6.9.4. Brazier’s periodic cleaning
When the stove is activated, the system automatically starts the brazier’s periodic
clearing.
With intervals as Timer
T07
(minutes) the Combustion is taken to Periodic Cleaning
Power according to parameters
C08
and
U08
for the Timer
T08
(seconds).
6.9.5. Automatic combustion power management
In the Combustion Power setting, the user can set the Automatic modality [
A
]
The work power is automatically selected according to the Water Temperature and
the value of the selected Boiler Thermostat:
• Water Temperature ≤
Boiler Thermostat–d08
→The system goes to the maximum available Combustion Power
•
Boiler Thermostat–d08
< Water Temperature <
Boiler Thermostat
→The Combustion Power decreases reaching the Boiler Thermostat
• Water Temperature
≥ Boiler Thermostat
→The system goes to Combustion Power 1 if
A06=0
or to Modulation Power
if
A06=1
Example
A06 = 1
Modality = [A]
Boiler Thermostat
=75 °C
d08
=
5 °C
P03 = 5
Water
Temperature°C
≤ 70
71
72
73
74
≥ 75
Work
Combustion
Power
Power 5
Power 4
Power 3
Power 2
Power 1
Power 1
6.9.6. Pellet Load Correction Management
The user could correct the Auger’s times ON of Pellet Loading in Step
– 7 ÷ 7
P15
is the percentage value of the single correction Step and is applied on the Work
default values.
C03=2,0
C03=1,8
C03=2,0
C03=2,0
C03=2,0
C03=2,0
C03=2,0
C03=2,0
C03=2,0
C03=1,8
C03=1,8
C03=1,8
C03=1,8
C03=1,8
C03=1,8
C03=1,8
The defined values are within the defined range
P27 ÷ P05