Locate SW1, the switch on the left hand side.  Note the lettering above this switch
(DELAY – NO DELAY).  Setting this switch to DELAY will cause the TA44T to blink the ALARM 
and BELL ICONS when the Sensor temperature passes the threshold set by the Front Panel
Adjustment.  When approximately one hour has passed and the Sensor temperature has 
remained past the threshold set by the Front Panel Adjustment, the TA44T will sound the
audible alarm, close the N.O. relay contacts, and transmit the alarm code to the remote
receiver.  Should the temperature return to its normal value before this period has elapsed, 
the one-hour delay will be reset.  Setting this switch to NO DELAY will cause the TA44T to 
sound an immediate alarm, close the N.O. relay contacts, display the ALARM and BELL ICONS 
(Solid), and send an alarm code to the remote receiver, when the temperature passes the 
threshold set by the Front Panel Adjustment.  Should the temperature return to its normal value, 
the TA44T will automatically reset, and send a no alarm code to the remote receiver.

Locate the terminal strip below the switches.  This is where sensor probe, power supply and 
remote alarm are connected to the TA44T.  The TA44T comes from the factory with the power 
supply and sensor probe attached.  Note the 3 unused terminals on the right.  These are the 
relay contacts for use with external devices, such as remote alarms or automatic dialers.  
Since each installation has different requirements, it is suggested you consult the instructions 
supplied with any remote device prior to making any connections to the TA44T.  Note the 5 
Amp 120VAC rating of the relay contacts.  PERMANENT DAMAGE will result if these limits are 
exceeded.

TYPICAL CONNECTIONS ARE SHOWN IN THE DRAWING

USING MULTIPLE TRANSMITTERS AND RECEIVERS

Every TA44T transmitter and R10 receiver come preconfigured with a standard alarm
transmit code.  This means that if multiple TA44T units are installed at a location, if any of 
them generates an alarm, every R10 receiver at the same location will sound an alarm.  When 
more than one TA44T is installed at a location, it may be desirable for one or more
transmitters to transmit a unique alarm code, triggering different R10 receivers.

TA44 Manual.indd   5

5/8/2012   4:39:17 PM

Distributed by MicroDAQ.com, Ltd.                   www.MicroDAQ.com                   (603) 746-5524

Summary of Contents for TA44

Page 1: ...MOTE WIRELESS ALARM Sealed Unit Parts Co inc PO Box 21 2230 Landmark Place Allenwood NJ 08720 USA Phone 732 223 6644 Fax 732 223 1617 www supco com info supco com 19204 TA44 Manual indd 1 5 8 2012 4 39 15 PM Distributed by MicroDAQ com Ltd www MicroDAQ com 603 746 5524 ...

Page 2: ...y its state as follows In delayed alarm state the ALARM icon and the Bell will flash In the alarm state the ALARM icon and the Bell will remain solid The Bell clapper will flash Audible alarm will sound and the N O relay contacts will close The unit will transmit an alarm code to the wireless receiver causing the remote receiver to activate its audible alarm If the Silence button is pressed during...

Page 3: ...n the receiver should turn off When the R10 receiver sounds an alarm this alarm can be silenced by pressing the silence button on the receiver When the receiver received the No Alarm signal from the transmitter the silence state is reset and the receiver returns to normal operation SENSOR EXTENSION The TA44T sensor probe is designed to measure air temperature and may be mounted in any convenient l...

Page 4: ...mote receiver audible alarm as outlined above in the INSTALLATION AND REMOTE ALARM OPERATION section Set the temperature alarm threshold to the temperature the TA44T must respond to using the Up and Down buttons Typical values will be between 35 to 45 degrees for a refrigerator and 0 to 15 degrees for a freezer The setting of this adjustment will depend on the type of protection the TA44T is being...

Page 5: ... the terminal strip below the switches This is where sensor probe power supply and remote alarm are connected to the TA44T The TA44T comes from the factory with the power supply and sensor probe attached Note the 3 unused terminals on the right These are the relay contacts for use with external devices such as remote alarms or automatic dialers Since each installation has different requirements it...

Page 6: ...er code follow the steps below 1 Make sure an alarm condition is not present If possible turn off any other TA44T transmitters operating at the location 2 On the R10 receiver press and hold the Silence button until the Power and Alarm indicators start to flash 3 Let go of the Silence button 4 On the TA44T transmitter press the SILENCE button for about 1 second and then release it The Power and Ala...

Page 7: ...ff and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help The user is cautio...

Page 8: ...30 Landmark Place Allenwood NJ 08720 USA Phone 732 223 6644 Fax 732 223 1617 www supco com info supco com REV 03162012 P N22147 TA44 Manual indd 8 5 8 2012 4 39 17 PM Distributed by MicroDAQ com Ltd www MicroDAQ com 603 746 5524 ...

Reviews: