If the vent system extends more than 5 feet (1.5 
m) above the roof fl ashing, stabilizers may be 
necessary. Additional screws may be used at 
section joints for added stability. Guide wires 
may be attached to the joint for additional sup-
port on multiple joint confi gurations.

G.

 

Continue installation of horizontal/inclined 

sections -

 Continue with the installation of the 

straight vent sections in horizontal/inclined run 
as described in 

Step C.

 Install support straps 

every 5 ft. (1.52 m) along horizontal/inclined 
vent runs using conventional plumber’s tape. 

See Page 19, Figure 31. It is very important 
that the horizontal/inclined run be maintained 
in a straight (no dips) and recommended to be 
in a slightly elevated plane, in a direction away 
from the fi replace of

 1/4 " rise per foot (20 mm 

per meter) which is ideal, though rise per foot 
run ratios that are smaller are acceptable all the 
way down to at or near level

.

  Use a carpenter’s 

level to measure from a constant surface and 
adjust the support straps as necessary. 

It is important to maintain the required clear-
ances to combustibles: 1" (25 mm) at all sides 
for all vertical runs; and 3" (76 mm) at the top, 
1" (25 mm) at sides, and 1" (25 mm) at the 
bottom for all horizontal/inclined runs.

H.

 

Frame roof opening -

 Identify location for 

vent at the roof. Cut and/or frame opening per 
Roof Framing Chart and 

Figure 23

.

One method of support is by utilizing fi eld pro-
vided support straps (conventional plumber's 
tape).  Secure the plumber's tape to the framing 
members with nails or screws.

 

Loop the tape 

around the vent, securing the ends of the tape 
to the framing. If desired, sheet metal screws #6 
x 1/2" length may be used to secure the support 
straps to the vent pipe.  Refer to 

Figure 21

F.

 

Change vent direction to horizontal/inclined 

run -

 At transition from or to a horizontal/in-

clined run, install the SV4.5E45 and SV4.5E90 
elbows in the same manner as the straight vent 
sections. The elbows feature a twist section to 
allow them to be routed about the center axis 
of their initial collar section to align with the 
required direction of the next vent run element. 

Twist elbow sections in a clockwise direction 
only so as to avoid the possiblity of unlocking 
any of the previously connected vent sections.

 

See 

Figure 22

.

K.

 Install the vertical termination - 

The fi nal 

step involves installation of the SV4.5CGV-1 
Vertical Termination.  Extend the vent sections 
to the height as shown in the "Vertical vent ter-
mination section" on 

Page 7

.  The SV4.5CGV-1 

Vertical Termination 

(Figure 25)

 can be installed  

in the exact same fashion as any other 

Secure 

Vent

 section. Align the termination over the 

end of the previously installed section, adjust-
ing the radial alignment until the four locking 
dimples of the termination are aligned with 
the inlets of the four incline channels of the 
last vent section.  Push the termination down 
until it fully engages, then twist the termination 
clockwise running the dimples down and along 
the incline channels until they are seated at the 
end of the channels.

I.

 

Install the roof fl ashing - 

Extend the vent 

sections through the roof structure. Install the 
roof fl ashing over the vent section and posi-
tion such that the vent column rises vertically 
(use carpenters level) 

(

Figure 24

 

)

. Nail along 

perimeter to secure fl ashing or adjust roofi ng 
to overlap the fl ashing edges at top and sides 
only and trim where necessary. Seal the top 
and both sides of the fl ashing with waterproof 
caulking.

J.

 

Install the storm collar -

 Install the storm 

collar, supplied with the fl ashing, over the 
vent/fl ashing joint. See 

Figure 24. 

Loosen the 

storm collar screw. Slide collar down until it 
meets the top of the fl ashing. Tighten the ad-
justing screw. Apply non-combustible caulking 
or mastic around the circumference of the joint 
to provide a water tight seal.

Figure 22

7-5/8”

(194 mm)

4-13/16 

(122 mm)

Swivel Joint

(360° swivel)

SV4.5E45

45° Elbow)

Swivel Joint

(360° swivel)

SV4.5E90

90° Elbow)

(206 mm)

8-1/8"

Figure 24

Storm
Collar

Figure 25

Framing Dimensions for Roof

Inches (millimeters)

Pitch

C

D

0/12

10-1/2 in.
(267 mm)

10-1/2 in.
(267 mm)

6/12

10-1/2 in.
(267 mm)

12 in.

(305 mm)

12/12

10-1/2 in.
(267 mm)

17 3/4 in.

(451 mm)

C

D

Figure 23

 - Roof Framing

Summary of Contents for SSDVR-3530CNE

Page 1: ...T light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If yo...

Page 2: ...oms and Manufactured Homes Manufactured Homes See Manufactured Home Requirements on Page 7 for additional information PACKAGING The assembled vented gas fireplace heater is packaged with 1 One log set...

Page 3: ...kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4 5 and 6 show the appliances gas pressure requirements Manifold Gas Supply Pressure millivolt mod...

Page 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Page 5: ...ionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have these signs obtainfreshairi...

Page 6: ...elveslikethesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide...

Page 7: ...mm or less See Figure 6 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 7 on Page 8 Figure 6 Side Elevation View Note See Figure 33 on Pag...

Page 8: ...e meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service...

Page 9: ...w of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figure 10 At 8 1 4 side wall clearance a combustible...

Page 10: ...ot factory provided and bringinelectricalservicelineforforcedair circulating blower optional equipment b ElectronicAppliances Fieldwireandinstall operating control switch Step 5 Page 25 Install blower...

Page 11: ...re top vent only Louvered Front Model Shown Rear vent models only Electrical Inlet 2 3 4 x 2 70 x 51 Cover Plate W Knockout Right Side View 9 229 E B D C Front View 3 76 A 1 3 8 35 Optional ELECTRICAL...

Page 12: ...be aware that if tank size is too small i e under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can...

Page 13: ...appliance The vent pipe is tested to be run inside an enclosing wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe WARNIN...

Page 14: ...0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2...

Page 15: ...ectinglengthcombinations Elbowsare available in 90 and 45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent s...

Page 16: ...the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of un...

Page 17: ...usingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Se...

Page 18: ...restop Spacer SF4 5HF Figure 29 Rear Vent THREE ELBOWS Figure 30 Top Vent THREE ELBOWS VERTICAL VENT FIGURES TABLES CONTINUED HORIZONTAL OUTSIDE WALL TERMINATION SYSTEM Figure 31 and Figures 34 to 40...

Page 19: ...ush the vent component against the previous section until it fully engages then twist the componentclockwiserunningthedimplesdown and along the incline channels until they seat at the end of the chann...

Page 20: ...Termination J Assemble vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as described in Step B Assemble the vent system topoin...

Page 21: ...CCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 35 See Table 12 as an aid in venting component selection for a particular range of ex...

Page 22: ...ee Table 12 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES CONTINUED Table H H H1 Maximum HMaximum V Minimum fee...

Page 23: ...of horizontal run up to a maximum total H H1 H2 horizontal run of 20 feet Figure 40 Top Vent THREE 90 DEGREE ELBOWS Figure 39 Rear Vent THREE 90 DEGREE ELBOWS See Table 12 on Page 21 as an aid in ven...

Page 24: ...sely around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from...

Page 25: ...ed Electrical power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the con...

Page 26: ...s the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22 1 Canadian Electrical Code Step 6 CONNECTING GAS LINE Make gas line connections All codes require a shut offval...

Page 27: ...er HI LO flame adjustment knob and pilot and main gas OFF ON control knob are located below the glass panel enclosure The gas valve for electronic systems is also located below the glass enclosure pan...

Page 28: ...sts on the subfloor 5 Placethetoprightlog D asshown Thetop fork on log D fits into notch on log A as shown The bottom fork on log D rests on subfloor flange identified in photo 1 SSDV 4035 Install as...

Page 29: ...Item letters above correspond to photos B C D A A Notch Notch 2 C 3 Notchesonbottomoflog C fitsover2locatingbrackets Topforkonlog B fitsintonotchonlog A B A 4 D A 5 Topforkonlog D fitsintonotchonlog A...

Page 30: ...MODEL SSDV 4035 Log Placement Instructions D A 4 A Bottomoflog B restsonsubfloor B Topforkonlog D fitsintonotchonlog A asshown Topforkonlog B fitsintonotchonlog A as shown 1 Place Embers and Volcanic...

Page 31: ...glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to touch...

Page 32: ...ll Figure 58 See Page 6 for Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avo...

Page 33: ...L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing...

Page 34: ...Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV...

Page 35: ...qualified service agency performing thisinstallationassumesresponsibil ity for this conversion AVERTISSEMENT Cet quipement de conversion sera install par une agence qualifi e de service conform ment a...

Page 36: ...ning it clockwise Replace the plastic protecting cap Pilot for Honeywell Millivolt Gas Valve Loosening of Hex Fitting For Orifice Strip Tab Positioning Figure 63 7 16 in Open End Wrench Hood Hood Alig...

Page 37: ...emove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and red spring for propane gas u...

Page 38: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 38 NOTES...

Page 39: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 39 NOTES...

Page 40: ...CA 92865 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your...

Reviews: