Installer / Service Manual BURNiT PM Comfort
Plus
27 –ЕN
P25=1: Encoder version >
values are in RPM
; P25=
0: No Encoder version >values are in VOLT.
The set or calculated values are automatically delimited between in the thresholds
P14
and
P30.
The fan of pellet stove has an integrated encoder. In this case, parameter
P25
must be set as
"1". To adjust the fan power must adjust the fan speed.
If the pellet stove operation is chosen without encoder, parameter
P25
must be set as "0".
Then adjust the fan in volts.
The settings in both cases are shown in the table below.
Code
Description
Min
Max
U
13kW 25kW
U01
Ignition Speed
0
230
Volt
145
160
300
2800
RPM
1600
1700
U02
Stabilization Speed
0
230
Volt
150
165
300
2800
RPM
1650
1700
U03
Power 1 Speed
0
230
Volt
100
120
300
2800
RPM
1100
1300
U04
Power 2 Speed
0
230
Volt
115
125
300
2800
RPM
1200
1400
U05
Power 3 Speed
0
230
Volt
125
145
300
2800
RPM
1250
1500
U06
Power 4 Speed
0
230
Volt
135
150
300
2800
RPM
1350
1650
U07
Power 5 Speed
0
230
Volt
155
165
300
2800
RPM
1450
1800
U08
Speed during the Periodic
Cleaning
0
230
Volt
200
200
300
2800
RPM
2000
2000
U09
Speed during the Extinguishing
0
230
Volt
220
220
300
2800
RPM
2350
2350
U10
Second ignition Speed
0
230
Volt
145
160
300
2800
RPM
1700
1800
U11
Modulation Speed
0
230
Volt
130
140
300
2800
RPM
1250
1750
P14
Combustion Fan Minimum Speed
0
230
Volt
90
100
300
2800
RPM
800
1000
P30
Combustion Fan Maximum
Speed
0
230
Volt
230
230
300
2800
RPM
2500
2500
P16
Correction Step Value of the
Combustion Fan Speed
1
20
[%]
3
3
P25
0
Combustion Fan no Encoder
0
2
[nr]
1
1
1
Combustion Fan with
Encoder
2
Combustion Fan with
Encoder whit automatic
Summary of Contents for BURNiT PM Comfort 13 Plus
Page 16: ...Installer Service Manual BURNiT PM Comfort Plus 16 N 6 2 Wiring controller Version 1 V1...
Page 17: ...Installer Service Manual BURNiT PM Comfort Plus 17 N 6 3 Wiring controller Version 2 V2...
Page 42: ...Installer Service Manual BURNiT PM Comfort Plus 42 N 6 9 9 Pressure Sensor Configuration...