SC847 Chassis Manual
5-14
Seven hot-swappable, heavy-duty fans provide cooling for the chassis. These fans
circulate air through the chassis thereby lowering the chassis internal tempera-
ture.
5-10 System Fans
Replacing a System Fan
1. Open the chassis while the power is running to determine which fan has
failed. (Never run the server for an extended period of time with the chassis
cover open.)
2. Remove the failed fan's power cord from the serverboard.
3. Press the fan release tab to lift the failed fan from the chassis and pull it
completely out of the chassis.
4. Place the new fan into the vacant space in the housing while making sure the
arrows on the top of the fan (indicating airflow direction) point in the same
direction as the arrows on the other fans.
5. Check that the fan is working properly before replacing the chassis cover.
Figure 5-13. System Fan
Release Tab
Airflow
Direction
Indicator
Summary of Contents for SC847 Series
Page 12: ...SC847 Chassis Manual 1 4 Notes...
Page 32: ...2 20 SC847 Chassis Manual Notes...
Page 53: ...5 15 Chapter 5 Chassis Setup and Maintenance Figure 5 14 Placing the System Fan...
Page 76: ...SC847 Chassis Manual B 2 Notes...
Page 86: ...C 10 SC847 Chassis Manual Notes...
Page 96: ...D 10 SC847 Chassis Manual Notes...
Page 118: ...E 22 SC847 Chassis Manual Notes...
Page 187: ...H 23 Appendix H SAS2 846EL Backplane Specifications Notes...