background image

19

Horizontal / Inclined Run

Support Brackets

Building

Support

Framing

SV4.5E90

Elbow

Ceiling

 Firestop / Spacer

SV4.5VF

 When Using Secure Flex, 

Use Firestop / Spacer SF4.5VF

Fireplace

SV4.5L6/12/24/36/48

Vent Sections

Vertical

Rise

SV4.5HT-2

Termination

Shown

Support Bracket Spacing

Every 5 ft (1.52 m)

Exterior

Wall

SV4.5HT-2

Termination

Shown

Figure 31 - 

TYPICAL HORIZONTAL VENT INSTALLATION

See 

Figure 18 

on 

Page 14

 or 

Figure 21

 on 

Page 15 

 for vertical vent section support.

B.

 

Frame exterior wall opening -

 

Locate the center of the vent outlet on 
the exterior wall according to the dimen-
sions shown in 

Figure 14 

on 

Page 11.

  Cut 

and/or frame an opening, 10-1/2" x 12-1/8" 
(267 mm x 308mm) inside dimensions, about 
this center. 

C.

 

Frame ceiling opening -

 If the vertical route 

is to penetrate a ceiling, use plumb line to locate 
the center above the appliance. Cut and/or frame 
an opening, 10-1/2" x 10-1/2" (267 mm x 267 
mm) inside dimensions, about this center (refer 
to 

Figure 19 

on 

Page 15

).

D.

 

Attach vent components to appliance - 

To 

attach a vent component to the appliance collar, 
align the dimpled end over the collar, adjust-
ing the radial alignment until the four locking 
dimples are aligned with the inlets of the four 
incline channels on the collar (

refer to Figure 

20

 

on 

Page 15).

Push the vent component against the collar 
until it fully engages, then twist the component 
clockwise, running the dimples down and along 
the incline channels until they seat at the end 
of the channels.

The unitized design of the 

Secure Vent

 

components will engage and seal both the 
inner and outer pipe elements with the same 
procedure.  Sealant and securing screws are 
not required.

Note:

 An elbow may also be attached to the 

appliance collar.  Attach in the same manner 
as you would a vent section. 

E.

 

Attach vent components to each other 

-

 Other vent sections may be added to the pre-

viously installed section in accordance with the 
requirements of the vent tables.  To add another 
vent component to a length of vent run, align the 
dimpled end of the component over the inclined 
channel end of the previously installed section, 
adjusting the radial alignment until the four lock-
ing dimples are aligned with the inlets of the four 
incline channels of the previous section.  

Push the vent component against the previous 
section until it fully engages, then twist the 
component clockwise running the dimples down 
and along the incline channels until they seat at 
the end of the channels.

This seating position 

is indicated by the alignment of the arrow and 
dimple as shown in

 

Figure 20 on Page 15.

F.

 

Install fi restop/spacer at ceiling - 

When using Secure Vent, use SV4.5VF fi restop/
spacer at ceiling joists; when using Secure Flex, 
use SF4.5VF fi restop/spacer. 

If there is living space above the ceiling level, 
the fi restop/ spacer must be installed on the 
bottom side of the ceiling. If attic space is 
above the ceiling, the fi restop/ spacer must be 
installed on the top side of the joist. Route the 
vent sections through the framed opening and 
secure the fi restop/spacer with 8d nails or other 
appropriate fasteners at each corner.

Remember to maintain 1" (25 mm) clearance 
to combustibles, framing members, and attic 
or ceiling insulation when running vertical 
chimney sections

.

G.

 

Support the vertical run sections - 

See 

Section E

 on 

Page 15.

H.

 

Change vent direction  -

 At transition from or 

to a horizontal/inclined run, install the SV4.5E45 
and SV4.5E90 elbows in the same manner as 
the straight vent sections.  The elbows feature a 
twist section to allow them to be routed about the 
center axis of their initial collar section to align 
with the required direction of the next vent run 
element. 

Twist elbow sections in a clockwise 

direction only so as to avoid the possiblity of 
unlocking any of the previously connected vent 
sections.

 See 

Figure 22 on Page 16

.

I.

 

Continue installation of horizontal/inclined 

sections -

  Continue with the installation of the 

straight vent sections in horizontal/inclined run 
as described in 

Step E

. Install support straps 

every 5 ft. (1.52 m) along horizontal/inclined 
vent runs using conventional plumber’s tape. 
See 

Figure 31.

 

It is very important that the 

horizontal/inclined run be maintained in a 
straight (no dips) 

and recommended to be in 

a slightly elevated plane, in a direction away 
from the fi replace of 1/4" rise per foot (20 mm 
per meter) which is ideal, though rise per foot 
run ratios that are smaller are acceptable all the 
way down to at or near level.

It is important to maintain the required clear-
ances to combustibles: 1" (25 mm) at all sides 
for all vertical runs; and 3" (76 mm) at the top, 
1" (25 mm) at sides, and 1" (25 mm) at the 
bottom for all horizontal/inclined runs.

Summary of Contents for SSDVR-3530CNE

Page 1: ...T light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If yo...

Page 2: ...oms and Manufactured Homes Manufactured Homes See Manufactured Home Requirements on Page 7 for additional information PACKAGING The assembled vented gas fireplace heater is packaged with 1 One log set...

Page 3: ...kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4 5 and 6 show the appliances gas pressure requirements Manifold Gas Supply Pressure millivolt mod...

Page 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Page 5: ...ionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have these signs obtainfreshairi...

Page 6: ...elveslikethesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide...

Page 7: ...mm or less See Figure 6 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 7 on Page 8 Figure 6 Side Elevation View Note See Figure 33 on Pag...

Page 8: ...e meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service...

Page 9: ...w of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figure 10 At 8 1 4 side wall clearance a combustible...

Page 10: ...ot factory provided and bringinelectricalservicelineforforcedair circulating blower optional equipment b ElectronicAppliances Fieldwireandinstall operating control switch Step 5 Page 25 Install blower...

Page 11: ...re top vent only Louvered Front Model Shown Rear vent models only Electrical Inlet 2 3 4 x 2 70 x 51 Cover Plate W Knockout Right Side View 9 229 E B D C Front View 3 76 A 1 3 8 35 Optional ELECTRICAL...

Page 12: ...be aware that if tank size is too small i e under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can...

Page 13: ...appliance The vent pipe is tested to be run inside an enclosing wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe WARNIN...

Page 14: ...0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2...

Page 15: ...ectinglengthcombinations Elbowsare available in 90 and 45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent s...

Page 16: ...the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of un...

Page 17: ...usingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Se...

Page 18: ...restop Spacer SF4 5HF Figure 29 Rear Vent THREE ELBOWS Figure 30 Top Vent THREE ELBOWS VERTICAL VENT FIGURES TABLES CONTINUED HORIZONTAL OUTSIDE WALL TERMINATION SYSTEM Figure 31 and Figures 34 to 40...

Page 19: ...ush the vent component against the previous section until it fully engages then twist the componentclockwiserunningthedimplesdown and along the incline channels until they seat at the end of the chann...

Page 20: ...Termination J Assemble vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as described in Step B Assemble the vent system topoin...

Page 21: ...CCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 35 See Table 12 as an aid in venting component selection for a particular range of ex...

Page 22: ...ee Table 12 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES CONTINUED Table H H H1 Maximum HMaximum V Minimum fee...

Page 23: ...of horizontal run up to a maximum total H H1 H2 horizontal run of 20 feet Figure 40 Top Vent THREE 90 DEGREE ELBOWS Figure 39 Rear Vent THREE 90 DEGREE ELBOWS See Table 12 on Page 21 as an aid in ven...

Page 24: ...sely around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from...

Page 25: ...ed Electrical power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the con...

Page 26: ...s the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22 1 Canadian Electrical Code Step 6 CONNECTING GAS LINE Make gas line connections All codes require a shut offval...

Page 27: ...er HI LO flame adjustment knob and pilot and main gas OFF ON control knob are located below the glass panel enclosure The gas valve for electronic systems is also located below the glass enclosure pan...

Page 28: ...sts on the subfloor 5 Placethetoprightlog D asshown Thetop fork on log D fits into notch on log A as shown The bottom fork on log D rests on subfloor flange identified in photo 1 SSDV 4035 Install as...

Page 29: ...Item letters above correspond to photos B C D A A Notch Notch 2 C 3 Notchesonbottomoflog C fitsover2locatingbrackets Topforkonlog B fitsintonotchonlog A B A 4 D A 5 Topforkonlog D fitsintonotchonlog A...

Page 30: ...MODEL SSDV 4035 Log Placement Instructions D A 4 A Bottomoflog B restsonsubfloor B Topforkonlog D fitsintonotchonlog A asshown Topforkonlog B fitsintonotchonlog A as shown 1 Place Embers and Volcanic...

Page 31: ...glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to touch...

Page 32: ...ll Figure 58 See Page 6 for Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avo...

Page 33: ...L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing...

Page 34: ...Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV...

Page 35: ...qualified service agency performing thisinstallationassumesresponsibil ity for this conversion AVERTISSEMENT Cet quipement de conversion sera install par une agence qualifi e de service conform ment a...

Page 36: ...ning it clockwise Replace the plastic protecting cap Pilot for Honeywell Millivolt Gas Valve Loosening of Hex Fitting For Orifice Strip Tab Positioning Figure 63 7 16 in Open End Wrench Hood Hood Alig...

Page 37: ...emove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and red spring for propane gas u...

Page 38: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 38 NOTES...

Page 39: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 39 NOTES...

Page 40: ...CA 92865 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your...

Reviews: