TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
10
Table 1
European Certification of Wood Pellets for Heating Purposes
Parameters
Units
ENplus-A1
ENplus-A2
EN-B
Diameter
mm
6 (± 1)
8 (± 1)
6 (± 1)
8 (± 1)
6 (± 1)
8 (± 1)
Lenght
mm
15 ≤ L ≤ 40
1)
15 ≤ L ≤ 40
1)
15 ≤ L ≤ 40
1)
Bulk dentsity
kg / m
2
≥ 600
≥ 600
≥ 600
Calorific/heating value
MJ / kg
≥ 16,5-19
≥ 16,3-19
≥ 16,0-19
Humidity /moisture
Ма .-%
≤ 10
≤ 10
≤ 10
Dust
Ма .-%
≤ 1
3)
≤ 1
3)
≤ 1
3)
Mechanical durability
Ма .-%
≥ 97,5
4)
≥ 97,5
4)
≥ 96,5
4)
Ash
Ма .-%
2)
≤ 0,7
≤ 1,5
≤ 3,5
Melting point of ash
°C
≥ 1200
≥ 1100
-
Chlorine content
Ма .-%
2)
≤ 0,02
≤ 0,02
≤ 0,03
Sulfur content
Ма .-%
2)
≤ 0,03
≤ 0,03
≤ 0,04
Nitrogen content
Ма .-%
2)
≤ 0,3
≤ 0,3
≤ 1,0
Copper content
mg / kg
2)
≤ 10
≤ 10
≤ 10
Chromium content
mg / kg
2)
≤ 10
≤ 10
≤ 10
Arsenic content
mg / kg
2)
≤ 1,0
≤ 1,0
≤ 1,0
Cadmium content
mg / kg
2)
≤ 0,5
≤ 0,5
≤ 0,5
Mercury content
mg / kg
2)
≤ 0,1
≤ 0,1
≤ 0,1
Plumbum content
mg / kg
2)
≤ 10
≤ 10
≤ 10
Nickel content
mg / kg
2)
≤ 10
≤ 10
≤ 10
Zinc content
mg / kg
2)
≤ 100
≤ 100
≤ 100
1) Not more than 1% of the pellets may be longer than 40 mm, max. Length 45 mm;
2) Dry weight;
3) Particles <3.15 Mm, particulate matter, before handing over the goods;
4) Measurements with lignotester limit value ≥ 97,7% by weight.
7.1. Pellet burner connection to the fuel
hopper and pellet auger
Take the feeder chute flexible hose (from
the auger set). Using a bracket, clamp
one end of the hose onto the motor-end
outlet of the pellet auger.
- Remember – pellet auger must be
installed at 45° angle to the ground
horizontal surface.
- Fill the hopper with fuel (see table 1 for
parameters of the fuel types used)
- Plug the power cord of the pellet auger
into the indicated Schuko-type burner
socket on the left side of the
Electric
control box housing.