29
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
12.2. Technical parameters
Table 4
Pell 300 Mega
Pell 500 Mega
Nominal heat output
kW
300
500
Min. / Max. heat output
kW
90÷300
150÷500
Average
power
consumption
Firing-Up mode
Operate mode
W
W
~ 980
~ 419
~ 1540
~ 550
Electric power supply V/Hz
~220/50
~220/50
Overall dimensions
Height H
Width L / Depth D
mm
555
1250/420
770
1370/520
Minimal recommended size of
boi ler combustion chamber
Height
Width
Depth
mm
350
390
550
350
450
550
Required chimney draught
Pa
30
30
Heat-output adjustment
P
P
Combustion Efficiency
Emitted heat
%
%
96
93
96
94
Weight of burner
kg
90
110
Burner body
Length
Width
Height
mm
mm
290
550
400
600
Feeder chute Diameter
mm
84
84
Built-in CPU control unit
P
P
Pellet auger Diameter
Length
mm
84
2000
84
2000
Flexible connection Diameter
Length
mm
mm
90
800
90