36
DAUGHTER BOARD SETUP
Set High-Temperature shutdown value from T/C:
1.
Unlock the system by holding down the “status code” button for 5 seconds.
2.
Hold down the “Flame Strength” button for 5 seconds to see set-point value and press the “Status Code”
button to set high-temperature shut down value. (Default value is set to 1900°).
NOTE: The temperature will scroll quickly when button is held down. If you go past the temperature set
point continue to hold the up arrow button and the display will scroll past 2400°F and re-start at
100°F again.
Shutdown Codes
Status Codes
Symptom
Action
Visual
22
Safety T/C High
Temperature
Flame reached the safety T/C
high-temperature shut down
value
Wait for T/C to cool down
Blinking Red
LED
23
Safety T/C
Error or Disconnect
Safety T/C is damaged
Safety T/C is not installed.
Jumper is not installed
Replace the Safety T/C
Make sure that safety T/C is installed
Verify jumper is installed (When T/C is
not is use)
Blinking Red
LED
Summary of Contents for iBURNER BMS-100
Page 1: ...Proudly Made in the USA INSTALLATION OPERATIONS MANUAL PROUDLY MADE IN THE USA...
Page 16: ...16 INSTALLATION WIRING DIAGRAM...
Page 17: ...17 1 SureFire Solenoid Fuel Train 1 SOLENOID FUEL TRAIN...
Page 18: ...18 1 SureFire Solenoid Actuator Fuel Train 1 SOLENOID ACTUATOR FUEL TRAIN...
Page 19: ...19 1 4 ASCO Solenoid 3PG Valve Actuator Fuel Train 1 4 SOLENOID 3PG ACTUATOR FUEL TRAIN...
Page 23: ...23 Flowchart without Daughter Board OPERATIONS GUIDE FLOW CHART...
Page 25: ...25 Flowchart with Safety T C Daughter Board installed OPERATIONS GUIDE FLOW CHART...
Page 27: ...27 Flowchart with Daughter Board Safety T C and 4 20mA Input OPERATIONS GUIDE FLOW CHART...