32
NOTE:
If the present issue is not resolved by the above steps, please call
SureFire Technical Support @ 505-333-2876
SHUTDOWN CODES
Status Codes
Symptom
Action
Visual
20
Solenoid Disconnected
Pilot flame not present
System detecting a disconnect
Check device for faulty coil
Verify wiring from device
Blinking Red
LED
21
Solenoid Short
Pilot flame not present
System detecting a short
Check device for wire short
Verify wiring from device
Blinking Red
LED
22
Safety T/C High
Temp. Shutdown
Pilot flame not present
High temperature set point reached
System detecting a disconnect upon ini-
tial start-up
Check device for failure
Verify wiring from device
If not using, check for jumper on input
Blinking Red
LED
23
Safety T/C Error or
Disconnected
Pilot flame not present
System detecting a disconnect upon ini-
tial start-up
Check device for failure
Verify wiring from device
System detecting a disconnect
If not using, check for jumper on input
Blinking Red
LED
TROUBLESHOOTING GUIDE
Summary of Contents for iBURNER BMS-100
Page 1: ...Proudly Made in the USA INSTALLATION OPERATIONS MANUAL PROUDLY MADE IN THE USA...
Page 16: ...16 INSTALLATION WIRING DIAGRAM...
Page 17: ...17 1 SureFire Solenoid Fuel Train 1 SOLENOID FUEL TRAIN...
Page 18: ...18 1 SureFire Solenoid Actuator Fuel Train 1 SOLENOID ACTUATOR FUEL TRAIN...
Page 19: ...19 1 4 ASCO Solenoid 3PG Valve Actuator Fuel Train 1 4 SOLENOID 3PG ACTUATOR FUEL TRAIN...
Page 23: ...23 Flowchart without Daughter Board OPERATIONS GUIDE FLOW CHART...
Page 25: ...25 Flowchart with Safety T C Daughter Board installed OPERATIONS GUIDE FLOW CHART...
Page 27: ...27 Flowchart with Daughter Board Safety T C and 4 20mA Input OPERATIONS GUIDE FLOW CHART...