Operation of LCD Menu
10
61
Parameter
Explanation
Ⅰ
-Min -V. time
Stage
Ⅰ
Grid under -voltage tripping time
Ⅱ
-Min -V. grid
Stage
Ⅱ
Grid under -voltage
Ⅱ
-Min -V. time
Stage
Ⅱ
Grid under -voltage tripping time
Max-F. prote
Maximum protection frequency
Ⅰ
-Max-F. grid
Stage
Ⅰ
Grid over-frequency
Ⅰ
-Max-F. time
Stage
Ⅰ
Grid over-frequency tripping time
Ⅱ
-Max-F. grid
Stage
Ⅱ
Grid over-frequency
Ⅱ
-Max-F. time
Stage
Ⅱ
Grid over-frequency tripping time
Min-F. prote
Minimum protection frequency
Ⅰ
-Min-F. grid
Stage
Ⅰ
Grid under-frequency
Ⅰ
-Min -F. time
Stage
Ⅰ
Grid under-frequency tripping time
Ⅱ
-Min -F. grid
Stage
Ⅱ
Grid under-frequency
Ⅱ
-Min -F. time
Stage
Ⅱ
Grid under-frequency tripping time
If change the Country selected, the protective settings will be available after restart of
the inverter.
10.16
Communication Parameters Settings
If there is more than one inverter to communicate with a PC or a data logger, it is
crucial to configure communication parameters of each inverter.
You can set address for inverters and choose the communication protocol as the
following indications. The default protocol is Modbus protocol.
Summary of Contents for SG2K5TL
Page 2: ......
Page 6: ......
Page 10: ...IV...
Page 16: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 6...
Page 60: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 50 10 3 Overview of Complete LCD Menu Fig 10 1 Menu Tree...
Page 76: ...66 Temperature Derating Curve 1 0 2 45 60 Pnom P U Ambient temperature C...
Page 79: ......