Table 23 - Top Vent—Three 90° Elbows

H Maximum

V Minimum

feet

meters

feet

meters

5

1.524

Elbow only

5

1.524

1

0.305

10

3.048

2

0.610

15

4.572

3

0.914

20

6.096

4

1.219

H + H

1

 = 25 ft (7.62 m) maximum

V + V

1

 + H + H

1

 = 60 ft (18.288 m) maximum

Install the U-shaped vent restrictor in any vent run with more than 4 

ft of vertical rise. See 

Page 24 

for more information.

See 

Table 19, Page 36

  as an aid in venting component selection for a 

particular range of exterior wall thicknesses.
If 20 ft of (H) horizontal vent run is needed, then 4 ft minimum of (V) vertical 

vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 ft of (V) vertical, you are 

allowed 5 ft of (H) horizontal run, up to a maximum horizontal run of 20 ft 

(6.096 m).

NOTE

 The Wall Heatshield provided shall be installed per 

instructions on Page 34 (see instruction #12 and Figure 26) 

DRL3535/DRL4545 model series only.
NOTE: 35” & 45” model = Strongly recommend at least 1 ft of vertical 

rise directly off top of unit.

55” = 1 ft of vertical rise is required directly off unit.

  *

When using 

Secure Flex

, use

    Ceiling Firestop/Spacer 

SF4.5VF

.

**

When using 

Secure Flex

, use

    Wall Firestop/Spacer 

SF4.5HF

Ceiling

Firestop/Spacer

SV4.5VF*

Wall Firestop/Spacer 

SV4.5HF**

V

H

V1

Wall Firestop/Spacer 

SV4.5HF**

1

H

Wall firestop/spacer 

SV4.5HF **

When using Secure Flex

®

, use 

ceiling firestop/spacer SF4.5VF.

When using Secure Flex, use wall 

firestop/spacer SF4.5HF.

*

**

Wall firestop/

spacer SV4.5HF **

Ceiling 

firestop/spacer 

SV4.5VF *

H

V

H1

V1

f i r e - p a r t s . c o m

Summary of Contents for DRL2000 Series

Page 1: ...un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installationetl entretiendoivent treassur spar un installateur ou...

Page 2: ...tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install pour la protection Des enfants et Des personnes risques Vea el volante...

Page 3: ...toca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidr...

Page 4: ...ion Preparation 17 Installation Installation Sequence 17 Construct the Fireplace Framing 17 Prepare the Fireplace Top Spacers 21 Route the Gas Supply Line to the Fireplace 21 Installing Header Shield...

Page 5: ...bir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po...

Page 6: ...rous Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon monoxide po...

Page 7: ...ccessibility clearance for service and proper operation Never obstruct the front openings of the appliance These appliances are designed as supplemental heaters Therefore it is advisable to have an al...

Page 8: ...a professional service person More frequent cleaning may be required due to excessive lint from carpeting bedding material etcetera It is imperative that control compartment burners and circulating a...

Page 9: ...tructions 900949 00 provided with this appliance Table 1 Input Rate BTU HR Gas Valves Burner Model Natural Gas Propane LP Gas Field Converted High Rate Low Rate High Rate Low Rate DRL2035 15 000 13 00...

Page 10: ...diminish 4 for every 1 000 ft of altitude IN CANADA CAN CGA 2 17 M91 HIGH ALTITUDE THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER S AUTHORIZED REPRESENTATIVE IN ACCORDANCE WITH THE REQUIREMENT...

Page 11: ...noxide detector must comply with NFPA 720 be ANSI UL 2034 listed and be ISA certified A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum h...

Page 12: ...urniture and draperies En raison des temp ratures lev es l appareil devrait tre install dans un endroit o il y a peu de circulation et loin du mobilier et des tentures The location should also be free...

Page 13: ...to 14 12 5 0 ft 1 52 m 14 12 to 16 12 6 0 ft 1 83 m 16 12 to 18 12 7 0 ft 2 13 m 18 12 to 20 12 7 5 ft 2 29 m 20 12 to 21 12 8 0 ft 2 44 m 12 X Roof pitch is X 12 2 ft minimum 2 ft minimum Lowest disc...

Page 14: ...onmechanical air supply inlet to building or the combustion air inlet to any other fireplace 6 150 mm for fireplaces 10 000 Btu h 3 kW 9 230 mm for fireplaces 10 000 Btu h 3 kW and 50 000 Btu h 15 kW...

Page 15: ...m 3 77 mm above any horizontal inclined vent component See Page 23 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it 6 153 mm if opti...

Page 16: ...nimum clearance requirements include any projections such as shelves window sills mantels etc above the fireplace NOTE To avoid heat related finish damage we recommend the use of high temperature pain...

Page 17: ...l Vent System Page 23 9 Install the Vent Restrictor if necessary Page 23 10 Connecting the Vent Pipe Page 25 11 Install the Vent System Page 28 Electrical Connection 12 Complete the Field Wiring Page...

Page 18: ...1 2 547 29 737 42 1067 18 458 N A A Minimum opening size additional 1 8 per side is recommended G For installations with 12 section directly off unit then elbow NOTE Framing specifications do NOT app...

Page 19: ...ith HeatFlo Kit for Recessed Wall Pocket E B A G H C F F D A B E G H C with HeatFlo Kit for Flush Wall with HeatFlo Kit for Recessed Wall Pocket E B A G H C F F D A B E G H C with HeatFlo Kit for Flus...

Page 20: ...replace Ceiling Wall HeatFlo Vent Opening B C A Min 76 1 930 m Max 20 ft 6 096 m Base of Fireplace Figure 6A Dimensions for Television TV Installed Above Fireplace on a Recessed Wall Pocket Television...

Page 21: ...kets NOTE DRL3535TEN and DRL3545TEN models require a 4 75 non combustible fireboard provided while DRL2035TEN and DRL2045TEN models require a 2 75 non combustible board provided The gas supply line sh...

Page 22: ...Step 1 Remove screw holding standoff to firebox bend to 4 tall as seen above and attach screw Step 2 Install the header shield by sliding it into the slot in the standoffs Step 3 Fireboard standoff ca...

Page 23: ...oved vent components See Pages 28 31 vertical and Pages 34 38 horizontal NOTE This fireplace must be vented directly to the outside WARNING The vent system may not service multiple appliances and must...

Page 24: ...rea raised Base Vent Restrictor Base Vent Restrictor Wing With break away raised Minimal Restrictor Vent Restrictor with Vertical Terminations When vertically terminating the vent system through the r...

Page 25: ...equired length The SV4 5LA Telescopic Vent Section has an effective length of from 1 1 2 to 7 38 to 178 mm The SV4 5LA is fitted with a locking inclined channel end identical to a normal vent section...

Page 26: ...ctions in Figure 18 NOTE Same installation applies if installed in a corner STEP 1 Locate the two 2 flat elbow shields STEP 2 Bend the three 3 tabs 90 degrees as shown below STEP 3 Attach the two 2 sh...

Page 27: ...5 38 75 0 0 0 0 10 10 69 5 75 0 0 0 2 0 2 475 5 39 625 0 1 0 0 10 11 73 5 6 125 1 0 0 2 0 3 480 40 1 1 0 0 10 12 79 5 6 625 0 1 0 2 0 3 492 41 1 0 1 0 10 12 81 6 75 0 0 0 1 1 2 499 5 41 625 0 0 0 1 10...

Page 28: ...figures Secure Flex pipe may also be used A table summarizes each configuration s minimum and maximum vertical and horizontal length parameters for a variety of applications 1 Refer to Figure 24 and T...

Page 29: ...living space above the ceiling level the firestop spacer must be installed on the bottom side of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side o...

Page 30: ...op and both sides of the flashing with waterproof caulking The flashing must overlap the roofing material along the bottom 11 Install the storm collar Install the storm collar supplied with the flashi...

Page 31: ...HF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible wall NOTE Two 2 45 elbows may be used in place of one 1 90 elbow The same rise to run ratios as shown in the...

Page 32: ...f H horizontal run up to a maximum horizontal run of 25 ft Minimum 6 ft and maximum of 60 ft of vertical venting Table 18 Top Vent Three Elbows H H1 Maximum V Minimum feet meters feet meters 5 1 524 E...

Page 33: ...t Length on Pages 25 27 for more information Plan the venting so that a joint does not occur in the ceiling or roof joists Allow for elbows Figure 18 Page 26 Maintain clearances to combustibles equal...

Page 34: ...the exterior side of the framing long side up with the 3 spacer clearance at the top Figure 27 Page 33 and nail into place This Wall Heatshield shall be installed using the provided burn screws on th...

Page 35: ...0K81 or high temperature silicone Figure 28 Venting Connection and Exterior Wall Recessing of the Horizontal Termination Use silicone caulking to seal the top and sides of the termination up to the un...

Page 36: ...able all the way to at or near level Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary NOTE SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer...

Page 37: ...ne Foot Vent Section Required When using Secure Flex use ceiling firestop spacer SF4 5VF When using Secure Flex use wall firestop spacer SF4 5HF Wall firestop spacer SV4 5HF Ceiling firestop spacer SV...

Page 38: ...hows a 1 V to 5 H ratio For every 1 ft of V vertical you are allowed 5 ft of H horizontal run up to a maximum horizontal run of 20 ft 6 096 m NOTE The Wall Heatshield provided shall be installed per i...

Page 39: ...ing the dimples down and along the incline channels until they seat at the end of the channels Figure 29 Flexible Vent Adaptor Figure 30 Flexible Vent Apply ONLY MIL PAC BLACK HIGH TEMPERATURE SEALANT...

Page 40: ...e flexible vent NOTE Ensure that the flexible vent is properly routed to provide the required clearance Do NOT allow the flexible vent to bend in a radius tighter than 5 127 mm Figure 30 Page 39 Place...

Page 41: ...pre wired at the factory for the Electronic wiring 2000 series Electronic Wiring DRL2000 series One of the following optional controls must be used ON OFF Wall Switch Thermostat or Remote Control See...

Page 42: ...an umbilical cord wiring harness Install a junction box not provided on the wall adjacent to the appliance within reach of the remote system umbilical cord wiring harness 7 After the wiring is complet...

Page 43: ...ectronic Gas Valve DRL3500 Series Pilot Tube COLOR CODE B BLACK BB BROWN W BLACK STRIPE BG BROWN W GREEN STRIPE BL BLUE BR BROWN G GREEN GY GRAY O ORANGE R RED W WHITE Y YELLOW Spark Electrode Flame S...

Page 44: ...ther tighten or refasten the leaking connection and then retest as described above 3 When the gas lines are tested and leak free rinse off the leak testing solution 13 Connect the Gas Line All codes r...

Page 45: ...it will take a few minutes for the gas line to purge itself of air When purged the pilot and burner will light and operate as indicated Subsequent lighting of the fireplace will not require purging I...

Page 46: ...e following fireplace functions Primary burner ON OFF Flame height and heat output adjustment six levels The receiver accepts commands via radio frequency from the transmitter and does not require lin...

Page 47: ...ooting black tip the air shutter opening may need to be adjusted If the air shutter opening is closed too far sooting may develop Sooting is indicated by black puffs developing at the tips of very lon...

Page 48: ...up to decrease it The rod is located in the lower control compartment Position the air shutter to the factory setting Table 25 2 Light the fireplace Follow the lighting procedure on the lighting label...

Page 49: ...f left hand side of unit and remove 2 screws or remove the barrier assembly and remove the front lower access panel 2 screws B If unit is installed with optional facade remove facade and follow Step A...

Page 50: ...bels at all fireplace operation and control points Page 51 NOTE The installer MUST ensure these warnings are properly attached during installation The warning labels are a critical means of informing...

Page 51: ...ollez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Choisissez la langue qui est principalement parl e dans la r sidence du propr...

Page 52: ...of Flashing 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 77L81 SV4 5SC6 Storm Collar 6 pack H6183 SV4 5HF5 Firestop Spacer 5 rigid H6184 SF4 5HF5 Fire...

Page 53: ...ion for flex with 24 610 mm of compressed flex vent see 750204M 94L07 SFKIT36SS Small Square Termination for flex with 36 914 mm of compressed flex vent see 750204M 94L08 SFKIT48SS SmallSquareTerminat...

Page 54: ...tte trousse L installation n est pas ad quate ni compl te tant que le bon fonctionnement de l appareil converti n a pas t v rifi selon les instructions du fabricant fournies avec la trousse Le fournis...

Page 55: ...by carbon monoxide than others including pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes NOTE Do not place furniture or othe...

Page 56: ...tato de pared quecontrolalachimenea verifiquequeelinterruptor opera la chimenea encendi ndola y apag ndola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta...

Page 57: ...smoke detector Do not operate the blower during the burn in period A white film may develop on the glass front during the first few fires as part of the burn in period The glass should be kept clean...

Page 58: ...vent sooting and performance IMPORTANT NOTE Not remove sticker until media is completely placed Verify pilot flame is not obstructed and the 1 2 clearance from pilot cover to burner is maintained Ensu...

Page 59: ...over Make certain not to drop glass down in between pilot cover and burner Figure 48 NOTE As crushed glass varies in size and installation it may be necessary to add or remove small amounts of glass t...

Page 60: ...talled AVERTISSEMENT Une barri re con ue pour r duire le risque de br lure par le hublot chaude est fournie avec l appareil et doit tre install WARNING Do not operate appliance with the glass front re...

Page 61: ...force When installed properly the bottom of the door should not have interference with the fireplace in order to close If it does remove the door and inspect the door gasket to ensure it is even and n...

Page 62: ...ing system components However more frequent periodic inspections and cleanings should be performed by the homeowner NOTE Prior to the first use of the fireplace and each burn season and periodically d...

Page 63: ...dia Vacuum out any foreign matter on the burner e g lint carbon etc Ensure the burner ports are free of debris NOTE Improper positioning of logs media can create carbon build up and will alter the per...

Page 64: ...ction Look for any signs of dislocation of the vent components Appliance Inspection Qualified Service Technician Perform the appropriate appliance inspection procedure detailed in this manual Maintena...

Page 65: ...inor scratches and discoloration of the fireplace black painted surfaces with the touch up paint kits PA I N T Glass Media Kits 5 lb Bag Cat No Model Description H8412 CRSHGL RBLK Reflective Black H84...

Page 66: ...120 OFF minutes Wall surface mounted Connects to wall switch wire Perfect for rental and resort applications Wall Switch Countdown Timer Cat No Model No Description H8863 WS S TMR Wall Switch Remote S...

Page 67: ...A This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand B BEFORE OPERATING smell all around the appliance area for gas Be sure...

Page 68: ...pe suivante 8 Mettez l appareil sous tension 9 Placez l interrupteur du r cepteur en position REMOTE 10 Appuyez sur le bouton ON OFF pour s lectionner ON 11 Ajustez le thermostat sur la t l commande l...

Page 69: ...y gas control which has been under water Electronic Gas Control Valve SIT Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may ha...

Page 70: ...peut avoir une batterie de secours installer les batteries au besoin 8 Placez l interrupteur du r cepteur en position REMOTE ou l interrupteur mural en position ON 9 Si applicable Appuyez sur le bouto...

Page 71: ...r call a service technician if required e Unit is not receiving power Replace unit battery backup 3 The main Burner comes on but then goes out a Fireplace has not established proper draft Switch CPI I...

Page 72: ...es Electronic DRL2000 series 19 19 14 13 15 17 16 18 Cat No Fireplace Model Shipping Wt Shipping Vol F4182 DRL2035TEN 101 lb 9 3 cu ft F4183 DRL3535TEN 101 lb 9 3 cu ft F4186 DRL2045TEN 126 lb 11 9 cu...

Page 73: ...432 1 F4433 1 8 Lintel F3656 1 F3658 1 F3656 1 F3658 1 F4429 1 F4429 1 9 Firebox Floor Front F4264 1 F4265 1 F4264 1 F4265 1 F4435 1 F4435 1 10 Convection Hood F3653 1 F3655 1 F3653 1 F3655 1 F4430 1...

Page 74: ...er for backup batteries Proflame I H8803 1 H8803 1 H8803 1 19 Gas Flex Line Connector with Shutoff 93L32 1 93L32 1 93L32 1 93L32 1 93L32 1 93L32 1 Pilot Assembly SIT Natural Gas H7268 1 H7268 1 H7268...

Page 75: ...or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damage...

Page 76: ...er Date fireplace was Installed Type of gas fireplace uses Dealer name Innovative Hearth Products IHP reserves the right to make changes at any time without notice in design materials specifications p...

Reviews: