background image

Maintenance 

Heatseker Nova  Inverter Heat Pump

supremeheating.com.au                                  23

9. Maintenance

1. 

You should check the water supply system regularly to avoid the 

air entering the system and occurrence of low water flow, because 

it would reduce the performance and reliability of heat pump unit.

 

2.

 Clean your pools and filtration system regularly to avoid the 

damage of the unit as a result of the dirty of clogged filter. 

3.

You should discharge the water from bottom of water pump if HP 

unit will stop running for a long time (expecially during the winter 

season).

 

4. 

In another way, you should check the unit is water fully before 

the unit start to run again. 

5. 

After the unit is conditioned for the winter season, he is 

preconize to cover the heat pump with special winter heat pump.

 

6.

 When the unit is running, there is all the time a little water 

discharge under the unit. 

    

    

Appendix

Heatseker Nova  Inverter Heat Pump

supremeheating.com.au                                  24

10. Appendix

    CHECKING THE PARAMETERS

    NOTES

1. 

When the Heatseeker Nova heat pump stops running for 30

     seconds, the water pump will shut off automatically (in the case               

     of an independant system).

2. 

The LED controller can operate the water pump by connecting

      an additional cable between the pump and the “PUMP” terminal

      on the heat pump.

3. 

It is necessary to put an extra 3-phase transfer device for a

     3-phase water pump.

SYSTEM RESET FUNCTION

MALFUNCTION                        ERROR       REASON                                      SOLUTION

Inlet water temperature 

Real testing value

Ambient temperature 

Real testing value

Gas return temperature

Real testing value

Coil temperature

Check or change the sensor

Gas exhaust temperature

Check or change the sensor

Steps of electronic 

expansion valve 

Compressor operating 

frequency:

Powerful: 65,70,75Hz

Smart: 50,55,60Hz

Silent: 30,35,40,45Hz

Compressor current

d1

d3

d4

d5

d6

d7

d8

d9

Outlet water temperature

Real testing value

d2

PARAMETER

NAME

REMARKS

-9-99°C

-F(-30°C)-70°C

-F(-30°C)-70°C

-F(-30°C)-70°C

0-C5°C(125°C)

0-99

-9-99°C

RANGE

N*5

Real testing value

0-99Hz

Real testing value

0-30A

PARAMETERS
OVERVIEW:

STEP 1

Press                

STEP 2

Press                to scroll through the paramaters, from d1 - d9 as shown below

Summary of Contents for heatseeker nova

Page 1: ......

Page 2: ...tallation Accessories 12 5 ELECTRICAL WIRING 13 3 4 CHECK VALVE INSTALLATION 3 5 TYPICAL ARRANGEMENT Independant System Index supremeheating com au I n d e x Index Heatseeker Nova Inverter Heat Pump 6 OPERATION 16 6 1 Controller Overview 16 6 2 1 Start 16 6 2 2 Mode Controls 16 6 2 3 Water Temperature Settings 16 6 2 4 Checking The Time 17 6 2 5 Setting The Time 17 6 2 6 Setting The Automatic Star...

Page 3: ...r Heat Pump Read this manual carefully before proceeding with the installation and operation of your Heatseeker Nova Inverter Heat Pump Consult your Heatseeker Nova distributor with any questions regarding this equipment Installation and service must be performed by a qualified installer The manufacturer will not be responsible for any damage to the unit caused by improper installation operation o...

Page 4: ... 3 26 7 6 7 6 20 15 10 2 67 25 18 7 12 5 3 34 5 6 5 6 11 9 35 14 9 40 60 000L 80 000L 80 000L 200 L m 120 000L 240 L m 50mm 50mm Panasonic Panasonic 59 db 60 db 50 db 2800g 52 db 3100g 130 142 1085 410 920 145 157 1050 430 1215 1145 450 1050 1110 480 1350 17 kW 26 kW 17 12 8 8 5 1 69 26 19 5 13 2 56 13 kW 12 5 9 3 6 3 1 23 7 6 7 6 7 6 12 9 6 1 61 20 15 10 2 67 9 6 8 4 5 1 21 5 6 5 6 5 6 7 2 20 11 ...

Page 5: ...ions ATTENTION THE FOLLOWING INSTRUCTIONS MUST BE FOLLOWED WHEN INSTALLING THE HEAT PUMP ATTENTION NEVER INSTALL THE UNIT IN A CLOSED ROOM WITH A LIMITED AIR VOLUME IN WHICH THE AIR EXPELLED FROM THE UNIT WILL BE RE USED OR CLOSE TO SHRUBBERY THAT COULD BLOCK THE INLET SUCH LOCATIONS IMPAIR THE CONTINUOUS SUPPLY OF FRESH AIR RESULTING IN REDUCED EFFICIENCY AND POSSIBLE PREVENTION OF SUFFICIENT HEA...

Page 6: ...OOL OUT HEATSEEKER NOVA HEAT PUMP BACK SOLAR PUMP Chlorinator FROM POOL TO POOL SOLAR PUMP HEATSEEKER NOVA HEAT PUMP BACK V FILTER X IN OUT Non return valve 3 way valve Installation Connection Heatseker Nova Inverter Heat Pump supremeheating com au 8 3 6 ADJUSTING THE BYPASS AUTOMATIC DOSING IF AUTOMATIC DOSING EQUIPMENT FOR CHLORINE AND ACIDITY pH IS USED THIS EQUIPMENT MUST BE FITTED IN THE PIPI...

Page 7: ...eat pump BYPASS INSTALLATION OPERATION WITHOUT A BYPASS OR WITH IMPROPER BYPASS ADJUSTMENT MAY RESULT IN SUB OPTIMAL HEAT PUMP OPERATION AND POSSIBLE DAMAGE TO THE HEAT PUMP FAILURE TO OBSERVE THIS INSTRUCTION IS NOT COVERED WITHIN THE WARRANTY EARTHING ALTHOUGH THE HEAT PUMP IS ELECTRICALLY ISOLATED FROM THE REST OF THE SWIMMING POOL SYSTEM THIS ONLY PREVENTS THE FLOW OF ELECTRICAL CURRENT TO OR ...

Page 8: ...rt up after the time delay expires 3 After a few minutes check whether the air blowing out of the unit is cooler 4 When the filter pump is turned off the unit should also turn off automatically If this does not occur adjust the Water Flow Switch detailed below 5 Allow the heat pump and the filter pump to run 24 hours a day until the desired water temperature is reached Once the temperature is reac...

Page 9: ...is being serviced ATTENTION THE FOLLOWING ELECTRICAL WIRING DIAGRAMS ARE ONLY FOR YOUR REFERENCE PLEASE CONSULT A SUPREME HEATING REPRESENTATIVE FOR MORE INFORNMATION 2 Neutral 1 Active 2 Neutral 1 Active Earth GPO L N 1 2 Electrical Wiring Heatseker Nova Inverter Heat Pump supremeheating com au 14 LED Controller Displays Actual Water Temperature No Error Codes MALFUNCTION ERROR REASON SOLUTION MO...

Page 10: ...ting Press again to turn on off the heat pump ADJUSTING THE HEAT OR COOL MODE OVERVIEW STEP 1 Press for 5 seconds STEP 2 Press or to adjust the Heat MODE or Cool MODE Operation Heatseker Nova Inverter Heat Pump supremeheating com au 16 ADJUSTING THE WATER TEMPERATURE DIRECTLY OVERVIEW STEP 1 Press or to adjust the water temperature MODE SETTINGS UP DOWN HEAT HEATING WHEN IN OPERATION THE LIGHT WIL...

Page 11: ...cessfully set the light will display STEP 9 If you wish to cancel the automatic start setting set the time as 00 00 ATTENTION FAILURE TO CORRECTLY SET THE AUTOMATIC STOP TIME WILL ALLOW THE PUMP TO RUN IN THE CURRENT MODE FOR 24 HOURS OR UNTIL SET TEMPERATURE IS REACHED 3 8 INITIAL OPERATION ATTENTION IN ORDER TO HEAT THE WATER IN THE POOL OR SPA THE FILTER PUMP MUST BE RUNNING TO CAUSE THE WATER ...

Page 12: ...Failure The sensor in open or short circuit Check or change the sensor Ambient Temperature Sensor Sailure The sensor in open or short circuit Check or change the sensor Condenser Gas Exit Failure The sensor in open or short circuit Check or change the sensor Antifreeze Protection in Winter Ambient temperature or water inlet temperature is too low Low Ambient Temperature Protection Ambient temperat...

Page 13: ... Ice On Evaporator 1 Check the location of heat pump unit and eliminate any obstacles to increase ventalation 2 Replace or repair the heat pump unit Too Much Ice On Evaporator Water Stains on Heat Pump Unit Water Stains OBSERVING REASONS SOLUTIONS MALFUNCTIONS Short running 1 Check the cable connections between the motor and the fan replace if necessary 2 Check the location of the heat pump unit a...

Page 14: ...KING THE PARAMETERS NOTES 1 When the Heatseeker Nova heat pump stops running for 30 seconds the water pump will shut off automatically in the case of an independant system 2 The LED controller can operate the water pump by connecting an additional cable between the pump and the PUMP terminal on the heat pump 3 It is necessary to put an extra 3 phase transfer device for a 3 phase water pump SYSTEM ...

Page 15: ...wear and tear b negligent careless or improper use or handling c non adherence to operating cleaning or maintenance instructions d harsh or adverse Pool Spa water conditions e repair to or alteration of any parts of the 6 1 9 SYSTEM PARAMETERS See Appendix 1 Warranty Agreement Heatseker Nova Inverter Heat Pump supremeheating com au 26 b is defective as a result of any of the events specified in pa...

Page 16: ...Notes Heatseker Nova Inverter Heat Pump supremeheating com au Notes Notes Heatseker Nova Inverter Heat Pump supremeheating com au Notes ...

Reviews: