Page 19: ...a Courant nominal 24 A installation sur un circuit d di de 30 A 24 A installation sur un circuit d di de 30 A Efficacit 3 0 L kWh 6 35 pintes kWh 27 C 80 F 60 d HR 240 V c a 3 0 L kWh 6 35 pintes kWh...

Page 20: ...lles r guliers dans toute la zone d shumidifier en tenant compte des consid rations suivantes 1 vitez de les placer de telle sorte que l vacuation d un d shumidificateur soit dirig e vers l admission...

Page 21: ...in d obtenir une pente ininterrompue vers la conduite d vacuation Utilisez les pieds r glables pour mettre l appareil niveau vers la droite et vers la gauche et vers l arri re et vers l avant de sorte...

Page 22: ...ri re et vers l avant de sorte que l vacuation se fasse correctement IMPORTANT Installez des crous de blocage pour fixer le d shumidificateur la tige filet e comme indiqu dans la FIGURE 5 CONDUITES Ut...

Page 23: ...eportez vous la FIGURE 6 Installez le frein vide apr s le siphon en P BAC CONDENSATS POMPE DE CONDENSATS ET INTERRUPTEUR DU FLOTTEUR Un bac condensats est recommand lorsqu on suspend le d shumidificat...

Page 24: ...u du disjoncteur 2 Amenez l alimentation lectrique l o le d shumidificateur doit tre install en respectant tous les codes et normes locaux et nationaux en vigueur 3 Retirez le panneau d acc s aux circ...

Page 25: ...de mise en marche La commande mod le S77 va mesurer l humidit relative et activer ou d sactiver le d shumidificateur pour maintenir la teneur en humidit au niveau d sir Le r glage de l humidit peut tr...

Page 26: ...e par le mod le S77 Lorsque le niveau d humidit d passe le param tre d humidit toutes les unit s d shumidifient jusqu ce que l humidit mesur e par le mod le S77 tombe en dessous du param tre IMPORTANT...

Page 27: ...commande externe tombe en dessous du param tre IMPORTANT Si la commande externe subit une d fectuosit tous les d shumidificateurs en aval cesseront aussi de fonctionner Si un des d shumidificateurs su...

Page 28: ...afficher l cran Arr t 90 1854 90 1854 COMMANDE DISTANCE 90 1854 Si vous n installez pas un mod le S77 laissez DISABLED d sactiv et appuyez sur MODE pour passer l cran suivant 90 1854 Si vous installe...

Page 29: ...Marche le mod le S77 va afficher l HR mesur e 3 Utilisez le bouton avec les fl ches vers le haut ou vers le bas sur le mod le S77 pour r gler l humidit au niveau d sir 4 Si l HR mesur e par le mod le...

Page 30: ...e bas 7 Notez les et contactez le support technique Rallumer l appareil E5 D faillance de la thermistance hautes temp ratures 1 Inspectez la connexion du capteur de hautes temp ratures au panneau d al...

Page 31: ...obligation exclusive de Research Products Corporation en vertu de cette garantie sera de fournir gratuitement toute pi ce de rechange pour tout composant qui serait d fectueux durant une telle p riode...

Page 32: ...es temp ratures 5814 11 Capteur de hautes temp ratures 5815 N Description de la pi ce N de pi ce 12 Carte movistor 240 V 5854 Carte movistor 277 V 5855 13 Carte de filtre d interf rence lectromagn tiq...

Reviews: