VENTING INSTALLATION  

Continued

Figure 9 - Installing the Horizontal Termination

9.  Continue installation of horizontal/inclined sections

Continue with the installation of the straight vent sections 

in horizontal/inclined run. Install support straps every 

5 ft. (1.52 m) along horizontal/inclined vent runs using 

conventional plumber’s tape (Figure 8, page 14). Maintain 

the horizontal/inclined run in a straight (no dips), slightly 

elevated plane. The recommended incline is approximately 

1/4” per 1 ft (20 mm per 1 m) horizontal, in a direction 

away from the fireplace. Smaller rise per foot run ratios are 

acceptable all the way to at or near level. Use a carpenter’s 

level to measure from a constant surface and adjust the sup-

port straps as necessary. Maintain the required clearances 

to combustibles (Page 9).

10.  Assemble the vent run to the exterior wall

—If not previ-

ously measured, locate the center of the vent at the exterior 

wall. Prepare the opening. Assemble the vent system until 

the terminus of the last section is within 7” (178 mm) to 

11 1/4” (286 mm) inboard of the exterior surface to which 

the SV4.5 HT termination is to be attached (Figure 9). If the 

terminus of the last section is not within this distance, use 

the telescopic vent section SV4.5LA, as the last vent section. 

Table 1, page 16 lists the additional venting components 

needed (in addition to the termination and adaptor) for a 

range of wall thicknesses.

11.  Attach the termination adaptor

—Attach the adaptor 

(SV4.5RCH, provided with the termination) to the vent sec-

tion or telescoping vent section, elbow or fireplace collar 

(Figure 9).

12.  Install the firestop/spacer at the exterior wall

—When us-

ing the square termination, install SV4.5HF Firestop/Spacer 

over the opening at the exterior side of the framing, long 

side up, with the 3” spacer clearance at the top (Figure 9) 

and nail into place.

NOTE:

 The firestop/spacer may also be installed over the 

opening at the interior side of the framing.

13.  Install the termination (SV4.5HTKCT)

—From outside the 

exterior wall, slide the collars of the termination onto the 

adaptor (the outer over the outer and the inner inside the 

inner) until the termination seats against the exterior wall 

surface to which it will be attached. Orient the housing of 

the termination with the arrow pointed upwards. Secure the 

termination to the exterior wall. The horizontal termination 

must not be recessed into the exterior wall or siding by more 

than the 1 1/4” (32 mm) (Figure 10, page 16).

NOTE:

 The vent termination is hot while in operation and for 

a period of time following the use of the fireplace. To pre-

vent contact with hot surfaces, use a horizontal termination 

guard; available for purchase at your local dealer.

The horizontal terminations have been designed to perform 

in a wide range of weather conditions. Our terminations meet 

or exceed industry standards.
When selecting the locations of your horizontal terminations, 

do not place the termination where water from eaves and ad-

joining rooflines may create a heavy flow of cascading water 

onto the termination cap. If the cap must be placed where the 

possibility of cascading water exists, it is the responsibility of 

the builder to direct the water away from the termination cap 

by using gutters or other means.
Take care to carefully follow the installation instructions for 

the termination, including the use of silicone caulking where 

required.

Termination

10 1/2”

(267mm)

7”

(178)

5 1/8”

(130 mm)

12 1/8”

(308 mm)

Note: Centerline of Vent Piping is

NOT the Same as the Centerline of

the Framed Opening.

6 to 48” Vent Section,

Telescopic vent section,

Elbow or Appliance Collar

53” (1346 mm) Min. 

Plus 1/4”(6 mm) 

Rise per Foot  

Base of Appliance

3”

(76 mm)

1” 

(26 mm)

Adaptor

SV4.5RCH

To help minimize water 

infiltration it is recommended that 

the Firestop/Spacer (SV4.5HF) 

be installed on the exterior 

side of the wall.

NOTE:

 To help minimize wa-

ter infiltration install the 

firestop/spacer (SV4.5HF) on 

the exterior side of the wall..

Summary of Contents for DRL4543TEN

Page 1: ...icinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immedia...

Page 2: ...MADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitr...

Page 3: ...famille soient conscients du danger de br lure encouru Les surfaces de votre foyer deviennent EXTR MEMENT CHAUDES La vitre situ e l avant du foyer atteint des temp ratures EXTR MEMENT LEV ES et peut...

Page 4: ...s viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une bar...

Page 5: ...young children and other at risk individuals out of the room and away from hot surfaces This vented gas fireplace is a sealed combustion gas fireplace de signed for residential applications This firep...

Page 6: ...uard or barrier removed for servicing an appliance must be replaced prior to operating the appliance SAFETY Continued Installation and repair should be done by a qualified service person The appliance...

Page 7: ...NFPA 54 USA or the current CSA B149 1 Installation Code Canada Available from American National Standards Institute Inc 25 West 43rd Street 4th floor New York NY 10036 National Fire Protection Associa...

Page 8: ...MONWEALTH OF MASSACHUSETTS Massachusetts Horizontal Vent Requirements In the Commonwealth of Massachusetts horizontal terminations installed less than seven 7 feet above the finished grade must comply...

Page 9: ...t Do not locate termination cap and outside air vent where excessive snow or ice build up may occur Be sure to clear vent termination area after snow falls to prevent accidental blockage of venting sy...

Page 10: ...tible Material May Be Used TOP VIEW SAFE ZONE Perpendicular Wall 33 4 to Face Opening 5 53 1 4 1353 mm 53 1 4 1353 mm 38 965 mm 38 965 mm STUDS MOUNTED FLAT INSIDE OF NAILING FLANGE 15 1 4 387 mm MOUN...

Page 11: ...m 16 1 2 419 mm 8 1 4 210 mm 29 7 8 759 mm 29 7 8 759 mm 3 1 2 89 mm 16 3 8 416 mm 7 1 8 181 mm 1 7 8 48 mm 8 1 4 210 mm 4 1 8 105 mm 44 1 8 1121 mm 55 1 8 1400 mm 47 1194 mm 1 25 mm 1 25 mm 52 1321 m...

Page 12: ...en 10 000 and 50 000 12 30 cm in Canada if between 10 000 and 100 000 12 30 cm in US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In C...

Page 13: ...estops when penetrating ceilings or attic spaces For installation of fireplace at elevations of 4000 feet or greater pay special attention to venting requirement recommendations WARNING Read all instr...

Page 14: ...rate a ceiling use plumb line to locate the center above the fireplace Cut and or frame an opening 10 1 2 x 10 1 2 267 x 267 mm inside dimensions about this center Figure 17 page 19 4 Attach the vent...

Page 15: ...he firestop spacer may also be installed over the opening at the interior side of the framing 13 Install the termination SV4 5HTKCT From outside the exterior wall slide the collars of the termination...

Page 16: ...silicone caulking to seal the top and sides of the termination up to the underlayment stucco or masonry wall surface Caulk Caulk NOTE See table 1 for wall thickness ranges when using SV4 5HTKCT termin...

Page 17: ...seal both the inner and outer vent pipe 3 If desired a 6 x 1 2 screw can be used at the joint but is not required as the pipe will securely lock when twisted Figure 12 Figure 11 Connecting vent compon...

Page 18: ...op spacer SF4 5VF When using Secure Flex use wall firestop spacer SF4 5HF Wall firestop spacer SV4 5HF Ceiling firestop spacer SV4 5VF H V H1 V1 VENTING INSTALLATION Continued V Vertical Minimum Requi...

Page 19: ...Frame the ceiling opening Use a plumb line from the ceil ing above the fireplace to locate the center of the vertical run Cut and or frame an opening 10 1 2 x 10 1 2 267 x 267 mm inside dimensions abo...

Page 20: ...oof flashing over the vent sec tion and position such that the vent column rises vertically use carpenters level Nail along perimeter to secure flashing or adjust roofing to overlap the flashing edges...

Page 21: ...west discharge opening H H minimum height from roof to lowest discharge opening of vent Horizontal overhang Vertical wall Vent termination Storm collar Concentric vent pipe Flashing 1 26 mm minimum cl...

Page 22: ...OR VENTING KITS AND COMPONENTS Table 3 Listed Components Listed Secure Flex Components Continued F1801 SFKIT36CT Compact Termination for flex with 36 914 mm compressed flex F1802 SFKIT48CT Compact Ter...

Page 23: ...vent 4 Slide the inner flex vent over the adaptor collar at least 1 3 4 5 NOTE Ensure the flex vent is free from damage or tears 6 Slide the gear clamp down and tighten it fully to secure the flexible...

Page 24: ...ified service person must con nect fireplace to gas supply Follow all local codes CAUTION For propane LP units never connect fireplace directly to the propane LP supply This heater requires an externa...

Page 25: ...ply line as shown in Figure 28 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and fireplace Locate sediment trap drip leg where trappe...

Page 26: ...eplace or using compressed air 3 Check all joints from propane LP supply tank or gas meter to equipment shutoff valve see Figure 31 or Figure 32 Apply noncorrosive leak detection fluid to all joints B...

Page 27: ...x using your fingers or the latch opener provided 3 Hook opener over latch as shown in Figure 34 Swing the bot tom of the opener down toward the door You will not need to pull down 4 Tilt open glass d...

Page 28: ...embers to refresh the ember bed during annual maintenance Reinstall the included barrier J7457 WARNING Reinstall any barrier removed before operating the fireplace The barrier is designed to reduce th...

Page 29: ...g Replacing Glass Door page 27 of this manual Installing Access Door Retaining Brackets 1 Screw access door retaining brackets into the inner side face using 2 screws on both the left and right side a...

Page 30: ...use only non combustible materials You may extend up to the edge of the exterior door covering up the screws used for installation Installing Outdoor Barrier F2253 1 Using a flat head screwdriver pop...

Page 31: ...nterrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette...

Page 32: ...nge flamewillalsobepresent Openwindowtoventsmell This will only last a few hours 1 STOP Read the safety information in column 1 2 Turn off all electric power to fireplace 3 Turn safety shutoff switch...

Page 33: ...a Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterruptorquecontrola la chimenea Figura A o en el termostato de pared Figura...

Page 34: ...e entire flame may be blue and will gradually turn yellow orange during the first 15 minutes of operation If the flame remains blue or if the flame is orange with evidence of sooting black tip the air...

Page 35: ...rom glass If glass has been broken carefully remove glass door see Remov ing Replacing Glass Door page 27 Vacuum all glass pieces with a shop vacuum CAUTION Do not vacuum if pieces are hot Use only gl...

Page 36: ...rammed to the Remote Control transmitter To program the module make sure the system has power locate the learn button on left side as shown in Figure 50 Press and release the learn button There will b...

Page 37: ...order above by pressing the MODE Zone or the MODE SET Button MANUAL OFF MODE Transmits flame OFF command LCD Displays MODE Zone OFF is displaye ROOM TEMP Zone Measured temperature is displayed SET TEM...

Page 38: ...OCK icon will appear in the MODE Zone If any touch zone or button is pressed when activated the LCD backlight will illuminate and the LOCK icon will flash for 5 seconds in the MODE Zone SENSOR SAFETY...

Page 39: ...tor 110V MAX 15 AMPS 110V MAX 15 AMPS To Rocker Switch To J Box Pilot Main HI LO DC Motor Drive J7860 Light Module J7865 J7864 J7868 Black Brown Red Orange Orange Green To Ground BATTERY PACK Black Bl...

Page 40: ...y other possible obstructions 4 Contact your gas supplier to check pres sure 5 Have a qualified technician replace pilot line 6 Replace control valve Refer to Parts page 43 7 Checkthatmainpowerisonand...

Page 41: ...nfiguration 1 Air holes at burner inlet blocked 2 Burner flame holes blocked 3 Improper venting or excessive blockage OBSERVED PROBLEM Gas odor even when gas control valve is off Gas odor during combu...

Page 42: ...2 3 1 4 4 5 7 8 9 10 12 13 14 15 16 18 17 19 20 11 6 4 4 PARTS BURNER ASSEMBLY This list contains replaceable parts used in your fireplace When ordering parts follow the instructions listed under Rep...

Page 43: ...11 J7852 Flextube 1 12 J7853 Burner Gasket 2 13 J7854 Power Module 1 14 J7855 Battery Backup 1 15 J7856 Battery Backup Bracket 1 16 J7857 Valve Bracket 1 17 J7858 Valve NG 1 J7859 Valve LP 1 18 J7860...

Page 44: ...Superiorfireplaces US com 126718 01_D 44 1 2 3 6 7 7 9 4 12 11 14 13 10 15 8 5 16 17 18 19 21 20 PARTS MODELS DRL4543TEN AND DRL4543TEP...

Page 45: ...ng Bracket 2 11 J7883 Ceramic Door Assembly 1 12 J7884 Cover Assembly Mesh Linear DV 1 13 J7885 Corner Bracket 4 14 J7886 Side Walls 2 15 J7887 Pebble Pan 1 16 J7888 Rear Wall 1 17 J7889 Rail Barrier...

Page 46: ...ville TN 37210 Visit us at Superiorfireplaces US com SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition fireplace will not produce specified heat pro...

Page 47: ...urn either natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a f...

Page 48: ...ealer name P126718 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and produ...

Reviews: