21
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
Select the desired option using the
navigation arrows. Use the „
Enter
”
button to open the next parameter. Use
the
button to open the next page of
the menu.
9.3.4. Burn Level
The burner has
three main levels of
burning
(three
main output modes
of operation). Use
this menu to set the temperature
differences at which the burner will shift
from higher output mode to lower (step
modulation).
Example:
We have set maximum
temperature of
85°С
. Upon reaching
75°С
, the burner will shift down to lower
mode of operation (
two flames
). Upon
reaching
80°С
, the burner enters into still
lower mode of operation (
one flame
).
Upon reaching
85°С
, the burner enters
into suspend mode (
Suspend
).
Select the desired option using the
navigation arrows. Use the „
Enter
”
button to open the next parameter. Use
the
button to open the next page of
the menu.
9.3.5. Setup of burning Level
This submenu
allows you to adjust
the parameters of
the
main
mode of
o p e r a t i o n
Maximum output
of the burner. It is
indicated by three flames
.
You can modify the pellet quantity
(Feed)
, time interval at which these
pellets are fed
(Cycle)
and fan output as a
percentage value
(FAN)
.
Example:
with the period set at
10
seconds, the pellet auger runs for
2
seconds feeding pellets in the burner,
and is off for
8
seconds.
Select the desired option using the
navigation arrows. Use the "
Enter
"
button to open the next parameter. Use
the
button to open the next page of
the menu.
In this submenu
you can adjust the
parameters of the
medium output
mode of operation
of the burner.
It is indicated by two flames
.
We recommend to set at
50%
of the main
mode.
You can modify the pellet quantity
(
Feed
), time interval at which these
pellets are fed (
Cycle
) and fan output as a
percentage value (
FAN
).
Example:
with the period set at
10
seconds, the pellet auger runs for
1
seconds feeding pellets in the burner,
and is off for
9
seconds.
Select the desired option using the
navigation arrows. Use the „
Enter
”
button to open the next parameter. Use
the
button to open the next page of
the menu.
In this submenu you
can adjust the
parameters of the
lowest output
mode
of operation of the
burner. It is indicated by one flame
.
We recommend to set at
10÷35%
of the
main mode.
You can modify the pellet quantity