Troubleshooting

Heatseker Nova  Inverter Heat Pump

supremeheating.com.au                                  21

Communication Failure 

Between Controller and 

Converter Board

1.  Insufficient Wire 

     Connection 

2.  Controller failure

Module Board Failure 

Between Outdoor Board 

And Module Board 

1. Communication wire is

     broken.

2. Outdoor board or module 

     board failure.

Restart the power or change

the broken board.

Module Board Failure 

Data is incorrect or module

board failure.

Restart the power or change

the broken board.

Direct Main Current's 

Voltage Too High Or Too

Low Protection  

1. The pressure is too high 

     or too low.

2. The inner communication

     contractor is broken.

Over Current Protection 

1.  Electric supply pressure is

      too low. 

2. The Heat Pump is

     overloaded.

The Heating Light is on

EE08

EE10

EE11

EE12

EE13

Defrosting

Communication Failure 

Between Converter and 

Outdoor Board 

Wire connection between

communication wire

and outdoor board is 

incorrect.

Restart the power supply 

or change the outdoor

board.

EE09

MALFUNCTION

REASONS

SOLUTIONS

ERROR

1. Check the wire 

     connection.

2.  Restart the power supply

3.  Change the controller.

1.  Check the power supply.

2.  Change the contactor. 

1.  Check the power supply.

2.  Check whether the water 

      temperature is too high. 

HEAT

EE02

    ATTENTION

    

THE FOLLOWING ELECTRICAL WIRING DIAGRAMS ARE 

 

 

 

 

ONLY FOR YOUR REFERENCE, PLEASE CONSULT A SUPREME

 

 

 

 

HEATING REPRESENTATIVE FOR MORE  INFORNMATION.

Troubleshooting

Heatseker Nova  Inverter Heat Pump

supremeheating.com.au                                  22

EE02

MALFUNCTION                        ERROR       REASON                                      SOLUTION
LED Displays Actual

Water Temperature,

No Error Code 

Displays.

1.  Fan not running.

2. Air ventilation is 

     insufficient.

3. Refrigerant is 

     insufficient. 

Ice On Evaporator

1.  Check the location

     of heat pump unit

     and eliminate any

     obstacles to increase

     ventalation.

2.  Replace or repair the

     heat pump unit.

Too Much Ice On

Evaporator.

Water Stains on Heat 

Pump Unit 

 

Water Stains.

OBSERVING

REASONS

SOLUTIONS

MALFUNCTIONS

Short running. 

1.  Check the cable 

      connections 

      between the motor

      and the fan- replace

      if necessary.  

2. Check the location

     of the heat pump 

     unit and eliminate

     all obstacles to 

     increase ventilation.

3. Replace or repair the

     heat pump unit.

1.  Concreting.

2. Water leakage.

1.  No action required.

2.  Check the titanium

      heat exchanger

     carefully to observe 

      any defects. 

3.  LED controller

     should display:

     “Defrosting” 

    8.2 Other Malfunctions and Solutions- No LED Display 

      

      

    

MALFUNCTION                        ERROR       REASON                                      SOLUTION
No Display on LED

No power supply.

Check cable + circuit 

breaker is connected

LED Controller

Displays The Actual

Water Temperature

1. Water temp is

     reaching setting 

     value, heat pump is

     under constant

      temperature status.

2. Currently defrosting.

1.  Verify water temp

      setting.

2.  Startup heat pump

    after a few minutes.

3.  LED controller

     should display:

     “Defrosting” 

LED Controller 

Displays Actual Water

Temp No

Error Codes.

1.  The incorrect mode

     has been chosen. 

2.  Figures show 

     defects.

3.  Controller defect.

Heat pump is not 

running.

Water temperature is

cooling when heat 

pump runs in heating

mode.

LED Controller 

Displays Real Time 

Heat pump on 

standby. 

 

Start heat pump to run.

Heat pump is not 

running.

OBSERVING

REASONS

SOLUTIONS

MALFUNCTIONS

Heat pump is not 

running.

HEAT

1.  Adjust the Mode.

2.  Replace the defect 

      LED wire controller, 

      and then check the 

      status, verifying the 

      water inlet and 

      outlet temperature.

3.  Replace or repair

     the heat pump unit.

Summary of Contents for heatseeker nova

Page 1: ......

Page 2: ...tallation Accessories 12 5 ELECTRICAL WIRING 13 3 4 CHECK VALVE INSTALLATION 3 5 TYPICAL ARRANGEMENT Independant System Index supremeheating com au I n d e x Index Heatseeker Nova Inverter Heat Pump 6 OPERATION 16 6 1 Controller Overview 16 6 2 1 Start 16 6 2 2 Mode Controls 16 6 2 3 Water Temperature Settings 16 6 2 4 Checking The Time 17 6 2 5 Setting The Time 17 6 2 6 Setting The Automatic Star...

Page 3: ...r Heat Pump Read this manual carefully before proceeding with the installation and operation of your Heatseeker Nova Inverter Heat Pump Consult your Heatseeker Nova distributor with any questions regarding this equipment Installation and service must be performed by a qualified installer The manufacturer will not be responsible for any damage to the unit caused by improper installation operation o...

Page 4: ... 3 26 7 6 7 6 20 15 10 2 67 25 18 7 12 5 3 34 5 6 5 6 11 9 35 14 9 40 60 000L 80 000L 80 000L 200 L m 120 000L 240 L m 50mm 50mm Panasonic Panasonic 59 db 60 db 50 db 2800g 52 db 3100g 130 142 1085 410 920 145 157 1050 430 1215 1145 450 1050 1110 480 1350 17 kW 26 kW 17 12 8 8 5 1 69 26 19 5 13 2 56 13 kW 12 5 9 3 6 3 1 23 7 6 7 6 7 6 12 9 6 1 61 20 15 10 2 67 9 6 8 4 5 1 21 5 6 5 6 5 6 7 2 20 11 ...

Page 5: ...ions ATTENTION THE FOLLOWING INSTRUCTIONS MUST BE FOLLOWED WHEN INSTALLING THE HEAT PUMP ATTENTION NEVER INSTALL THE UNIT IN A CLOSED ROOM WITH A LIMITED AIR VOLUME IN WHICH THE AIR EXPELLED FROM THE UNIT WILL BE RE USED OR CLOSE TO SHRUBBERY THAT COULD BLOCK THE INLET SUCH LOCATIONS IMPAIR THE CONTINUOUS SUPPLY OF FRESH AIR RESULTING IN REDUCED EFFICIENCY AND POSSIBLE PREVENTION OF SUFFICIENT HEA...

Page 6: ...OOL OUT HEATSEEKER NOVA HEAT PUMP BACK SOLAR PUMP Chlorinator FROM POOL TO POOL SOLAR PUMP HEATSEEKER NOVA HEAT PUMP BACK V FILTER X IN OUT Non return valve 3 way valve Installation Connection Heatseker Nova Inverter Heat Pump supremeheating com au 8 3 6 ADJUSTING THE BYPASS AUTOMATIC DOSING IF AUTOMATIC DOSING EQUIPMENT FOR CHLORINE AND ACIDITY pH IS USED THIS EQUIPMENT MUST BE FITTED IN THE PIPI...

Page 7: ...eat pump BYPASS INSTALLATION OPERATION WITHOUT A BYPASS OR WITH IMPROPER BYPASS ADJUSTMENT MAY RESULT IN SUB OPTIMAL HEAT PUMP OPERATION AND POSSIBLE DAMAGE TO THE HEAT PUMP FAILURE TO OBSERVE THIS INSTRUCTION IS NOT COVERED WITHIN THE WARRANTY EARTHING ALTHOUGH THE HEAT PUMP IS ELECTRICALLY ISOLATED FROM THE REST OF THE SWIMMING POOL SYSTEM THIS ONLY PREVENTS THE FLOW OF ELECTRICAL CURRENT TO OR ...

Page 8: ...rt up after the time delay expires 3 After a few minutes check whether the air blowing out of the unit is cooler 4 When the filter pump is turned off the unit should also turn off automatically If this does not occur adjust the Water Flow Switch detailed below 5 Allow the heat pump and the filter pump to run 24 hours a day until the desired water temperature is reached Once the temperature is reac...

Page 9: ...is being serviced ATTENTION THE FOLLOWING ELECTRICAL WIRING DIAGRAMS ARE ONLY FOR YOUR REFERENCE PLEASE CONSULT A SUPREME HEATING REPRESENTATIVE FOR MORE INFORNMATION 2 Neutral 1 Active 2 Neutral 1 Active Earth GPO L N 1 2 Electrical Wiring Heatseker Nova Inverter Heat Pump supremeheating com au 14 LED Controller Displays Actual Water Temperature No Error Codes MALFUNCTION ERROR REASON SOLUTION MO...

Page 10: ...ting Press again to turn on off the heat pump ADJUSTING THE HEAT OR COOL MODE OVERVIEW STEP 1 Press for 5 seconds STEP 2 Press or to adjust the Heat MODE or Cool MODE Operation Heatseker Nova Inverter Heat Pump supremeheating com au 16 ADJUSTING THE WATER TEMPERATURE DIRECTLY OVERVIEW STEP 1 Press or to adjust the water temperature MODE SETTINGS UP DOWN HEAT HEATING WHEN IN OPERATION THE LIGHT WIL...

Page 11: ...cessfully set the light will display STEP 9 If you wish to cancel the automatic start setting set the time as 00 00 ATTENTION FAILURE TO CORRECTLY SET THE AUTOMATIC STOP TIME WILL ALLOW THE PUMP TO RUN IN THE CURRENT MODE FOR 24 HOURS OR UNTIL SET TEMPERATURE IS REACHED 3 8 INITIAL OPERATION ATTENTION IN ORDER TO HEAT THE WATER IN THE POOL OR SPA THE FILTER PUMP MUST BE RUNNING TO CAUSE THE WATER ...

Page 12: ...Failure The sensor in open or short circuit Check or change the sensor Ambient Temperature Sensor Sailure The sensor in open or short circuit Check or change the sensor Condenser Gas Exit Failure The sensor in open or short circuit Check or change the sensor Antifreeze Protection in Winter Ambient temperature or water inlet temperature is too low Low Ambient Temperature Protection Ambient temperat...

Page 13: ... Ice On Evaporator 1 Check the location of heat pump unit and eliminate any obstacles to increase ventalation 2 Replace or repair the heat pump unit Too Much Ice On Evaporator Water Stains on Heat Pump Unit Water Stains OBSERVING REASONS SOLUTIONS MALFUNCTIONS Short running 1 Check the cable connections between the motor and the fan replace if necessary 2 Check the location of the heat pump unit a...

Page 14: ...KING THE PARAMETERS NOTES 1 When the Heatseeker Nova heat pump stops running for 30 seconds the water pump will shut off automatically in the case of an independant system 2 The LED controller can operate the water pump by connecting an additional cable between the pump and the PUMP terminal on the heat pump 3 It is necessary to put an extra 3 phase transfer device for a 3 phase water pump SYSTEM ...

Page 15: ...wear and tear b negligent careless or improper use or handling c non adherence to operating cleaning or maintenance instructions d harsh or adverse Pool Spa water conditions e repair to or alteration of any parts of the 6 1 9 SYSTEM PARAMETERS See Appendix 1 Warranty Agreement Heatseker Nova Inverter Heat Pump supremeheating com au 26 b is defective as a result of any of the events specified in pa...

Page 16: ...Notes Heatseker Nova Inverter Heat Pump supremeheating com au Notes Notes Heatseker Nova Inverter Heat Pump supremeheating com au Notes ...

Reviews: