background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

15

To add another vent component to a length of 
vent run, align the dimpled end over the inclined 
channel end of the previously installed section, 
adjusting the radial alignment until the four lock-
ing dimples are aligned with the inlets of the four 
incline channels of the previous section.  

Push the vent component against the previous 
section until it fully engages, then twist the 
component clockwise running the dimples down 
and along the incline channels until they seat at 
the end of the channels. 

This seating position 

is indicated by the alignment of the arrow and 
dimple as shown in

 

Figure 20.

D.

 

Install fi restop/spacer at ceiling -

 When 

using Secure Vent, use SV4.5VF fi restop/spacer 
at ceiling joists; when using Secure Flex, use 
SF4.5VF fi restop/spacer. If there is living space 
above the ceiling level, the fi restop/spacer 
must be installed on the bottom side of the 
ceiling. If attic space is above the ceiling, the 
fi restop/spacer must be installed on the top side 
of the joist. Route the vent sections through the 
framed opening and secure the fi restop/spacer 
with 8d nails or other appropriate fasteners at 
each corner. 

Remember to maintain 1" (25 

mm) clearance to combustibles, framing 
members, and attic or ceiling insulation 
when running vertical chimney sections. 
Attic insulation shield (96K94) may be used 
to obtain the required clearances indicated 
here. See installation accessories, 

Pages 

32 through 34.

E.

 

Support the vertical vent run sections -

Note - 

Proper venting support is very important. 

The weight of the vent must not be supported 
by the fi rplace in any degree.

Support the vertical portion of the venting 
system every 8 feet (2.4m) above the fi replace 
vent outlet. 

Figure 20

Align the dimple (four places) of the 
upper vent section with the opening 
of the locking incline channel on the 
lower vent section or appliance col-
lar.  Twist vent component clockwise 
to engage and seal until arrow and 
dimple align.

Dimple

Locking Incline 
Channel

Connected Vent 
Sections

Arrow

Arrow

Appliance Collar or 
Vent Section

Figure 19

10-1/2" Min. 

(267 mm)

10-1/2" Min. 

(267 mm)

Vertical (Offset) Installation

Analyze the vent routing and determine the 
quantities of vent sections and number of elbows 
required. Refer to 

Vertical Vent Figures and 

Tables on 

Pages 17 and 18 

 to select the type 

of vertical installation desired. Vent sections 
are available in net lengths of 4-1/2" (114 mm), 
10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2 " 
(876 mm) and 46-1/2" (1181 mm). Refer to the 

Vent Section Length Chart on 

Page 14 

for an 

aid in selecting length combinations. Elbows are 
available in 90° and 45° confi gurations. Refer 
to 

Figure 22 on Page 16 

 

for the SV4.5E45 and 

SV4.5E90 elbow dimensional specifi cations.

Where required, a 

telescopic vent section 

 

(SV4.5LA)

  may be used to provide the installer 

with an option in installing in tight and  confi ned 
spaces or where the vent run made up of fi xed 
length pieces develops a joint in a undesirable 
location, or will not build up to the required 
length. The SV4.5LA Telescopic Vent Section 
has an effective length of from 1-1/2" (38 mm) 
to 7-1/2" (191 mm). The SV4.5LA  is fi tted with 
a locking inclined channel end (identical to a 
normal vent section component) and a plain end 
with 3 pilot holes. Slip the plain end over the 
locking channel end of  a standard  SV4.5 vent 
component the required distance and secure 
with three screws.

Maintain a minimum 1" (25 mm) clearance to 
combustible materials for all vertical elements. 
Clearances for all horizontal elements are 3" 
(76 mm) on top, 1" (25 mm) on sides and 1" 
(25 mm) on the bottom.

A.

 

Frame ceiling opening -

 Use a plumb line 

from the ceiling above the appliance to locate 
center of the vertical run. Cut and/or frame an 
opening, 10-1/2" x 10-1/2"  (267mm x 267mm) 
inside dimensions, about this center mark 
(

Figure 19 

).

To attach a vent component to the appliance collar, 
align the dimpled end over the collar, adjusting the 
radial alignment until the four locking dimples are 
aligned with the inlet of the four inclined channels 
on the collar 

(refer to Figure 20)

.  Push the 

vent component against the collar until it fully 
engages, then twist the component clockwise, 
running the dimples down and along the incline 
channels until they seat at the end of the chan-
nels. The unitized design of the 

Secure Vent

 

components will engage and seal both the inner 
and outer pipe without the need for sealant or 
screws.  If desired, a #6 x 1/2" screw may be 
used at the joint, but is not required as the pipe 
will securely lock when twisted.

Note:

 An elbow may also be attached to the 

appliance collar.  Attach in the same manner 
as you would a vent section. 

C.

 

Attach vent components to each other 

-

 Other vent sections may be added to the 

previously installed section in accordance with 
the requirements of the vertical vent Figures 
and Tables.  

B.

 

Attach vent components to appliance 

-

 

Secure Vent

 SV4.5 direct vent system compo-

nents are unitized concentric pipe components 
featuring positive twist lock connections (

see 

Figure 20

)

All of the appliances covered in this document 
are fi tted with collars having locking inclined 
channels. The dimpled end  of the vent com-
ponents fi t over the appliance collar to create 
the positive twist lock connection.

Blocking

Support Straps
(Plumber's tape)

8 feet (2.4 m)

Maximum

1 inch (25.4 
mm) minimum 
clearance to 
combustibles

 Figure 21

Summary of Contents for SSDVR-3530CNE

Page 1: ...T light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If yo...

Page 2: ...oms and Manufactured Homes Manufactured Homes See Manufactured Home Requirements on Page 7 for additional information PACKAGING The assembled vented gas fireplace heater is packaged with 1 One log set...

Page 3: ...kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4 5 and 6 show the appliances gas pressure requirements Manifold Gas Supply Pressure millivolt mod...

Page 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Page 5: ...ionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have these signs obtainfreshairi...

Page 6: ...elveslikethesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide...

Page 7: ...mm or less See Figure 6 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 7 on Page 8 Figure 6 Side Elevation View Note See Figure 33 on Pag...

Page 8: ...e meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service...

Page 9: ...w of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figure 10 At 8 1 4 side wall clearance a combustible...

Page 10: ...ot factory provided and bringinelectricalservicelineforforcedair circulating blower optional equipment b ElectronicAppliances Fieldwireandinstall operating control switch Step 5 Page 25 Install blower...

Page 11: ...re top vent only Louvered Front Model Shown Rear vent models only Electrical Inlet 2 3 4 x 2 70 x 51 Cover Plate W Knockout Right Side View 9 229 E B D C Front View 3 76 A 1 3 8 35 Optional ELECTRICAL...

Page 12: ...be aware that if tank size is too small i e under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can...

Page 13: ...appliance The vent pipe is tested to be run inside an enclosing wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe WARNIN...

Page 14: ...0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2...

Page 15: ...ectinglengthcombinations Elbowsare available in 90 and 45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent s...

Page 16: ...the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of un...

Page 17: ...usingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Se...

Page 18: ...restop Spacer SF4 5HF Figure 29 Rear Vent THREE ELBOWS Figure 30 Top Vent THREE ELBOWS VERTICAL VENT FIGURES TABLES CONTINUED HORIZONTAL OUTSIDE WALL TERMINATION SYSTEM Figure 31 and Figures 34 to 40...

Page 19: ...ush the vent component against the previous section until it fully engages then twist the componentclockwiserunningthedimplesdown and along the incline channels until they seat at the end of the chann...

Page 20: ...Termination J Assemble vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as described in Step B Assemble the vent system topoin...

Page 21: ...CCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 35 See Table 12 as an aid in venting component selection for a particular range of ex...

Page 22: ...ee Table 12 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES CONTINUED Table H H H1 Maximum HMaximum V Minimum fee...

Page 23: ...of horizontal run up to a maximum total H H1 H2 horizontal run of 20 feet Figure 40 Top Vent THREE 90 DEGREE ELBOWS Figure 39 Rear Vent THREE 90 DEGREE ELBOWS See Table 12 on Page 21 as an aid in ven...

Page 24: ...sely around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from...

Page 25: ...ed Electrical power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the con...

Page 26: ...s the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22 1 Canadian Electrical Code Step 6 CONNECTING GAS LINE Make gas line connections All codes require a shut offval...

Page 27: ...er HI LO flame adjustment knob and pilot and main gas OFF ON control knob are located below the glass panel enclosure The gas valve for electronic systems is also located below the glass enclosure pan...

Page 28: ...sts on the subfloor 5 Placethetoprightlog D asshown Thetop fork on log D fits into notch on log A as shown The bottom fork on log D rests on subfloor flange identified in photo 1 SSDV 4035 Install as...

Page 29: ...Item letters above correspond to photos B C D A A Notch Notch 2 C 3 Notchesonbottomoflog C fitsover2locatingbrackets Topforkonlog B fitsintonotchonlog A B A 4 D A 5 Topforkonlog D fitsintonotchonlog A...

Page 30: ...MODEL SSDV 4035 Log Placement Instructions D A 4 A Bottomoflog B restsonsubfloor B Topforkonlog D fitsintonotchonlog A asshown Topforkonlog B fitsintonotchonlog A as shown 1 Place Embers and Volcanic...

Page 31: ...glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to touch...

Page 32: ...ll Figure 58 See Page 6 for Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avo...

Page 33: ...L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing...

Page 34: ...Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV...

Page 35: ...qualified service agency performing thisinstallationassumesresponsibil ity for this conversion AVERTISSEMENT Cet quipement de conversion sera install par une agence qualifi e de service conform ment a...

Page 36: ...ning it clockwise Replace the plastic protecting cap Pilot for Honeywell Millivolt Gas Valve Loosening of Hex Fitting For Orifice Strip Tab Positioning Figure 63 7 16 in Open End Wrench Hood Hood Alig...

Page 37: ...emove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and red spring for propane gas u...

Page 38: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 38 NOTES...

Page 39: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 39 NOTES...

Page 40: ...CA 92865 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your...

Reviews: