User Manual
101
Parameter
Range
Default
AC under-frequency level 2 protection value 53.00Hz -59.90Hz
57.00Hz
AC over-frequency level 2 protection value
65.00Hz -62.00Hz
60.50Hz
AC under-voltage level 2 protection time
0s-600s
0.16s
AC over-voltage level 2 protection time
0s-600s
0.16s
AC under-frequency level 2 protection time
0s-600s
0.16s
AC over-frequency level 2 protection time
0s-600s
0.16s
AC under-voltage level 3 protection value
477V-826V
720V
AC under-voltage level 3 protection time
0s-600s
0.16s
Proceed to set the protection recovery value after setting the
single-stage/multi-stage protection stage.
Tab. 10-9
Description of protection recovery parameters
Parameter
Explanation
Range
Default
Vmax-recover Max. protection
recovery voltage
600.0V- 738.0V
657V
Vmin-recover Min. protection
recovery voltage
60.0V- 600.0V
531V
Fmax-recover Max. protection
recovery frequency
60.00Hz-65.00Hz
60.49Hz
Fmin-recover
Min. protection
recovery frequency
50.00Hz-60.00Hz
59.81Hz
* Please follow the rules below to set parameters
:
AC under-voltage level 1 protection value
≥
AC under-voltage level 2 protection
value
≥
AC under-voltage level 3 protection value;
AC over-voltage level 1 protection value
≤
AC over-voltage level 2 protection
value
≤
AC over-voltage level 3 protection value;
AC under-frequency level 1 protection value
≥
AC under-frequency level 2
protection value
≥
AC under-frequency level 3 protection value;
AC over-frequency level 1 protection value
≤
AC over-frequency level 2
protection value
≤
AC over-frequency level 3 protection value;
AC under-voltage level 1 protection time
≥
AC under-voltage level 2 protection
time
≥
AC under-voltage level 3 protection time;
AC over-voltage level 1 protection time
≥
AC over-voltage level 2 protection time
Summary of Contents for SG125HV
Page 2: ......
Page 11: ...IX 11 4 Contact Information 109...
Page 12: ......
Page 24: ...1 Safety Instructions User Manual 12 service d utilisateur avant l utilisation...