9
5 Button Keypad:
The SureFire BMS-100 has a 5 button keypad to assist in controlling and monitoring the system.
Note: Secondary functions can only be adjusted, when system is unlocked. Pre-purge time and timing
between ignition attempts is now the same.
Button
Functions
Turns the unit ON.
Turns the unit OFF.
Primary: Displays the code that corresponds with the current unit status.
Secondary: Press button for 5 seconds to unlock the system.
Tertiary: Up arrow - Increments settable value for pre-purge & safety T/C limit.
LED Indicators
The circuit board LEDs illuminate through the lid of the enclosure. The LEDs indicate the following:
LED Indicator
Status
GREEN
LED ON
- Indicates that the system is on and operating properly
Blinking
- Indicates a standby interlock is activated
RED
LED ON
- Indicates that the system is off
Blinking
- Indicates a shutdown failure or interlock has been activated
BMS-100 DESCRIPTION
Primary: Displays the current battery voltage.
Secondary: Press button for 5 seconds to display current pre-purge timing.
To set pre-purge timing: Unlock system, press & hold Battery Volts button & use
the up arrow button to set timing. Range: 01 - 10 minutes pre-purge time.
Primary: Displays the current flame strength value for the igniter or T/C.
Secondary: Press for 5 seconds to display current safety T/C limit.
To set safety T/C limit: Unlock system, press & hold T/C HTS button & use the
up arrow button to set limit. Range: 100°F - 2400°F.
Summary of Contents for iBURNER BMS-100
Page 1: ...Proudly Made in the USA INSTALLATION OPERATIONS MANUAL PROUDLY MADE IN THE USA...
Page 16: ...16 INSTALLATION WIRING DIAGRAM...
Page 17: ...17 1 SureFire Solenoid Fuel Train 1 SOLENOID FUEL TRAIN...
Page 18: ...18 1 SureFire Solenoid Actuator Fuel Train 1 SOLENOID ACTUATOR FUEL TRAIN...
Page 19: ...19 1 4 ASCO Solenoid 3PG Valve Actuator Fuel Train 1 4 SOLENOID 3PG ACTUATOR FUEL TRAIN...
Page 23: ...23 Flowchart without Daughter Board OPERATIONS GUIDE FLOW CHART...
Page 25: ...25 Flowchart with Safety T C Daughter Board installed OPERATIONS GUIDE FLOW CHART...
Page 27: ...27 Flowchart with Daughter Board Safety T C and 4 20mA Input OPERATIONS GUIDE FLOW CHART...