SUSPENDING THE DEHUMIDIFIER
HANGING THE DEHUMIDIFIER
Use 3/8" or 1/2" threaded rod to suspend
the unit from appropriate ceiling structure
(see
FIGURE 4
)� The unit weight is 360 lbs�
Install vibration isolators if located in an
area where noise could be a concern� Level
unit right to left and front to back so that
unit drains properly�
IMPORTANT: Install
lock nuts to secure the dehumidifier to
the threaded rod as shown in FIGURE 5.
DUCTING
Use duct kit part number 5859 for installing
ductwork to the dehumidifier� Reference the
instructions provided with duct kit 5859 for
installation details�
4X DOUBLE NUT BOTTOM WITH FLAT WASHER,
SINGLE NUT ON TOP
4X VIBRATION ISOLATORS
(OPTIONAL)
FIGURE 5
– SECURE BRACKET TO DEHUMIDIFIER
FIGURE 4
– SUSPENSION
6
English