41
step 4 Seal the unused PV terminals with the terminal caps.
If the PV string is equipped with the optimizer, please refer to the optimizer manual
for electrical connections and make sure that the polarity of the optimizer cables is
correct.
- - End
5.7
WiNet-S Connection
The WiNet-S module supports Ethernet communication and WLAN communication. It is not
recommended to use both communication methods at the same time.
For details, see the quick guide for the WiNet-S module. Scan the following QR code for the
quick guide.
5.7.1 Ethernet Communication
step 1
(Optional)
Strip the insulation layer of the communication cable with an Ethernet wire strip-
per, and lead the corresponding signal cables out. Insert the stripped communication cable
into the RJ45 plug in the correct order, and crimp it with a crimper.
1: RJ45 plug
2: Protective cap
Skip this step if a standard network cable with RJ45 plug is prepared.
step 2 Unscrew the swivel nut from the communication module and take out the inner sealing ring.
User Manual