90
11.7.3
Procedure when using the SD3SOFT user software version 1.00 or later
1) Starting the PCs
2) Connection of X1 (electrical power supply with zone pair activated) and X2 (RS-232
cable 1:1)
3) Start
SD3SOFT
user software
4) Select the “Authorized user” access level
5) Confirm the echo data shown by the scanner
6) Click on the “Calibrate optical window monitoring” icon under “System data”
7) Start the optical window calibration with “Calibration” (lasts a few seconds, typically
with values between 100 and 700).
8) Click on the “Close” button