background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

20

SV4.5 HT-2

Termination

SV4.5 HT-2

Termination

Horizontal terminations have been designed to perform in a wide range of weather condi-
tions.  Our terminations meet or exceed industry standards.

When selecting the locations of your horizontal terminations, do not place the termina-
tion where water from eaves and adjoining roofl ines may create a heavy fl ow of cascad-
ing water onto the termination cap.  If the cap must be placed where the possibility of 
cascading water exists, it is the responsibility of the builder to direct the water away 
from the termination cap by using gutters or other means.

Take care to carefully follow the installation instructions for the termination, including 
the use of silicone caulking where required.

Figure 33

Figure 32 -

 INSTALLING SQUARE HORIZONTAL TERMINATION (SV4.5HT-2)

Siding

Stucco

1-1/4” Maximum Recess of 
Square Termination
into Exterior Finishing Material

Exterior Surface of
Framing

Exterior Surface of Siding

Maximum Extent of 
Vent Run Sections
Relative to Exterior
Surface of Framing

Interior Surface of
Finished Wall

Last Vent Section. 

Use Telescopic Vent

Section (SV4.5LA), If

Necessary

Adapter

SV4.5RCH

 Use silicone caulking to seal

the top and sides of the
termination, up to the
underlayment, stucco, or
masonry wall surface.

Caulk

Caulk

Maximum Wall Thickness
10 in. (254 mm) 

6 in. to 9-1/4 in.
(152 to 235 mm) 

10

¹⁄₂

"

(267mm)

7"

(178)

5

¹⁄₈

"

(130 mm)

12

¹⁄₈

"

(308 mm)

Note: Centerline of Vent Piping is

NOT the Same as the Centerline of

the Framed Opening.

6 to 48 inch Vent Section,

Telescopic vent section,

Elbow or Appliance Collar

Base of Appliance

3"

(76 mm)

1"

(25.4 mm)

Adapter

SV4.5RCH

To help minimize water infiltration it is
recommended that the Firestop/Spacer

(SV4.5HF) be installed on the exterior

side of the wall.

Venting Connection and Exterior Wall Recessing of the Horizontal Square 
Termination (SV4.5HT-2).

See 

Figure 14

 on 

Page 11

  for Min. 

Distance to Base of Appliance.

For thicknesses greater 

than 10", see 

Table 12

SV4.5 HT-2

Termination

J.

 

Assemble vent run to exterior wall -

 If not 

previously measured, locate the center of the 
vent at the exterior wall. Prepare an opening as 
described in 

Step B

.  Assemble the vent system 

to point where the terminus of the last section is 
located relative to the exterior surface to which 
the termination is to be attached (see

 Figures 

32 & 33 and Table 12 on Page 21

If the terminus of the last section is not within 
this distance, use the 

telescopic vent section 

SV4.5LA, 

as the last vent section. For wall thick-

nesses greater than that shown in 

Figure 33 on 

Page 20 and

 

Table 12 on Page 21

.  This table 

lists  the additional venting components needed 
(in addition to the termination and adapter) for 
a particular range of wall thicknesses.

K.

 

Attach termination adapter -

 Attach the 

adapter (adapter - SV4.5RCH - provided with the  
termination) to the vent section or telescoping 
vent section, elbow or appliance collar as shown 
in 

Figures 32 & 33

 

in the same manner as any 

SV4.5 vent component (refer to 

Step E

).

L.

 

Install Firestop/Spacer at exterior wall 

-

 When using the 

square 

termination, install  

SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) 
Firestop/Spacer over the opening at the exterior 
side of the framing, long side up, with the 3 inch 
spacer clearance at the top as shown in 

Figure 

32

, and nail into place.

(The Firestop/Spacer may also be installed over 
the opening at the interior side of framing).

M. Install the Square Termination (SV4.5HT-2) 

Install the square termination - Fo

r the last step 

, from outside the exterior wall, slide the collars 
of the termination onto the adapter (the outer 
inside the outer and the inner outside the inner) 
until the termination seats against the exterior 
wall surface to which it will be attached.  Orient 
the housing of the termination with the arrow 
pointed upwards.  Secure the termination to 
the exterior wall.  

The horizontal termination 

must not be recessed into the exterior wall 
or siding

 by more than the 1-1/4" (32 mm) as 

shown in 

Figure 33

.

        

IMPORTANT

The vent termination is hot while 
in operation and for a period of 
time following the use of the fi re-
place.  To prevent contact with hot 
surfaces, we recommend the use 
of a 

Termination Guard

. See 

Items 

12 and 13

 on

 Page 33.  This can be 

purchased at your local dealer.

Summary of Contents for SSDVR-3530CNE

Page 1: ...T light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If yo...

Page 2: ...oms and Manufactured Homes Manufactured Homes See Manufactured Home Requirements on Page 7 for additional information PACKAGING The assembled vented gas fireplace heater is packaged with 1 One log set...

Page 3: ...kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4 5 and 6 show the appliances gas pressure requirements Manifold Gas Supply Pressure millivolt mod...

Page 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Page 5: ...ionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have these signs obtainfreshairi...

Page 6: ...elveslikethesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide...

Page 7: ...mm or less See Figure 6 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 7 on Page 8 Figure 6 Side Elevation View Note See Figure 33 on Pag...

Page 8: ...e meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service...

Page 9: ...w of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figure 10 At 8 1 4 side wall clearance a combustible...

Page 10: ...ot factory provided and bringinelectricalservicelineforforcedair circulating blower optional equipment b ElectronicAppliances Fieldwireandinstall operating control switch Step 5 Page 25 Install blower...

Page 11: ...re top vent only Louvered Front Model Shown Rear vent models only Electrical Inlet 2 3 4 x 2 70 x 51 Cover Plate W Knockout Right Side View 9 229 E B D C Front View 3 76 A 1 3 8 35 Optional ELECTRICAL...

Page 12: ...be aware that if tank size is too small i e under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can...

Page 13: ...appliance The vent pipe is tested to be run inside an enclosing wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe WARNIN...

Page 14: ...0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2...

Page 15: ...ectinglengthcombinations Elbowsare available in 90 and 45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent s...

Page 16: ...the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of un...

Page 17: ...usingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Se...

Page 18: ...restop Spacer SF4 5HF Figure 29 Rear Vent THREE ELBOWS Figure 30 Top Vent THREE ELBOWS VERTICAL VENT FIGURES TABLES CONTINUED HORIZONTAL OUTSIDE WALL TERMINATION SYSTEM Figure 31 and Figures 34 to 40...

Page 19: ...ush the vent component against the previous section until it fully engages then twist the componentclockwiserunningthedimplesdown and along the incline channels until they seat at the end of the chann...

Page 20: ...Termination J Assemble vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as described in Step B Assemble the vent system topoin...

Page 21: ...CCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 35 See Table 12 as an aid in venting component selection for a particular range of ex...

Page 22: ...ee Table 12 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES CONTINUED Table H H H1 Maximum HMaximum V Minimum fee...

Page 23: ...of horizontal run up to a maximum total H H1 H2 horizontal run of 20 feet Figure 40 Top Vent THREE 90 DEGREE ELBOWS Figure 39 Rear Vent THREE 90 DEGREE ELBOWS See Table 12 on Page 21 as an aid in ven...

Page 24: ...sely around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from...

Page 25: ...ed Electrical power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the con...

Page 26: ...s the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22 1 Canadian Electrical Code Step 6 CONNECTING GAS LINE Make gas line connections All codes require a shut offval...

Page 27: ...er HI LO flame adjustment knob and pilot and main gas OFF ON control knob are located below the glass panel enclosure The gas valve for electronic systems is also located below the glass enclosure pan...

Page 28: ...sts on the subfloor 5 Placethetoprightlog D asshown Thetop fork on log D fits into notch on log A as shown The bottom fork on log D rests on subfloor flange identified in photo 1 SSDV 4035 Install as...

Page 29: ...Item letters above correspond to photos B C D A A Notch Notch 2 C 3 Notchesonbottomoflog C fitsover2locatingbrackets Topforkonlog B fitsintonotchonlog A B A 4 D A 5 Topforkonlog D fitsintonotchonlog A...

Page 30: ...MODEL SSDV 4035 Log Placement Instructions D A 4 A Bottomoflog B restsonsubfloor B Topforkonlog D fitsintonotchonlog A asshown Topforkonlog B fitsintonotchonlog A as shown 1 Place Embers and Volcanic...

Page 31: ...glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to touch...

Page 32: ...ll Figure 58 See Page 6 for Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avo...

Page 33: ...L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing...

Page 34: ...Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV...

Page 35: ...qualified service agency performing thisinstallationassumesresponsibil ity for this conversion AVERTISSEMENT Cet quipement de conversion sera install par une agence qualifi e de service conform ment a...

Page 36: ...ning it clockwise Replace the plastic protecting cap Pilot for Honeywell Millivolt Gas Valve Loosening of Hex Fitting For Orifice Strip Tab Positioning Figure 63 7 16 in Open End Wrench Hood Hood Alig...

Page 37: ...emove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and red spring for propane gas u...

Page 38: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 38 NOTES...

Page 39: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 39 NOTES...

Page 40: ...CA 92865 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your...

Reviews: