SG2K5TL/SG3KTL/SG4KTL-31
User Manual
32
PV arrays produce electrical energy when exposed to light and thus can create
an electrical shock hazard. Wiring of the PV arrays should only be performed by
qualified personnel.
Prior to connecting PV array to inverter, the following specifications of PV arrays
should be met:
Type
DC Power Limit
Open-circuit Voltage
Limit
Short-circuit Current
Limit
SG2K5TL-31 2.8kW
500V
19A
SG3KTL-31 3.3kW
500V
23A
SG4KTL-31 4.4kW
500V
25A
There is a risk of inverter damage! Exceeding the above specification
requirements will cancel any and all warranty and liability claims.
The three PV strings connected to inverter should also meet the following
requirements:
z
The same number of PV modules in each PV string
z
The same type of PV modules
z
The identical inclination angle of all PV modules
z
The identical azimuth angle of all PV modules
6.4.1
Assembling DC Cable to Connector
DC cables from PV strings should be equipped with DC connectors. Pairs of DC
connectors are supplied in the scope of delivery.
To maintain IP65 weatherproof function of inverter, only the supplied DC connectors
or the connectors of the same protection class can be used.
DC Cable Requirements
Cross-section Area Range
Max. Withstand Voltage
Max. Withstand Current
2.5~4mm
2
500V
Same with short-circuit current
The positive and negative connectors, marked with polarity symbols will be
assembled with colored cables as the following procedures:
Summary of Contents for SG2K5TL
Page 2: ......
Page 6: ......
Page 10: ...IV...
Page 16: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 6...
Page 60: ...SG2K5TL SG3KTL SG4KTL 31 User Manual 50 10 3 Overview of Complete LCD Menu Fig 10 1 Menu Tree...
Page 76: ...66 Temperature Derating Curve 1 0 2 45 60 Pnom P U Ambient temperature C...
Page 79: ......