MAX | User Manual
45
What you can do from this page:
Set up you Lithium-ion battery.
After installing a lithium battery, check on the communications page by clicking on the ‘Li BMS’ icon to see if
the BMS information is visible. If some information is not displayed correctly (it should look like the diagram
below) then there will be a communication error.
Therefore, if a communication error occurs:
1. Check that your data cable is the correct type.
2. Check that the data cable is plugged into the correct sockets. Usually, RS485 is employed, but some bat
-
tery manufacturers use others.
PLEASE NOTE
With some types of lithium battery, the BMS cannot be controlled by the Sunsynk inverter. In this case,
treat the battery as a lead-acid type and set the charging and
discharging protocol
following the bat-
tery manufacturer specification.
It is important to refer to the manuals that manufacturers produce for their batteries. That way, the chance
of errors occurring during installation are greatly reduced. Below there is a list of batteries that has been
examined, tested, and approved by Sunsynk.
Brand
Model
48V
Storage
Inverter
RS485
or CAN
Inverter
Setup
Notes
DYNESS
B4850
CAN
0
POWERBOXF
0
SolarMD
SS4074
CAN
0
To be used with V2 Logger
http://solarmd.co.za/
inverter-compatibility-so-
larmd/ sunsynk-and-solar-
md/
SS4037
0
SS202
0
SHOTO
SDC10-Box 5
CAN
0
Summary of Contents for SUNSYNK MAX
Page 4: ...MAX User Manual 4 APPENDIX A 68 APPENDIX B 69 APPENDIX C 69 APPENDIX D 69 APPENDIX E 70...
Page 9: ...MAX User Manual 9 2 1 Product Size...
Page 17: ...MAX User Manual 17 4 5 Function Port Definition for neutral earth bonding...
Page 21: ...MAX User Manual 21...
Page 23: ...MAX User Manual 23 4 9 1 Recommended AC Surge Protector...
Page 27: ...MAX User Manual 27 4 13 Wiring System for Inverter...
Page 32: ...MAX User Manual 32 4 18 Diesel Generator Connection Diagram...
Page 63: ...MAX User Manual 63 6 OPERATING MODES 6 1 Mode I Basic 6 2 Mode II With Generator...
Page 64: ...MAX User Manual 64 6 3 Mode III With Smart Load 6 4 Mode IV AC Couple...
Page 65: ...MAX User Manual 65...
Page 71: ...Ltd wered by Po...