6.3. Мodel PS 2 - with two coils
PS 2
150
PS 2
200
Capacity
L
150
200
Height
H, mm
1310
1710
Minimal vertical clearance
mm
1400
1780
Diameter without insulation /with insulation
D, mm
Ø 400/500
Ø 400/500
Operating pressure/Max. buffer temperature
bar/
0
C
3/95
3/95
Operating pressure /Max. coil temperature
bar/
0
C
16/110
16/110
Recommended boiler size, connected to buffer tank
kW
6-10
6-10
Weight kg,
69
91
Sleeve for Electric heating element
В, mm, Rp1
1/2”
755
995
Heat carrier
С1, mm, Rp1
1/2”
185
185
Heat carrier
С2, mm, Rp1
1/2”
185
185
Heat carrier
С3, mm, Rp1
1/2”
485
725
Heat carrier
С4, mm, Rp1
1/2”
485
725
Heat carrier
С5, mm, Rp1
1/2”
885
1165
Heat carrier
С6, mm, Rp1
1/2”
885
1165
Heat carrier
С7, mm, Rp1
1/2
”
1125
1525
Heat carrier
С8, mm, Rp1
1/2
”
1125
1525
Sensor sleeve
А1, mm, Rp1/2”
185
185
Sensor sleeve
А2, mm, Rp1/2”
485
725
Sensor sleeve
А3, mm, Rp1/2”
885
1165
Sensor sleeve
А4, mm, Rp1/2”
1125
1525
Air vent sleeve
F, mm, Rp1
1/2
”
1310
1710
Capacity lower/upper coil S1/S2
S1/S2 L
6.8/4.1
9.9/6.2
Heat exchange surface S1/S2
S1/S2 m
2
1.1/0.66
1.6/1.0
Inlet/Outlet Lower coi S1
S1i/S1o, mm, Rp1”
705/185
945/185
Inlet/Outlet Upper coil S2
S2i/S2o, mm, Rp1”
1125/805
1525/1045
Summary of Contents for P 1500
Page 2: ...2 INSTALLATION and OPERATION MANUALINSTALLATION and OPERATION MANUAL ...
Page 8: ...8 INSTALLATION and OPERATION MANUALINSTALLATION and OPERATION MANUAL CONNECTIONS SCHEMES ...
Page 9: ...9 INSTALLATION and OPERATION MANUAL INSTALLATION and OPERATION MANUAL ...
Page 13: ...13 INSTALLATION and OPERATION MANUAL INSTALLATION and OPERATION MANUAL ...
Page 36: ...36 INSTALLATION and OPERATION MANUALINSTALLATION and OPERATION MANUAL 8 SHEMES t 65 C ...
Page 37: ...37 INSTALLATION and OPERATION MANUAL INSTALLATION and OPERATION MANUAL ...
Page 38: ...38 INSTALLATION and OPERATION MANUALINSTALLATION and OPERATION MANUAL ...
Page 43: ...INSTALLATION and OPERATION MANUAL INSTALLATION and OPERATION MANUAL ...
Page 44: ...ISO 9001 BUREAU VERITAS Certification tel 359 700 17 343 www burnit bg ...