background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

7

Termination Heights For Vents 

Above Flat Or Sloped Roofs

Ref. NFPA 54 / ANSI Z223.1, 7.6

Roof Pitch

* Feet

* Meters

Flat to 6/12

1.0

0.3

6/12 to 7/12

1.25

0.38

7/12 to 8/12

1.5

0.46

8/12 to 9/12

2.0

0.61

9/12 to 10/12

2.5

0.76

10/12 to 11/12

3.25

0.99

11/12 to 12/12

4.0

1.22

12/12 to 14/12

5.0

1.52

14/12 to 16/12

6.0

1.83

16/12 to 18/12

7.0

2.13

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8.0

2.44

The vent / air intake termination clearances 
above the high side of an angled roof is as 
shown in the following chart:

12

X

Roof Pitch is X/12

2 FT
MIN.

2 FT MIN.

Lowest

Discharge

Opening

H*

*H = MINIMUM HEIGHT FROM ROOF TO

LOWEST DISCHARGE OPENING OF VENT

TERMINATION HEIGHTS FOR VENTS ABOVE

FLAT OR SLOPED ROOFS

Horizontal Overhang

Vertical

Wall

Vent

Termination

Storm Collar

Concentric

Vent Pipe

Flashing

1 inch (25.4 mm) Minimum
Clearance to Combustibles

Figure 5

Vertical Vent Termination  Clearances

VENT TERMINATION CLEARANCES

These instructions should be used as a guide-
line and do not supersede local codes in any 
way. Install vent according to local codes, 
these instructions, the current National Fuel 
Gas Code (ANSI-Z223.1) in the USA or the 
current standards of CAN/CGA-B149.1 and 
-B149.2 in Canada.

Terminate multiple vent terminations according to 
the installation codes listed above.

Terminate single  vent caps relative to building 
components according to 

Figure 5

.

Horizontal Vent Termination Clearances

The horizontal vent termination must have 
a minimum of 3" (76 mm) clearance to any 
overhead combustible projection of 2 1/2" (64 
mm) or less. See  

Figure 6. 

 For projections 

exceeding 2 1/2"  (64 mm), see 

Figure 6

. For 

additional vent location restrictions refer to 

Figure 7 on Page 8

.

Figure 6

Side Elevation View

Note - See Figure 33 on 
Page 20 for the exterior 
wall recess allowances 
of the square horizontal 
termination.

3"

(76 mm)

12"

(305 mm)

Combustible Projection greater 

 

Horizontal Vent Termination Clearances

Combustible Projection

2-1/2 inches or less in length

18"

(457 mm)

Ventilated

Soffit

Unventilated

Soffit

than 2-1/2 inches in length

Termination Kit

MANUFACTURED HOME 
REQUIREMENTS

This appliance may be installed in an after-
market permanently located, manufactured  
home (USA only) or mobile home, where not 
prohibited by local codes. 

Cet appareil peut être installé dans un maison 
préfabriquée (É.-U. seulement) ou mobile  déjà  
installée à demeure si les réglements locaux 
le permettent.

Manufactured Home installations must be 
installed in accordance with these instructions 
and the following standards / codes:

•  Manufactured Home Construction and 

Safety Standard Title 24 CFR, Part 3280, or 
the current Standard for Fire Safety Criteria 
for Manufactured Home Installations, Sites 
and Communities ANSI / NFPA 501A in the 
USA, and CAN / CSA Z240 MH Mobile Home 
Standard in Canada

•  (when applicable) The American National 

Standard for Manufactured Homes (NCSBCS 
/ ANSI A225.1 - latest edition). 

       CAUTIONS

Ensure that the cross members 
are not cut or weakened during 
installation. The structural integ-
rity of the manufactured home 
fl oor, wall, and ceiling / roof must 
be maintained. 

This appliance must be grounded 
to the chassis of the manufac-
tured home in accordance with 
local codes or in the absence of 
local codes, with the National 
Electrical Code ANSI / NFPA 70 
- latest edition or the Canadian 
Electrical Code CSA C22.1 - latest 
edition.

Summary of Contents for SSDVR-3530CNE

Page 1: ...T light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If yo...

Page 2: ...oms and Manufactured Homes Manufactured Homes See Manufactured Home Requirements on Page 7 for additional information PACKAGING The assembled vented gas fireplace heater is packaged with 1 One log set...

Page 3: ...kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4 5 and 6 show the appliances gas pressure requirements Manifold Gas Supply Pressure millivolt mod...

Page 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Page 5: ...ionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have these signs obtainfreshairi...

Page 6: ...elveslikethesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide...

Page 7: ...mm or less See Figure 6 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 7 on Page 8 Figure 6 Side Elevation View Note See Figure 33 on Pag...

Page 8: ...e meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service...

Page 9: ...w of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figure 10 At 8 1 4 side wall clearance a combustible...

Page 10: ...ot factory provided and bringinelectricalservicelineforforcedair circulating blower optional equipment b ElectronicAppliances Fieldwireandinstall operating control switch Step 5 Page 25 Install blower...

Page 11: ...re top vent only Louvered Front Model Shown Rear vent models only Electrical Inlet 2 3 4 x 2 70 x 51 Cover Plate W Knockout Right Side View 9 229 E B D C Front View 3 76 A 1 3 8 35 Optional ELECTRICAL...

Page 12: ...be aware that if tank size is too small i e under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can...

Page 13: ...appliance The vent pipe is tested to be run inside an enclosing wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe WARNIN...

Page 14: ...0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2...

Page 15: ...ectinglengthcombinations Elbowsare available in 90 and 45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent s...

Page 16: ...the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of un...

Page 17: ...usingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Se...

Page 18: ...restop Spacer SF4 5HF Figure 29 Rear Vent THREE ELBOWS Figure 30 Top Vent THREE ELBOWS VERTICAL VENT FIGURES TABLES CONTINUED HORIZONTAL OUTSIDE WALL TERMINATION SYSTEM Figure 31 and Figures 34 to 40...

Page 19: ...ush the vent component against the previous section until it fully engages then twist the componentclockwiserunningthedimplesdown and along the incline channels until they seat at the end of the chann...

Page 20: ...Termination J Assemble vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as described in Step B Assemble the vent system topoin...

Page 21: ...CCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 35 See Table 12 as an aid in venting component selection for a particular range of ex...

Page 22: ...ee Table 12 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES CONTINUED Table H H H1 Maximum HMaximum V Minimum fee...

Page 23: ...of horizontal run up to a maximum total H H1 H2 horizontal run of 20 feet Figure 40 Top Vent THREE 90 DEGREE ELBOWS Figure 39 Rear Vent THREE 90 DEGREE ELBOWS See Table 12 on Page 21 as an aid in ven...

Page 24: ...sely around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from...

Page 25: ...ed Electrical power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the con...

Page 26: ...s the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22 1 Canadian Electrical Code Step 6 CONNECTING GAS LINE Make gas line connections All codes require a shut offval...

Page 27: ...er HI LO flame adjustment knob and pilot and main gas OFF ON control knob are located below the glass panel enclosure The gas valve for electronic systems is also located below the glass enclosure pan...

Page 28: ...sts on the subfloor 5 Placethetoprightlog D asshown Thetop fork on log D fits into notch on log A as shown The bottom fork on log D rests on subfloor flange identified in photo 1 SSDV 4035 Install as...

Page 29: ...Item letters above correspond to photos B C D A A Notch Notch 2 C 3 Notchesonbottomoflog C fitsover2locatingbrackets Topforkonlog B fitsintonotchonlog A B A 4 D A 5 Topforkonlog D fitsintonotchonlog A...

Page 30: ...MODEL SSDV 4035 Log Placement Instructions D A 4 A Bottomoflog B restsonsubfloor B Topforkonlog D fitsintonotchonlog A asshown Topforkonlog B fitsintonotchonlog A as shown 1 Place Embers and Volcanic...

Page 31: ...glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to touch...

Page 32: ...ll Figure 58 See Page 6 for Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avo...

Page 33: ...L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing...

Page 34: ...Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV...

Page 35: ...qualified service agency performing thisinstallationassumesresponsibil ity for this conversion AVERTISSEMENT Cet quipement de conversion sera install par une agence qualifi e de service conform ment a...

Page 36: ...ning it clockwise Replace the plastic protecting cap Pilot for Honeywell Millivolt Gas Valve Loosening of Hex Fitting For Orifice Strip Tab Positioning Figure 63 7 16 in Open End Wrench Hood Hood Alig...

Page 37: ...emove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and red spring for propane gas u...

Page 38: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 38 NOTES...

Page 39: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 39 NOTES...

Page 40: ...CA 92865 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your...

Reviews: