7.3. GDFI Fault
Before the inverter connects to the Grid, it will detect the impedance (effective resistance) of the solar PV
+ to Ground, and the impedance of the solar PV - to ground. If any of the impedance values are less than
33kΩ, the inverter will not connect to the Grid and will report an error F24 on its LCD.
The inverter is low maintenance. However, it is important that at least twice a year (for dusty environments
this may need to be carried out weekly) all the cooling fans, air ducts are cleaned and dust free.
Check if there are no fault codes and Lithium battery communication is correct.
Weekly cleaning statement: Suggest micromesh filters as an available option, micro ants here are a real
problem.
APPENDIX A
The following table is the connection on
battery side
:
8. MAINTENANCE
Protocol
Description
CAN
Pin 1:
CAN-H
Pin 5: CAN-L
Pin 2, 3, 4, 6, 7, 8: NC
RS485
Pin 1: RS485B
Pin 2: RS485A
Pin 3, 6: GND
Pin 7: RS485A
Pin 8: RS485B
Pin 4, 5: NC
RS232
Pin 3: BMS transmit; Computer receiver
Pin 4: BMS receiver; Computer transmit
Pin 5: GND
Pin 1, 2, 6: NC
Summary of Contents for SUNSYNK MAX
Page 4: ...MAX User Manual 4 APPENDIX A 68 APPENDIX B 69 APPENDIX C 69 APPENDIX D 69 APPENDIX E 70...
Page 9: ...MAX User Manual 9 2 1 Product Size...
Page 17: ...MAX User Manual 17 4 5 Function Port Definition for neutral earth bonding...
Page 21: ...MAX User Manual 21...
Page 23: ...MAX User Manual 23 4 9 1 Recommended AC Surge Protector...
Page 27: ...MAX User Manual 27 4 13 Wiring System for Inverter...
Page 32: ...MAX User Manual 32 4 18 Diesel Generator Connection Diagram...
Page 63: ...MAX User Manual 63 6 OPERATING MODES 6 1 Mode I Basic 6 2 Mode II With Generator...
Page 64: ...MAX User Manual 64 6 3 Mode III With Smart Load 6 4 Mode IV AC Couple...
Page 65: ...MAX User Manual 65...
Page 71: ...Ltd wered by Po...