4.11. Earth Connection (MANDATORY)
An Earth Cable shall be connected to the earth plate on the grid size in order to prevent electric shock if the
original protective conductor fails.
All neutrals can be linked together to maintain the neutral bond. When a Neural Earth bond is required for
an ‘Off-grid’ operation, then it has to be removed on ‘Grid-Tied’ operation.
If an Earth Bond is required between neutral and earth and your system is a hybrid system, then you can
have a permanent earth wire since this can cause faults with an RCD before the inverter.
Since the inverter is a true hybrid, then the bond must only be made when the inverter is operating in Island
-
ing Mode. To accommodate this, Sunsynk provides an AC output, which is connected to the A/T/S connec
-
tions whenever the inverter is running on Island Mode. Therefore, you can simply connect the coil of an AC
relay to the ATS 240 connections. Next, you need to select Signal Island Mode on the battery charge menu
(click on the gear icon -> battery icon), as shown in the figure below.
Summary of Contents for SUNSYNK MAX
Page 4: ...MAX User Manual 4 APPENDIX A 68 APPENDIX B 69 APPENDIX C 69 APPENDIX D 69 APPENDIX E 70...
Page 9: ...MAX User Manual 9 2 1 Product Size...
Page 17: ...MAX User Manual 17 4 5 Function Port Definition for neutral earth bonding...
Page 21: ...MAX User Manual 21...
Page 23: ...MAX User Manual 23 4 9 1 Recommended AC Surge Protector...
Page 27: ...MAX User Manual 27 4 13 Wiring System for Inverter...
Page 32: ...MAX User Manual 32 4 18 Diesel Generator Connection Diagram...
Page 63: ...MAX User Manual 63 6 OPERATING MODES 6 1 Mode I Basic 6 2 Mode II With Generator...
Page 64: ...MAX User Manual 64 6 3 Mode III With Smart Load 6 4 Mode IV AC Couple...
Page 65: ...MAX User Manual 65...
Page 71: ...Ltd wered by Po...