3.  INSTALLATION INSTRUCTIONS 

The masonry fireplace is to be constructed in accordance to N.F.P.A. 211 (Latest Edition), Standards 
of  Chimney,  Fireplaces,  Vents  and  Solid-Fuel-Burning  Appliances  and  Equipment.  The  FUSION 
fireplace insert is intended only for masonry fireplaces installed with a continuous chimney liner of 5 
inch  diameter  extending  from  the  fireplace  insert  to  the  top  of  the  chimney.  This  insert  must  be 
connected to a code-approved masonry chimney or listed factory-built fireplace chimney with a direct 
flue connector into the first chimney liner section. The chimney size should not be less than or more 
than  three  times  greater  than  the  cross-sectional  area  of  the  flue  collar.  The  chimney  liner  must 
conform  to  the  Class  3  requirements  of  CAN/ULC-S635,  Standard  for  Lining  Systems  for  Existing 
Masonry  or  Factory-Built  Chimneys  and  Vents  or  CAN/ULC-S640,  Standard  for  Lining  Systems  for 
New Masonry Chimneys. Contact a local building inspector for information on additional requirements 
and/or codes in your area. 

CAUTION:  Read  these  instructions  carefully  before  starting  the  installation.  Failure  to  follow 
these instructions may result in property damage, bodily harm and even death.

 

Modifications 

of  the  instructions  presented  in  this  section  without  written  authorization  from  SUPREME 
FIREPLACES INC. will void the warranty. 

Be sure that the fireplace and chimney are clean and in good condition. Seal all cracks using stove 
cement.  Seal  permanently  any  openings  between  the  masonry  of  the  fireplace  and  the  facing 
masonry.  Remove  or  keep  permanently  open  the  existing  damper  of  the  fireplace.  If  there  is  an 
accumulation  of  creosote  in  the  chimney  or  flue,  it  must  be  thoroughly  cleaned.  When  installing, 
operating and maintaining a solid fuel heater, respect basic standards for fire safety. 

WARNING:  Do  not  remove  bricks  or  mortar  from  the 
masonry fireplace. 

Refer  to  Table  1,  Figure  15  and  Figure  16  for  minimum 
opening dimensions of the masonry fireplace. 

NOTE:

  The  non-combustible  hearth  must  extend  a 

minimum of 20” (508mm) from the front and 8” (203mm) on 
each side of the masonry fireplace opening and must be a 
minimum of 42” long. 

 

Table 1: Minimum Opening Dimensions 

Width (Front) 

32’’ (762 mm) 

Width (Back) 

22’’ (559 mm) 

Height 

23’’ (584 mm) 

Depth 

19’’ (483 mm) 

Figure 16: Minimum Opening Dimensions - Side View 

Figure 14: Minimum Opening Dimensions 

– Front View 

Summary of Contents for FUSION 24

Page 1: ...hase II particulate emission standards from the Environmental Protection Agency OWNER S MANUAL INSTALLATION OPERATION Important Keep the owner s manual for future use This product is proudly manufactu...

Page 2: ...r Installation 7 3 2 Liner Installation 7 3 3 Adjustable Circulation Chamber 7 3 3 1 Assembly 7 3 3 2 Installation 7 3 4 Liner Adaptor Installation 8 3 5 Firebox Installation 8 3 6 Power Cord Side Rev...

Page 3: ...ney Maintenance 16 6 3 Cleaning of Glass 17 6 4 Replacement of Gasket 17 6 5 Replacement of Glass 17 6 6 Door Latch Lubrication 18 6 7 Paint 18 6 8 Removal of Firebox 18 6 9 Replacement Parts 19 7 WAR...

Page 4: ...operation keep children pets flammable liquids or combustible materials at a safe distance Ensure that all clearances to combustible materials are respected Contact with the unit during operation may...

Page 5: ...Figure 1 FUSION Firebox Figure 2 Dimensions of FUSION Firebox Figure 3 Dimensions of FUSION Figure 4 Dimensions of FUSION with Circulating Chamber 2 COMPONENTS 2 1 Overall Dimensions 2...

Page 6: ...d Key The Cold Hand Key Figure 6 is an accessory that comes standard with the FUSION insert The Cold Hand Key is a tool used to manipulate the Combustion Air Control Levers Figure 5 when it is hot 2 4...

Page 7: ...surround electrical rating 115V 60Hz and 19W CAUTION Make certain that the fireplace in not in operation and the blowers are unplugged before accessing the electrical wiring Plug the power cord into a...

Page 8: ...The FUSION Liner Adaptor is a component that comes with the FUSION and is required to connect the stainless steel liner to the FUSION insert Figure 13 2 13 Metal Tag The Metal Tag is found on the fron...

Page 9: ...re starting the installation Failure to follow these instructions may result in property damage bodily harm and even death Modifications of the instructions presented in this section without written a...

Page 10: ...Stone Wool insulation to prevent heat from escaping Adjustable Circulating Chamber 3 3 3 3 1 Assembly i Remove the front cover of the unit and cut along the perforated lines to later use as the bottom...

Page 11: ...n the liner adaptor with the flue of the insert see Figure 19 c Insert your hand in the chimney sweeping cap opening and pull the liner down by its handle d Use your thumb to bend the 4 tabs of the li...

Page 12: ...a full length stainless steel liner flexible or rigid that meets 2100 F or 1149 C HT requirements in UL 1777 or ULC S635 Canada The liner must be properly installed to the flue collar and the chimney...

Page 13: ...stible wall is recessed the depth of the mantle can be increased by the amount of the recess Note that a mantel cannot be installed below the minimum clearance of 36 75 from the bottom of the mantel t...

Page 14: ...NG Do not keep the door open while the fireplace insert is in operation 4 2 First Fires Due to oil residues and the curing of the paint of the fireplace insert it is normal to smell an odor for the fi...

Page 15: ...estarter is well lit close the door Do not leave the door open for more than 2 minutes CAUTION The wood should be placed away from the door to avoid damage to the glass WARNINGS Over firing the unit m...

Page 16: ...or of the FUSION slightly unlatched until you see a flame in the firebox Never leave the FUSION door unlatched without constant supervision f Completely latch the FUSION door Assure that a flame is ma...

Page 17: ...tically in the presence and absence of heat respectively NOTE Standard location of the power cord is on the left when facing the surround but can be switched to the opposite side Please see Section 3...

Page 18: ...he FUSION Heat the chimney by burning newspaper near the exhaust of the baffle system Over Firing 5 2 The appearance of a red glow on the exterior of the firebox top and sides and or on the flexible l...

Page 19: ...lue lining When ignited this creosote makes an extremely hot fire The chimney connector and chimney burning wood or coal should be inspected at least once every two months during the heating season to...

Page 20: ...t for the FUSION gasket b Remove the door from the firebox and place it face down on a soft surface NOTE Rotate the handle to permit proper placing c Cover all painted surfaces of the door to avoid da...

Page 21: ...If applying paint to the door properly cover mask the glass of the door using painters tape and cardboard Wait for paint to dry before operating the unit Refer to the instructions on the label of the...

Page 22: ...raphite coated square gasket 0 1875 thick 7 length GSK_25_7 Graphite coated square gasket 0 25 thick 7 length RG 125 19 06 AC centrifugal compact fan Electrical rating 115VAC 60Hz 19W Certification VD...

Page 23: ...CPSP0301 Bib under door specify color FN1210 Removable BARBECUE grill 20...

Page 24: ...UPREME FIREPLACES INC will provide replacement parts if available at no charge except for the parts mentioned in the EXCLUSIONS portion of this warranty Supreme Fireplaces Inc shall not be responsible...

Page 25: ...rranty by refunding the wholesale price of the defective part s The manufacturer shall in no event be responsible for any consequential damages of any nature which are in excess of the original purcha...

Reviews: