28
Power Supply Specifications
Device
Specification
Battery
12VDC —13.4VDC
12 VDC Power Supply
SET @ 13.4 VDC
Solar Panel / 24 Volt Input
12 VDC Solar Panel / 24 Volt DC Power Supply
Note: Current limitations: 7 amps @ 12 VDC and 3 amps @ 24 VDC
Solar Panel
75 WATT Maximum (Solar panel not tested by Intertek)
Ignition Unit Specifications
Device
Specification
Ignition Unit @ In Rush
6.5 Amps
Ignition Unit @ Steady state
2.0 Amps nominal (During ignition only)
Max System Amperage
7.8 Amps
/ 0.6 Amps Avg.
Sensor Specifications
Device
Specification
Standby Switches
Dry Contact Switch (Open / Close loop)
Shutdown Switches
Dry Contact Switch (Open / Close loop)
Remote On/Off
Dry Contact Switch (Open / Close loop)
Note: No voltage or current should be applied to the ports above.
Battery / SureFire Igniter Wiring Requirements
16 AWG @ 10 ft,
Copper Stranded
14 AWG @ 20 ft,
Copper Stranded
12 AWG @ 30 ft,
Copper Stranded
SPECIFICATIONS
Summary of Contents for iBURNER BMS-100
Page 1: ...Proudly Made in the USA INSTALLATION OPERATIONS MANUAL PROUDLY MADE IN THE USA...
Page 16: ...16 INSTALLATION WIRING DIAGRAM...
Page 17: ...17 1 SureFire Solenoid Fuel Train 1 SOLENOID FUEL TRAIN...
Page 18: ...18 1 SureFire Solenoid Actuator Fuel Train 1 SOLENOID ACTUATOR FUEL TRAIN...
Page 19: ...19 1 4 ASCO Solenoid 3PG Valve Actuator Fuel Train 1 4 SOLENOID 3PG ACTUATOR FUEL TRAIN...
Page 23: ...23 Flowchart without Daughter Board OPERATIONS GUIDE FLOW CHART...
Page 25: ...25 Flowchart with Safety T C Daughter Board installed OPERATIONS GUIDE FLOW CHART...
Page 27: ...27 Flowchart with Daughter Board Safety T C and 4 20mA Input OPERATIONS GUIDE FLOW CHART...